Further information for Schneider Electric 18720 power switch 2-pole C 50A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
380...415 V AC 50/60 Hz; 500 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 440 V AC 50/60 Hz;
Magnetic tripping limit
8 x In +/- 20 %
[Ics] rated service breaking capacity
52.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 27 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 22.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 9 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 25 kA 100 % conforming to EN/IEC 60947-2 -
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
Control type
Manual tripping test; Toggle
Local signalling
ON/OFF indication; Trip indicator
Mounting mode
Clip-on
Mounting position
Vertical
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
6
Height
103 mm
Depth
81 mm
Width
54 mm
Net weight
0.48 kg
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Locking options description
Integrated padlocking
Connections - terminals
Tunnel type terminals1.5…50 mm² rigid; Tunnel type terminals1…35 mm² flexible
Wire stripping length
20 mm
Tightening torque
3.5 N.m
Earth-leakage protection
Separate block
Contact position indicator
Comb busbar and distribution block compatibility
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK05 conforming to EN/IEC 62262
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…70 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 NG125
Product or component type
Miniature circuit-breaker
Device short name
NG125H
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
50 A at 40 °C
Network type
DC; AC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
12 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2; 30 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 36 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at
Utilisation category
Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Standards
EN/IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.8 cm
Package 1 Width
8.1 cm
Package 1 Length
10.8 cm
Package 1 Weight
477 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
9.1 cm
Package 2 Width
11.9 cm
Package 2 Length
36 cm
Package 2 Weight
2.954 kg
Unit Type of Package 3
S03
Number of Units in Package 3
36
Package 3 Height
30 cm
Package 3 Width
30 cm
Package 3 Length
40 cm
Package 3 Weight
18.256 kg
The Acti9 NG125H circuit breaker from Schneider Electric is a two-pole (2P) protective switch for use in electrical distribution systems. It is designed for a rated current of 50 A at an ambient temperature of 40 °C and provides protection against overload and short-circuit currents. The tripping technology is thermomagnetic, with the thermal component detecting overloads and the magnetic component responding to sudden short circuits. The tripping characteristic is type C, suitable for applications with moderate inrush currents, such as those occurring with motors or lighting systems.
Applications
The switch is designed for use in industrial and commercial distribution systems, particularly in installations with operating voltages of 220–240 V AC, 380–415 V AC, 440 V AC, and 500 V AC at 50/60 Hz. It is designed for usage category A according to IEC 60947-2, which covers protective functions in consumer circuits with low energy transfer. The rated insulation voltage is 690 V AC, enabling use in systems with higher voltage levels. The rated impulse withstand voltage of 8 kV ensures reliability during transient voltage surges.
Functions and Equipment in Detail
The switch features a mechanical contact position indicator that visually signals the ON/OFF position. A red indicator on the front panel shows tripping, enabling quick fault diagnosis. An integrated test button allows checking of the tripping mechanism without power supply. Mounting is on a 35 mm symmetrical DIN rail, with vertical mounting orientation. The terminals consist of tunnel terminals for solid conductors from 1.5 to 50 mm² and flexible conductors from 1 to 35 mm². The wire stripping length is 20 mm, and the required tightening torque is 3.5 Nm. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles.
Technology Explained Simply
The thermomagnetic tripping technology combines a bimetal strip (thermal) for responding to sustained overloads and an electromagnet (magnetic) for rapid response to short circuits. The C characteristic means the switch trips within seconds at 5 to 10 times the rated current, typical for installations with motor loads. The breaking capacities vary by voltage: 70 kA at 220–240 V AC, 36 kA at 380–415 V AC, 30 kA at 440 V AC, and 12 kA at 500 V AC. These values comply with EN/IEC 60947-2 standards. The rated operational breaking capacities are 52.5 kA (220–240 V AC), 27 kA (380–415 V AC), 22.5 kA (440 V AC), and 9 kA (500 V AC), each at 75 % of nominal voltage.
Compatibility and Accessories
The switch is suitable for mounting on comb rails and distribution blocks and can be expanded with various optional modules. These include current trip units (e.g. 19064, 19066), under-voltage trip units (e.g. 19067, 19061), auxiliary switches (e.g. 19072, 19071), residual current modules (e.g. 19010), earth fault modules (e.g. 19012), as well as terminal covers (e.g. 19081, 19085) and multi-connection terminals (e.g. 19091, 19096). The integrated locking mechanism allows the use of padlocks for safety purposes.
Mounting and Installation
Mounting is on a 35 mm DIN rail in vertical position. Dimensions are 54 mm width, 103 mm height, and 81 mm depth. The protection rating is IP20, providing protection against contact with fingers and larger solid objects, but not against splashing water or dust. The IK05 protection rating safeguards against mechanical impacts with energy up to 0.5 J. The operating ambient temperature ranges from -30 °C to +70 °C, and storage temperature from -40 °C to +70 °C. Relative humidity may reach up to 95 % at 55 °C. The overvoltage category IV and pollution degree 2 are suitable for installations in industrial environments.
Operational Advantages
The snap-action switching ensures wear-free switching of contacts, increasing service life. The integrated contact position and tripping indicator enable quick visual inspection of operational status. Compatibility with various add-on modules allows flexible adaptation to specific requirements. Certification according to EN/IEC 60947-2 and VDE certification guarantee compliance with European safety and quality standards. The locking option supports safety during maintenance work.
Protection Rating, Standards and Environmental Conditions
The switch complies with EN/IEC 60947-2 and is designed for use in installations with pollution degree 3, indicating a heavily polluted environment. The IP20 protection rating safeguards against finger contact, and IK05 protects against mechanical impacts. The operating temperature ranges and drip-proof rating make it suitable for industrial applications. The rated insulation voltage of 690 V AC and impulse withstand voltage of 8 kV ensure reliability in electrical distribution systems.