Connection of round conductors, fine-stranded without ferrule
1,5 ‐ 16 mm²
Connection of stranded wires, fine-stranded with ferrule
1,5 ‐ 50 mm²
Maximum power dissipation
36 W
Power loss per fuse element (max.)
9 W
Copper content (kg/piece)
0,475
PCF/VE (Cradle-to-Gate)
5,85
With electronic fuse monitoring (ESÜ)
The Rittal RX 9362424 is an NH fuse switch disconnector in size 000, specifically developed for 60 mm busbar systems such as RiLineX and RiLine60. The device serves as a switch disconnector with integrated NH 000 fuse inserts and enables safe disconnection of electrical installations during operation. It is designed for a rated operational voltage of 690 V AC and features a rated insulation voltage of 1,000 V. The electronic fuse monitoring (ESÜ) is integrated as standard and enables continuous monitoring of the fuse status. The disconnector is 3-pole and complies with usage categories AC-23B, AC-22B, AC-21B, and DC-22B, making it suitable for various applications in industrial environments.
Applications
The disconnector is designed for use in industrial electrical installations, particularly in switchgear mounted on busbar systems with a 60 mm center spacing. It is suitable for installations with operational voltages up to 690 V AC and is designed for a maximum operating temperature of 35 °C. Storage is possible in the range of -25 °C to 70 °C. The compatibility with busbars having cross-sections of 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm enables flexible integration into existing systems. The protection rating IP 2XB according to IEC 60 529 ensures protection against finger contact and vertical dripping water, making it suitable for use in enclosed switchgear.
Functions and Equipment in Detail
The cover of the disconnector is lockable and sealable, enabling secure and documentable monitoring of the operational status. An visual fuse monitoring is also integrated, allowing the fuse status to be directly visible on the device. The safe voltage testing is performed via integrated test points on the cover, enabling testing without direct contact with conductive parts. A parking position for the cover facilitates maintenance work, as the cover can be held in a stable, open position. The connection type is via a frame terminal, suitable for round conductors with cross-sections from 1.5 to 50 mm², with a wire end ferrule required for fine-stranded conductors up to 50 mm². The cable exit is located at the top.
Technology Explained Simply
The electronic fuse monitoring (ESÜ) monitors the electrical condition of the fuse and signals any defect or failure. The frame terminal enables a secure and tool-free connection of round conductors. The push-on mounting up to 250 A and the tool-free adjustment to various rail thicknesses (5/10 mm) simplify installation. The material consists of polyamide (PA 6) with flame resistance according to UL 94, and the contact strips are made of electrolytic copper, silver-plated, ensuring high conductivity and corrosion resistance. The power loss is a maximum of 36 W, with up to 9 W per fuse insert. The color is available in RAL 9005 (black) and RAL 35745 (gray).
Compatibility and Accessories
The disconnector is compatible with the busbar systems RiLineX and RiLine60. As accessories, suitable enclosure protection profiles (RX 9365025) and mounting clips (RX 9365027) are available, providing additional safety during installation. For integration into safety concepts, microswitches (RX 9365500) and anti-shift clips (RX 9365501) are available, which monitor the operational status and prevent accidental operation of the disconnector.
Mounting and Installation
Mounting is done directly onto the 60 mm busbar system. The push-on mounting allows for quick and secure fastening. Adjustment to different rail thicknesses (5/10 mm) is possible without tools. The cable exit is located at the top, enabling flexible cabling. The delivery includes connection plug for the electronic fuse monitoring.
Operational Advantages
The disconnector offers high operational safety through the integrated electronic fuse monitoring and visual status indication. The lockable and sealable cover supports documentation and safety. The parking position and tool-free mounting reduce maintenance time. The use of polyamide and silver-plated copper ensures high durability and reliability. The compliance with IEC/DIN EN 60 947-3 and DIN EN 60 269-2 (fuse inserts) ensures conformity with international standards. The pollution degree 3 makes the device suitable for environments with increased pollution risk. The fire load is 13.62 MJ/m², meeting fire protection requirements in industrial installations. The copper content is 0.475 kg per unit, supporting recyclability. The PCF/VE (Cradle-to-Gate) is 5.85, describing the environmental impact of the product.