Further information for Schneider Electric 21113 motor protection switch 3p 25A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
440 V AC 50/60 Hz; 230...240 V AC 50/60 Hz; 400...415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 690 V AC 50/60 Hz
Magnetic tripping limit
12 x In
[Ics] rated service breaking capacity
2.25 kA conforming to EN/IEC 60947-2 - 690 V AC 50/60 Hz; 3 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 3 kA conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 50 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz; 6 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Control type
Toggle; Manual tripping test
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
5
Height
89 mm
Width
45 mm
Depth
70 mm
Net weight
0.26 kg
Electrical durability
AC-3: 100000 cycles AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to EN/IEC 60947-2; 4 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category
AC-3 conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.000 cm
Package 1 Width
8.500 cm
Package 1 Length
9.500 cm
Package 1 Weight
286.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
24
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
7.152 kg
The P25M motor protection circuit breaker from Schneider Electric, type 21113, is a circuit breaker from the Acti 9 series, specifically designed for use in three-phase installations for the protection function of electric motors. The device features a 3-pole configuration (3P) with a rated current of 25 A and is designed for alternating and three-phase current applications. The tripping technology is based on a thermomagnetic principle, responding to both overloads and short circuits. The K curve defines the tripping characteristic, with the magnetic tripping threshold set at 12 times the rated current. This ensures precise and reliable disconnection during sudden current surges.
Applications
The switch is intended for use in industrial and commercial installations, particularly for the protection function of electric motors. The usage category AC-3 according to IEC 60947-2 makes it suitable for operation with three-phase motors, with an electrical life of 100,000 switching cycles. The operating voltage includes several nominal voltages: 230–240 V, 400–415 V, 440 V, 500 V, and 690 V AC at 50/60 Hz. The rated insulation voltage is 690 V AC, confirming suitability for insulation requirements as per IEC 60947-2. The operating temperature ranges from -20 °C to 60 °C, with storage temperature from -40 °C to 80 °C. The maximum operating altitude is 2,000 m above sea level.
Functions and Equipment in Detail
The device features a contact position indicator, visually signaling the state of the contacts (ON/OFF). This enables safe work on downstream parts of the installation, as fully open contacts are indicated by the OFF marking on the toggle handle. Control is performed via a toggle switch, supplemented by a manual trip test, which allows checking the functionality of the tripping unit. The integrated locking mechanism enables secure locking of the switch, for example, during maintenance work. The terminals are designed for cable cross-sections from 1 to 6 mm² (rigid and flexible), with a tightening torque of 1.7 Nm. The terminals are rated to IP20.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping element. The thermal part responds to sustained overloads by activating the tripping mechanism through thermal expansion. The magnetic part immediately disconnects during sudden, high current surges (short circuit). The breaking capacities vary depending on voltage level: 50 kA at 230–240 V, 15 kA at 400–415 V, 6 kA at 440 V, 4 kA at 500 V, and 3 kA at 690 V AC. The rated operational breaking capacities are 50 kA (230–240 V), 6 kA (400–415 V), 3 kA (440 V and 500 V), and 2.25 kA (690 V). The overvoltage category III and drip proof class 2 (according to IEC 60947-2) ensure reliable operation under industrial conditions.
Compatibility and Accessories
The switch is designed to be mounted on a 35 mm symmetrical DIN rail and conforms to the 9 mm pitch, with a height of 89 mm, width of 45 mm, and depth of 70 mm. It is compatible with various accessory modules, including overvoltage tripping units (e.g. 21129 for 220/240 V, 21130 for 380/415 V), load current tripping units (e.g. 21127, 21128), auxiliary contacts (e.g. 21120, 21121, 21116, 21119), and short-circuit current limiters (e.g. 21115). These modules extend functionality, for example, by adding signaling, fault tripping, or current monitoring.
Mounting and Installation
Mounting is done on a standard 35 mm DIN rail, with an installation width of 5 pitches (45 mm). Power supply is possible from both top and bottom, increasing flexibility during installation. The snap-action switching ensures wear-free switching of contacts. The locking options allow secure securing of the device, for example, during maintenance work. Relative humidity up to 95 % at 55 °C is permissible.
Advantages in Operation
The switch offers high operational safety through the combination of thermal and magnetic tripping. Clear indication of switching position and integrated locking increase safety during maintenance work. The high electrical life of 100,000 cycles under AC-3 operation ensures long service life. Compatibility with various accessory modules allows flexible adaptation to specific requirements. Certifications according to EN/IEC 60947-2, as well as product certifications by DEMKO, FIMKO, NEMKO, SEMKO, and CEBEC, confirm compliance with international standards.