Further information for Schneider Electric 28912 power disconnector 3P 160A
Complementary
Control type
Rotary handle
Handle colour
Black
Mounting mode
Fixed
Mounting support
Plate; DIN rail
Upside connection
Front
Downside connection
Front
Maximum power
AC-23: 110 kW at 500/525 V AC 50/60 Hz; AC-23: 45 kW at 220/240 V AC 50/60 Hz; AC-23: 75 kW at 380/415 V AC 50/60 Hz; AC-23: 90 kW at 440 V AC 50/60 Hz; AC-23: 90 kW at 660/690 V AC 50/60 Hz
Rated duty
Uninterrupted
Intermittent duty class
Class 120 - 60 %
[Icw] rated short-time withstand current
1 kA during 30 s conforming to IEC 60947-3; 1.23 kA during 20 s conforming to IEC 60947-3; 3.175 kA during 3 s conforming to IEC 60947-3; 5.5 kA during 1 s conforming to IEC 60947-3
Mechanical durability
15000 cycles
Electrical durability
AC-22A: 1500 cycles 220/240 V AC 50/60 Hz; AC-22A: 1500 cycles 380/415 V AC 50/60 Hz; AC-22A: 1500 cycles 440 V AC 50/60 Hz; AC-22A: 1500 cycles 500 V AC 50/60 Hz; AC-23A: 1500 cycles 220/240 V AC 50/60 Hz; AC-23A: 1500 cycles 380/415 V AC 50/60 Hz; AC-23A: 1500 cycles 440 V AC 50/60 Hz; AC-23A: 1500 cycles 500 V AC 50/60 Hz; DC-22A: 1500 cycles 125 V DC 2 poles in series; DC-23A: 1500 cycles 125 V DC 2 poles in series; AC-22A: 1500 cycles 690 V AC 50/60 Hz; AC-23A: 1500 cycles 690 V AC 50/60 Hz
Connection pitch
30 mm
Height
100 mm
Width
135 mm
Depth
62.5 mm
Net weight
0.8 kg
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-3; IEC 60947-1
Product certifications
CCC; KEMA-KEUR
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Logistical informations
Country of origin
PL
Main
Range
ComPact
Product name
ComPacT INS
Product or component type
Switch disconnector
Poles description
3P
Network type
DC; AC
Network frequency
50/60 Hz
[Ie] rated operational current
AC-22A: 160 A AC 50/60 Hz 220/240 V; AC-22A: 160 A AC 50/60 Hz 380/415 V; AC-22A: 160 A AC 50/60 Hz 440/480 V; DC-22A: 160 A DC 125 V 2 poles in series; AC-22A: 160 A AC 50/60 Hz 500 V; AC-22A: 160 A AC 50/60 Hz 660/690 V; AC-23A: 100 A AC 50/60 Hz 660/690 V; AC-23A: 160 A AC 50/60 Hz 220/240 V; AC-23A: 160 A AC 50/60 Hz 380/415 V; AC-23A: 160 A AC 50/60 Hz 440/480 V; AC-23A: 160 A AC 50/60 Hz 500 V; DC-23A: 160 A DC 125 V 2 poles in series
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
160 A at 60 °C
[Icm] rated short-circuit making capacity
154 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz; 20 kA switch-disconnector alone 690 V AC at 50/60 Hz
[Ue] rated operational voltage
125 V DC; 690 V AC 50/60 Hz
Pollution degree
3
Suitability for isolation
Contact position indicator
Visible break
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
13.500 cm
Package 1 Width
11.500 cm
Package 1 Length
15.500 cm
Package 1 Weight
1.019 kg
Unit Type of Package 2
S03
Number of Units in Package 2
10
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
10.594 kg
Unit Type of Package 3
P12
Number of Units in Package 3
80
Package 3 Height
43.000 cm
Package 3 Width
80.000 cm
Package 3 Length
120.000 cm
Package 3 Weight
95.552 kg
Compact INS load-break switch. Load-break switch INS160, 160A/690V AC / 250V DC, black rotary drive. Rated current 160 A, number of poles 3. Complete devices with black switch lever. Disconnecting properties in accordance with VDE 0660 Part 100. Rotary drive on the front or side up to INS250.