| General |
| Material | Sheet steel, 1.5 mm |
| Surface protection | Zinc-plated |
| Scope of delivery | 4 cover plates (left/right side), 2 cover plates (top/bottom), including mounting hardware |
| Installation width when using Flat-PLS | 800 mm |
| Note | The specified mounting width when using the touch protection cover is only valid when using the busbar holders 9686.060/9686.070 |
| Suitable for | Cabinet type: TS, width: = 1.000 mm |
| PCF/VE (Cradle-to-Gate) | 28.5 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SV 9684900 is a shock protection cover type 2 b, specifically designed for use in enclosures with NH fuse switch disconnectors and busbar systems in the rear area. The product provides finger-safe coverage of outgoing fields and ensures a protection rating of IP 2X, protecting against contact with live parts. It is designed for enclosures of type TS with a width of at least 1,000 mm and is used in conjunction with the VX design. The cover is made of sheet steel with a thickness of 1.5 mm and features a galvanized surface, providing corrosion protection and extending the component's service life.
Applications
The shock protection cover is used in industrial electrical installations where safe coverage of switch disconnector fields is required. It is particularly suitable for installations with NH fuse switch disconnectors and serves to comply with safety regulations for handling electrical systems. The cover is installed in the rear area of the enclosure, where busbars and outgoing conductors are connected, to prevent direct contact with live parts.
Functions and Equipment in Detail
The SV 9684900 includes a total of six cover panels: four side panels (left and right) as well as two panels for the upper and lower areas of the outgoing field. This design enables complete coverage of the relevant areas, minimizing the risk of unintended contact. The delivery includes the necessary mounting hardware for securing the cover panels within the enclosure. The cover panels are designed to fit the geometry of the switch disconnectors and busbars, ensuring a secure and tight seal.
Technology Explained Simply
The cover is made of sheet steel with a wall thickness of 1.5 mm, ensuring sufficient mechanical stability and durability. The galvanized surface protects the material from corrosion, especially in environments with high humidity or aggressive atmospheres. The IP 2X rating means the cover protects against contact with fingers, but not against water or dust. The installation width is 800 mm when using Flat-PLS busbar holders (types 9686.060/9686.070). This specification is specific to the combination with these holders and does not apply to other mounting variants.
Compatibility and Accessories
The shock protection cover is designed for enclosures of type TS with a width of at least 1,000 mm. It is specifically intended for use with NH fuse switch disconnectors and busbar systems. As compatible accessories, the SV blank cover for VX W: 50 mm, design 2b, is offered, which can be used to cover unused fields in the enclosure. The combination with busbar holders 9686.060/9686.070 is required to achieve the specified installation width of 800 mm.
Installation and Mounting
Mounting takes place in the rear area of the enclosure, where the switch disconnectors and busbars are installed. The cover panels are secured at the appropriate positions using the included mounting hardware. The cover is designed to easily adapt to existing structures within the enclosure and ensures a secure, tight seal.
Operational Advantages
The use of the SV 9684900 increases safety in the operation of electrical systems by protecting against unintended contact with live parts. The galvanized surface ensures a longer service life and reduces maintenance requirements. The cover is easy to install and adapts to standard enclosure configurations, making installation efficient. Compliance with the IP 2X protection rating contributes to conformity with applicable safety standards and reduces the risk of accidents during operation.