| General |
| Model | For 60 mm busbar systems |
| Material | Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| Colour | RAL 9005, RAL 35745 |
| For rail systems with centre spacing | 60 mm |
| Cable exit | Above/under |
| Electrical connection type | Frame clamp |
| Fuse links | NH 00, NH 000 |
| Rated insulation voltage Ui | 1.000 V |
| Rated operating voltage | 690 V AC |
| For NH size | 00 |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 106 mm |
| Height | 194,2 mm |
| Depth | 104,5 mm |
| Operating temperature range | -5 °C...35 °C |
| Storage temperature range | -25 °C...70 °C |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Suitable for busbar system | RiLineX, RiLine60 |
| Number of poles | 3-pole |
| Utility category | AC-23B (400 V/100 A), AC-22B (500 V/100 A), AC-21B (690 V/100 A), DC-22B (250 V/100 A) |
| Pollution degree | 3 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Fire load | 14,2 MJ/m² |
| Maximum power dissipation | 22 W |
| Power loss per fuse element (max.) | 12 W |
| Copper content (kg/piece) | 0,409 |
| PCF/VE (Cradle-to-Gate) | 6,48 |
The Rittal RX 9362030 is an
NH fuse switch disconnector in size 00, specifically designed for 60 mm busbar systems. It serves as a
power disconnector in industrial electrical installations, where safe disconnection of the power supply is required for maintenance or inspection work. The device is designed for use in switchgear systems operating at a rated service voltage of 690 V AC, with a rated insulation voltage Ui of 1,000 V. The
usage category includes AC-23B (400 V/100 A), AC-22B (500 V/100 A), AC-21B (690 V/100 A), and DC-22B (250 V/100 A), enabling its use in various applications.
Applications include industrial switchgear, machine controls, and distribution systems where a safe, visual, and mechanical disconnection of the power supply is necessary. The disconnector is designed for
3-pole applications and adapts to busbars with a center spacing of 60 mm. Compatible busbar profiles include 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm, with mounting via
push-on mounting, which is possible up to 250 A. Adjustment to different busbar thicknesses is tool-free.
Functions and equipment in detail include a lockable and sealable cover, ensuring secure protection against unauthorized access. The
visual fuse monitoring allows the status of the installed NH fuse inserts (size 00, NH 000) to be directly observed on the device. Integrated test points on the cover enable safe voltage testing without direct contact with live parts. A
parking position for the cover facilitates maintenance work, as the cover can be secured in the open position, for example, with a padlock.
Technology explained simply shows that the disconnector is made of polyamide (PA 6), which is flame-retardant according to UL 94. The contact strips are made of silver-plated electrolytic copper, ensuring high electrical conductivity and corrosion resistance. The
connection type is via a frame terminal, designed for connecting round conductors with a cross-section of at least 1.5 mm² up to a maximum of 95 mm². The
cable exit can be individually set to top or bottom, with tool-free conversion. The
protection rating IP 2XB according to IEC 60 529 protects against finger contact and vertical dripping water, suitable for use in enclosed switchgear. The
pollution degree 3 accounts for environments with increased contamination, as found in industrial facilities.
Compatibility and accessories include use with NH fuse inserts of size 00 and 000. These components support integration into existing switchgear and extend functionality.
Mounting and installation are performed directly onto 60 mm busbar systems such as RiLineX or RiLine60. Mounting is tool-free and adaptable to various busbar thicknesses. The frame terminal enables a secure and reliable electrical connection. The operating temperature range is between -5 °C and 35 °C, while the storage temperature range extends from -25 °C to 70 °C. The maximum power loss is 22 W, with up to 12 W per fuse insert.
Operational advantages lie in high safety provided by the lockable cover, sealable construction, and integrated voltage testing. The parking position and tool-free reconfiguration of the cable exit reduce maintenance time. The use of high-quality materials such as silver-plated copper and flame-retardant polyamide ensures long service life and reliability. Compliance with standards IEC/DIN EN 60 947-3 and DIN EN 60 269-2 (for fuse inserts) ensures conformity with international standards.
Dimensions are 106 mm (width) × 194.2 mm (height) × 104.5 mm (depth). The device is designed for use in switchgear systems requiring high mechanical and electrical load capacity. Available color variants are RAL 9005 (black) and RAL 35745 (gray). The fire load is 14.2 MJ/m², and the copper content per unit is 0.409 kg. The environmental impact is documented by the PCF value of 6.48 (Cradle-to-Gate).
The product name is RiLineX NH fuse switch disconnector, and the manufacturer's number is 9362030. The device is designed for use in industrial electrical installations where a safe, reliable, and maintenance-friendly disconnection of the power supply is required. The combination of mechanical disconnection, visual monitoring, and integrated voltage testing makes the disconnector an important component in modern switchgear.