| General |
| Material | Cu-contacts: high-purity electrolytic copper F20, insulation: high-resistance vinyl compound, elongation 370 %, temperature: -30 °C...+105 °C, flammability according to UL-94 V0, dielectric strength: 20 kV/mm |
| Length | 2.000 mm |
| Rated current for temperature rise 50 K | 770 A |
| Rated current for temperature rise 30 K | 585 A |
| Rated current for temperature rise 70 K | 920 A |
| Note | Construction = number of fins x fin width x fin thickness, individually cuttable, the resulting conductor temperature of the finned flat copper busbar is the sum of ambient temperature and temperature rise. Example: 3565.005 loaded with 180 A, i.e. the temperature rises by 30 K. At an ambient temperature of 35 °C, the resulting conductor temperature is therefore 35 °C + 30 K = 65 °C. |
| Laminated flat copper execution | Number of lamellae: 10, lamella width: 24 mm, lamella thickness: 1 mm |
| Copper content (kg/piece) | 4,27 |
The SV 9685725 from Rittal is a laminated copper busbar made of high-purity electrolytic copper F20, tinned, with a total length of 2,000 mm. It serves as a power distribution component in enclosures and is used for safe and efficient power distribution in industrial installations. The busbar consists of 10 laminations with a width of 24 mm and a thickness of 1 mm, ensuring a stable and conductive structure. The tinning protects the copper laminations from corrosion and improves contact quality at connections.
Applications
The laminated copper busbar is designed for use in enclosures and distribution systems where high current loading and thermal stability are required. It is particularly suitable for applications in industrial electrical engineering, where the busbar serves as the main conductor for powering devices and components. The individual cut-to-length capability allows for application-specific adaptation to the respective enclosure geometry.
Functions and Equipment in Detail
The busbar features a highly durable vinyl compound as insulation, which exhibits an elongation of 370 %, providing high mechanical load capacity. The insulation is rated for temperatures from -30 °C to +105 °C and meets the flammability standard UL-94 V0, ensuring high fire resistance. The dielectric strength is 20 kV/mm, ensuring safe electrical insulation even under high voltages.
Technology Explained Simply
The rated currents depend on the permissible temperature rise. At a temperature rise of 50 K, the rated current is 770 A; at 30 K, it is 585 A; and at 70 K, it is 920 A. The resulting conductor temperature is the sum of the ambient temperature and the temperature rise. Example: At an ambient temperature of 35 °C and a temperature rise of 30 K, the resulting conductor temperature is 65 °C. The busbar can be individually cut to length to precisely match the required length.
Compatibility and Accessories
For mounting and securing the busbar, universal holders for laminated copper busbars 20x5 are available. These holders enable secure and stable fixation of the busbar in the enclosure. The combination with suitable holders ensures proper installation and prevents mechanical stress.
Mounting and Installation
The busbar is individually cut to length, allowing it to be adapted to the specific requirements of the enclosure. Mounting is done using appropriate holders that ensure secure fastening. The tinning of the laminations facilitates connection to other components and ensures a reliable electrical contact.
Advantages in Operation
The use of high-purity electrolytic copper F20 ensures high electrical conductivity and thermal stability. The laminated structure increases the surface area and improves heat dissipation, enhancing the thermal load capacity of the busbar. The high mechanical strength of the vinyl insulation and fire resistance according to UL-94 V0 increase operational safety. The individual cut-to-length capability and compatibility with standard holders simplify installation and adaptation to various enclosure configurations.