Further information for Schneider Electric 18895 load isolator 4-pole 100A
Additional features
[Ie] Rated operational current
100 A at 500 V AC 50/60 Hz
[Ue] Operational rated voltage
500 V AC 50/60 Hz
[Icm] Rated short-circuit making capacity
2 kA load isolator alone
[Icw] rated short-time current withstand
1.5 kA for 50 ms, corresponds to IEC 60947-3
[Ui] Rated insulation voltage
690 V AC 50/60 Hz compliant with IEC 60947-3
[Uimp] Rated impulse voltage withstand
8 kV corresponds to IEC 60947-3
Control type
Toggle switch; Manual trip test
Local signalling
ON/OFF indicator; trip indicator
Mounting mode
Fixed
Mounting bracket
35 mm symmetrical DIN rail
9-mm pitch
12
Height
103 mm
Width
108 mm
Depth
81 mm
Product weight
0,96 kg
Colour
Black
Mechanical life
20000 cycles
Electrical lifetime
Category A (except AC20, DC20): 1500 cycles AC 50/60 Hz according to IEC 60947-3; Category B (except AC20, DC20): 300 cycles AC 50/60 Hz according to IEC 60947-3
Provisions for padlocks
Lockable
Description of locking options
Integrated locking
Connections - terminals
Tunnel terminals (top or bottom) 10…50 mm² flexible
Wire stripping length
Circuit: 20 mm for top or bottom connection
[M] tightening torque
Circuit: 6 Nm top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti 9 NG125NA
Product or component type
Disconnect switch
Device short name
NG125NA
Device application
distribution; switching on and off under load
Pole description
3P + N
Neutral position
Left
Number of protected poles
4
Application category
AC-22A corresponds to IEC 60947-3; AC-22B corresponds to IEC 60947-3; AC-23B corresponds to IEC 60947-3
Suitability for insulation
Yes, complies with IEC 60947-3
Mounting
Standards
EN 60947-3; IEC 60947-3
Degree of protection (IP)
IP20 corresponds to IEC 60529; IP40 corresponds to IEC 60529
Degree of protection (IK)
IK05
Pollution degree
3 corresponds to IEC 60947-3
Drip-proof
2 corresponds to IEC 60068-1
Operating ambient temperature
-10…60 °C
Ambient temperature during storage
-40…70 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
8,4 cm
VPE 1 width
12,2 cm
VPE 1 length
15,6 cm
Packaging weight (Lbs)
1,026 kg
VPE 2 type
S03
VPE 2 quantity
12
VPE 2 height
30 cm
VPE 2 width
30 cm
VPE 2 length
40 cm
VPE 2 weight
12,99 kg
Circuit breaker Acti 9 NG125LMA, 50kA (IEC/EN 60947-2). 3-pole, nominal current 40A, MA characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 690V AC. Protection of the circuit against short-circuit currents. Protection of the circuit against overload currents. Tripping is indicated by the middle position of the switch knob and by a red, mechanical display on the front of the device. Test button for checking the tripping mechanism. Power supply from above or below. Snap action for low-wear switching of the contacts. Technology of the tripping unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. The NG125LMA circuit breaker meets the following standards - IEC/EN 60947-2.