Further information for Schneider Electric 18870 motor protection switch 2-pole 10A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
380 - 415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic trip threshold
12 x In
[Ics] Rated operational breaking capacity
75 kA 75 % corresponds to EN/IEC 60947-2 - 220 - 240 V AC 50/60 Hz; 37.5 kA 75 % corresponds to EN/IEC 60947-2 - 380 - 415 V AC 50/60 Hz; 30 kA 75 % corresponds to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 11.25 kA 75 % corresponds to EN/IEC 60947-2 - 500 V AC 50/60 Hz
Compatibility of comb rails and distribution blocks
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti 9 NG125LMA
Product or component type
Miniature circuit breaker (MCB)
Device short name
NG125LMA
Device application
Motor
Pole description
2P
Number of protected poles
2
[In] Rated current
10 A at 40 °C
Type of network
AC
Trigger technology
Magnetic
Cam disc
MA
Breaking capacity
100 kA Icu at 220 - 240 V AC 50/60 Hz corresponds to EN/IEC 60947-2; 40 kA Icu at 440 V AC 50/60 Hz corresponds to EN/IEC 60947-2; 50 kA Icu at 380 - 415 V AC 50/60 Hz corresponds to EN/IEC 60947-2; 15 kA Icu at 500 V AC 50/60 Hz corresponds to EN/IEC 60947-2
Application category
Category A corresponds to IEC 60947-2
Suitability for insulation
Yes, complies with IEC 60947-2
Standards
EN/IEC 60947-2
Mounting
Degree of protection (IP)
IP20 complies with IEC 60529
Degree of protection (IK)
IK05 corresponds to EN/IEC 62262
Pollution degree
3 corresponds to IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2.000 m
Operating ambient temperature
-30…70 °C
Ambient temperature during storage
-40…70 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
5,8 cm
VPE 1 width
8,1 cm
VPE 1 length
11 cm
Packaging weight (Lbs)
485 g
VPE 2 type
BB1
VPE 2 quantity
6
VPE 2 height
9,1 cm
VPE 2 width
11,9 cm
VPE 2 length
36,1 cm
VPE 2 weight
2,91 kg
VPE 3 type
S03
VPE 3 quantity
36
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
17,947 kg
Acti 9 NG125L circuit breaker, 50kA (IEC/EN 60947-2). 4-pole, nominal current 20A, D characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 690V AC. Protection of the circuit against short-circuit currents. Protection of the circuit against overload currents. Tripping is indicated by the middle position of the switch knob and by a red, mechanical display on the front of the device. Test button for checking the tripping mechanism. Power supply from above or below. Snap action for low-wear switching of the contacts. Technology of the tripping unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. The NG125L circuit breaker meets the following standards - IEC/EN 60947-2.