| General |
| Model | For 60 mm busbar systems |
| Material | Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| Colour | RAL 9005, RAL 35745 |
| For rail systems with centre spacing | 60 mm |
| Cable exit | Above |
| Electrical connection type | Frame clamp |
| Fuse links | NH 000 |
| Rated insulation voltage Ui | 1.000 V |
| Rated current max. | 125 A |
| Rated operating voltage | 690 V AC |
| For NH size | 000 |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 53 mm |
| Height | 212 mm |
| Depth | 103 mm |
| Operating temperature range | -5 °C...35 °C |
| Storage temperature range | -25 °C...70 °C |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Suitable for busbar system | RiLineX, RiLine60 |
| Number of poles | 3-pole |
| Utility category | AC-23B (400 V/100 A), AC-22B (500 V/100 A), AC-21B (690 V/100 A), DC-22B (250 V/100 A) |
| Pollution degree | 3 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Fire load | 10,84 MJ/m² |
| Connection of round conductors, fine-stranded without ferrule | 1,5 ‐ 16 mm² |
| Connection of stranded wires, fine-stranded with ferrule | 1,5 ‐ 50 mm² |
| Maximum power dissipation | 36 W |
| Power loss per fuse element (max.) | 9 W |
| Copper content (kg/piece) | 0,475 |
| PCF/VE (Cradle-to-Gate) | 4,53 |
The Rittal RX 9362422 is an
NH fuse switch disconnector in size 000, specifically designed for 60 mm busbar systems. It serves as a
power disconnector in industrial electrical installations and enables safe disconnection of circuits with the installation of NH fuse inserts. The device is rated for a nominal operating voltage of 690 V AC and a maximum nominal current of 125 A. The
rated insulation voltage is 1,000 V, allowing use in high-voltage environments up to this limit. The
usage category includes AC-23B (400 V/100 A), AC-22B (500 V/100 A), AC-21B (690 V/100 A), and DC-22B (250 V/100 A), making the disconnector suitable for various load types and operating conditions.
Applications
This disconnector is intended for use in industrial installations such as machine controls, distribution boxes, or enclosures, where safe electrical disconnection and visual monitoring of the fuse are required. It is designed for busbar systems of types RiLineX and RiLine60, which feature a center-to-center spacing of 60 mm. Compatible busbar profiles have dimensions of 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm, enabling flexible mounting on various busbar thicknesses.
Functions and Equipment in Detail
The disconnector's cover is
lockable and
sealable, preventing unauthorized manipulation and enhancing safety.
Visual fuse monitoring allows direct inspection of the installed NH fuse condition at the device.
Safe voltage testing is performed via integrated test points on the cover, providing secure access for voltage checks without direct contact with live parts. A
parking position for the cover facilitates maintenance work, as the cover can be held securely in an open, stable position.
Technology Explained Simply
The device consists of a housing made of
polyamide (PA 6), which is flame-retardant according to UL 94, and silver-plated contact strips made of
electrolytic copper, offering high electrical conductivity and corrosion resistance. The
connection type is via a
frame terminal, designed for connecting round conductors. Permissible cross-sections range from 1.5 to 16 mm² without wire end ferrules and from 1.5 to 50 mm² with wire end ferrules. The
cable exit is at the top, enabling flexible wiring. The
protection rating IP 2XB according to IEC 60 529 protects against finger contact and vertical dripping water, but not against splashing water or dust — thus, application is limited to indoor environments.
Compatibility and Accessories
The disconnector is designed for
NH size 000 and is compatible with fuse inserts of this size. Suitable accessories are available, including the
enclosure protection profile RX 9365025 (length 1200 mm) and the
mounting clip RX 9365027 for its installation. Additionally, the
microswitch RX 9365500 and the
anti-shift clip RX 9365501 can be used to extend the disconnector’s functionality.
Mounting and Installation
Mounting is done via
push-on mounting directly onto the busbars, with tool-free adjustment to busbar thickness (5/10 mm). The cable exit can be changed without tools, increasing installation flexibility. Dimensions are 53 mm (width) × 212 mm (height) × 103 mm (depth), allowing the disconnector to fit in standardized enclosures. Operating temperature ranges from -5 °C to 35 °C, and storage temperature ranges from -25 °C to 70 °C.
Operational Advantages
The disconnector offers high operational safety through the combination of mechanical disconnection, visual fuse monitoring, and sealable closure. The parking position and tool-free adjustment of busbar thickness reduce installation and maintenance time. Integrated test points for voltage testing increase safety during maintenance work. Power loss is maximally 36 W, with up to 9 W per fuse insert. Fire load is 10.84 MJ/m², meeting fire protection requirements in industrial installations. The
pollution degree 3 according to IEC 60 947-3 indicates suitability for environments with increased contamination, such as those found in industrial production settings.