Further information for Rittal 9363215 NH fuse-disconnector 3-pole 400 A
General
Model
with electronic fuse monitoring (ESÜ), for panel mounting
Material
Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated
Colour
RAL 9005, RAL 35745
Scope of delivery
Including connection plug for electrical fuse monitoring
Cable exit
Above/under
Electrical connection type
M10 screw
Fuse links
NH 2
Rated insulation voltage Ui
1.000 kV
Rated operating voltage
690 V AC
For NH size
2
Test basis
IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts)
Width
208,5 mm
Height
348,7 mm
Depth
128,7 mm
Operating temperature range
-5 °C...35 °C
Storage temperature range
-25 °C...70 °C
Number of poles
3-pole
Pollution degree
3
Degree of protection IP according to IEC 60 529
IP 2XB
Fire load
48,8 MJ/m²
Maximum power dissipation
71 W
Copper content (kg/piece)
1,32
PCF/VE (Cradle-to-Gate)
25,03
For panel mounting
With electronic fuse monitoring (ESÜ)
The Rittal RiLineX NH fuse switch disconnector type RX 9363215 is a 3-pole switch disconnector in size 2, specifically designed for mounting on mounting plates. It is intended for the safe disconnection of electrical installations and enables the use of NH fuse inserts. The version includes electronic fuse monitoring (ESÜ), which monitors the condition of the installed fuses and thus supports precise fault diagnosis. The operating voltage is 690 V AC, and the rated insulation voltage is 1,000 kV, enabling use in industrial installations with high electrical loads. The protection rating IP 2XB according to IEC 60 529 protects against finger contact and against solid foreign objects, although the devices are not designed for outdoor use or in damp environments.
Applications
The switch disconnector is intended for use in industrial electrical installations, particularly in enclosures and distributions, where safe disconnection and monitoring of fuses are required. Mounting is done on mounting plates, with dimensions of 208.5 mm (width) × 348.7 mm (height) × 128.7 mm (depth), enabling compact integration into existing control systems. The operating temperature ranges from -5 °C to 35 °C, and the storage temperature ranges from -25 °C to 70 °C, allowing flexible storage and installation under various environmental conditions.
Functions and Equipment in Detail
The cover of the disconnector is lockable and sealable, ensuring secure and documented access prevention. Visual fuse monitoring allows direct control of the fuse status. Safe voltage testing is performed via integrated test points on the cover, enabling precise and risk-free voltage testing. A parking position for the cover facilitates maintenance work, as the cover can be held in a stable, open position. The connection is made via screw connection M10, with cable exit possible at the top and bottom. Tool-free adjustment of the cable exit allows flexible adaptation without additional tools.
Technology Explained Simply
The electronic fuse monitoring (ESÜ) monitors the electrical condition of the NH fuse inserts and signals defects or faults. The contact strips are made of electrolytic copper, silver-plated, ensuring high conductivity and corrosion resistance. The housing is made of polyamide (PA 6) with flame resistance according to UL 94, providing high heat and fire resistance. The power loss is a maximum of 71 W, limiting thermal load during operation. The fire load of 48.8 MJ/m² is a measure of the energy released during combustion of the material and is relevant for planning fire protection measures.
Compatibility and Accessories
The disconnector is designed for NH fuse inserts of size 2. As suitable accessories, the cover RX 9365532 for the connection area is offered, which seals the connection area and thus provides additional protection. The test basis is according to IEC/DIN EN 60 947-3 and DIN EN 60 269-2, confirming compliance with European standards for switching devices and fuse inserts. The pollution degree class 3 indicates that the device is suitable for environments with increased contamination, as found in industrial installations.
Mounting and Installation
Mounting is done on mounting plates, with the dimensions and screw connection M10 enabling easy integration into existing control systems. The tool-free adjustment of the cable exit reduces mounting time and simplifies installation. The parking position of the cover facilitates maintenance, as the cover can be held stably in the open position. The connection plugs for the electronic fuse monitoring are included in the delivery scope, enabling direct integration into existing monitoring systems.
Advantages in Operation
The combination of electronic fuse monitoring, lockable cover, visual monitoring, and parking position offers high safety and ease of maintenance. The integrated test points for voltage testing reduce the risk of incorrect operation and increase safety during maintenance work. The tool-free adjustment of the cable exit and the compact design facilitate installation and use in confined control systems. Compliance with international standards ensures reliable and safe use in industrial applications.