Further information for Schneider Electric 18633 power circuit breaker 3-pole C 16A
Complementary
Network frequency
50/60 Hz
Magnetic tripping limit
8 x In
[Ics] rated service breaking capacity
37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 20 kA 100 % conforming to EN/IEC 60947-2 -
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
Control type
Manual tripping test; Toggle
Local signalling
Trip indicator; ON/OFF indication
Mounting mode
Clip-on
Mounting position
Vertical
Mounting support
35 mm symmetrical DIN rail
9 mm pitches
9
Height
103 mm
Depth
81 mm
Width
81 mm
Net weight
0.72 kg
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Locking options description
Integrated padlocking
Connections - terminals
Tunnel type terminals1.5…50 mm² rigid; Tunnel type terminals1…35 mm² flexible
Wire stripping length
20 mm
Tightening torque
3.5 N.m
Earth-leakage protection
Separate block
Contact position indicator
Comb busbar and distribution block compatibility
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK05 conforming to EN/IEC 62262
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…70 °C
Logistical informations
Country of origin
FR
Main
Range
Acti9
Product name
Acti9 NG125
Product or component type
Miniature circuit-breaker
Device short name
NG125N
Device application
Distribution
Poles description
3P
Number of protected poles
3
[In] rated current
16 A at 40 °C
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
20 kA Icu at
Utilisation category
Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Standards
EN/IEC 60947-2
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.6 cm
Package 1 Width
12 cm
Package 1 Length
12.7 cm
Package 1 Weight
758 g
Unit Type of Package 2
S03
Number of Units in Package 2
18
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
13.833 kg
Circuit breaker Acti 9 NG125N, 25kA (IEC/EN 60947-2). 2-pole, nominal current 16A, C characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 690V AC. Protection of the circuit against short-circuit currents. Protection of the circuit against overload currents. Tripping is indicated by the middle position of the switch knob and by a red, mechanical display on the front of the device. Test button for checking the tripping mechanism. Power supply from above or below. Snap action for low-wear switching of the contacts. Technology of the tripping unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position, fault tripping, shunt release, undervoltage release, overvoltage release. The NG125N circuit breaker meets the following standards - IEC/EN 60947-2. Furthermore, this series is VDE certified.