Further information for Schneider Electric 18841 power switch 2-pole 20A
Additional features
Network frequency
50/60 Hz
[Ue] Operational rated voltage
380 - 415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 220 - 240 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic trip threshold
12 x inch +/-20 %
[Ics] Rated operational breaking capacity
75 kA 75 % according to EN/IEC 60947-2 - 220 - 240 V AC 50/60 Hz; 37.5 kA 75 % according to EN/IEC 60947-2 - 380 - 415 V AC 50/60 Hz; 30 kA 75 % according to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 11.25 kA 75 % according to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 50 kA 100 % according to EN/IEC 60947-2 - 250 V DC
Compatibility of comb rails and distribution blocks
Contractual warranty
Warranty (in months)
18
Main features
Product series
Acti9
Product name
Acti9 NG125
Product or component type
Miniature circuit breaker (MCB)
Device short name
NG125L
Device application
Distribution
Pole description
2P
Number of protected poles
2
Neutral position
Left
[In] Rated current
20 A at 40 °C
Type of network
DC; AC
Trigger technology
Thermal-magnetic
Cam disc
D
Breaking capacity
100 kA Icu at 220 - 240 V AC 50/60 Hz complies with EN/IEC 60947-2; 40 kA Icu at 440 V AC 50/60 Hz complies with EN/IEC 60947-2; 50 kA Icu at 380 - 415 V AC 50/60 Hz complies with EN/IEC 60947-2; 15 kA Icu at 500 V AC 50/60 Hz complies with EN/IEC 60947-2; 36 kA Icu at
Application category
Category A corresponds to IEC 60947-2
Suitability for insulation
Yes, complies with IEC 60947-2
Standards
EN/IEC 60947-2
Mounting
Degree of protection (IP)
IP20 complies with IEC 60529
Degree of protection (IK)
IK05 corresponds to EN/IEC 62262
Pollution degree
3 corresponds to IEC 60947-2
Over voltage category
IV
Drip-proof
2 corresponds to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2.000 m
Operating ambient temperature
-30…70 °C
Ambient temperature during storage
-40…70 °C
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
8,3 cm
VPE 1 width
5,5 cm
VPE 1 length
10,8 cm
Packaging weight (Lbs)
478 g
VPE 2 type
BB1
VPE 2 quantity
6
VPE 2 height
9 cm
VPE 2 width
11,5 cm
VPE 2 length
35,6 cm
VPE 2 weight
2,948 kg
VPE 3 type
S03
VPE 3 quantity
36
VPE 3 height
30 cm
VPE 3 width
30 cm
VPE 3 length
40 cm
VPE 3 weight
18,175 kg
Circuit breaker Acti 9 NG125L, 50kA (IEC/EN 60947-2). 1-pole, nominal current 20A, D characteristic, operating voltage (Ue) 220-240V AC, insulation voltage (Ui) 690V AC. Protection of the circuit against short-circuit currents. Protection of the circuit against overload currents. Tripping is indicated by the middle position of the switch knob and by a red, mechanical display on the front of the device. Test button for checking the tripping mechanism. Feed from above or below. Snap action for low-wear switching of the contacts. Technology of the tripping unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. The NG125L circuit breaker meets the following standards - IEC/EN 60947-2.