Further information for Rittal 9363210 NH-fuse-disconnector 3-pole 400 A
General
Model
for panel mounting
Material
Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated
Colour
RAL 9005, RAL 35745
Cable exit
Above/under
Electrical connection type
M10 screw
Fuse links
NH 2
Rated insulation voltage Ui
1.000 kV
Rated operating voltage
690 V AC
For NH size
2
Test basis
IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts)
Width
208,5 mm
Height
298,6 mm
Depth
128,7 mm
Operating temperature range
-5 °C...35 °C
Storage temperature range
-25 °C...70 °C
Number of poles
3-pole
Pollution degree
3
Degree of protection IP according to IEC 60 529
IP 2XB
Fire load
44 MJ/m²
Maximum power dissipation
71 W
Copper content (kg/piece)
1,32
PCF/VE (Cradle-to-Gate)
22,07
For panel mounting
The Rittal RX 9363210 is an NH fuse switch disconnector in size 2, specifically designed for mounting plate installation. It serves as a power disconnector in industrial electrical installations and enables safe disconnection of circuits under load, with the integrated NH fuse inserts (size 2) providing protection against overloads and short circuits. The device is rated for a rated operational voltage of 690 V AC and features a rated insulation voltage of 1,000 kV, ensuring high electrical safety during commissioning and maintenance. The 3-pole configuration makes it suitable for three-phase installations.
Applications
This switch disconnector is intended for use in industrial switchgear, distribution boxes, and machine controls where safe and controlled power disconnection is required. The protection rating IP 2XB according to IEC 60 529 protects against finger contact and solid foreign objects, although the device is not designed for outdoor use or humid environments. The pollution degree 3 accounts for environments with increased contamination, such as those found in production facilities. The operating temperature range is between -5 °C and 35 °C, while the device can withstand storage temperatures from -25 °C to 70 °C.
Functions and Equipment in Detail
A central feature is the lockable and sealable cover, enabling secure access control. The visual fuse monitoring allows the status of the installed NH fuse to be checked directly on the device without opening the cover. The integrated test points on the cover enable safe voltage testing, allowing inspection without direct contact with live parts. The parking position of the cover facilitates maintenance work, as the cover can be held in a stable, open position. The tool-free reconfiguration of the cable exit allows flexible adjustment of the connection direction (top/bottom) without additional tools.
Technology Explained Simply
The device consists of a housing made of polyamide (PA 6), which, according to UL 94, exhibits specific flammability characteristics, limiting the fire load to 44 MJ/m². The contact strips are made of electrolytic copper, silver-plated, ensuring high electrical conductivity and corrosion resistance. The connection method is via M10 screws, providing a secure and mechanically stable connection. The maximum power loss is 71 W, describing the thermal load on the device during operation. The copper content per unit is 1.32 kg, indicating the material composition and recyclability.
Compatibility and Accessories
The switch disconnector is designed for NH fuse inserts of size 2. As suitable accessories, the connection space cover 1=2 for NH disconnectors size 2 (item RX 9365532) is offered, which additionally seals and protects the connection area. Testing is based on IEC/DIN EN 60 947-3 for switch disconnectors and DIN EN 60 269-2 for fuse inserts, confirming compliance with European standards.
Mounting and Installation
Mounting is performed on a mounting plate, with dimensions of 208.5 mm (width) × 298.6 mm (height) × 128.7 mm (depth) to be considered. The cable connections are designed for cable exit at top or bottom, enabling flexible installation in various switch enclosures. The M10 screw connections require no special tools for installation, and the tool-free reconfiguration of the cable exit provides additional flexibility.
Operational Advantages
The combination of visual fuse monitoring, integrated test points, and parking position enhances safety during maintenance and inspection work. The sealable and lockable cover ensures that only authorized personnel can access the device. The high insulation strength and robust construction ensure reliable performance in demanding industrial environments. The compatibility with NH fuse inserts size 2 enables flexible integration into existing switchgear installations.