| General |
| Model | universal, NOTE: Only suitable for MCCBs with frame terminals! |
| Material | Polyamide (PA 6), flammability according to UL 94 |
| Colour | RAL 9005, RAL 35745 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Electrical values UL (SCCR) | 65 kA - 480 V, Circuit Breaker max. 125 A, DIVQ/7 |
| Rated impulse voltage Uimp | 8 kV |
| Rated voltage | 690 V AC, 600 V AC (UL) |
| Rated insulation voltage Ui | 1.000 V |
| Pollution degree | 3 |
| Number of poles | 3-pole |
| Cable exit | Above |
| Electrical connection type | Frame clamp |
| Cross section | 9 mm², 6 mm² |
| Suitable for manufacturer (type) | Easily find the appropriate device adapter using our selection guide in the Downloads section. |
| Suitable for busbar system | RiLineX, RiLine60 |
| Maximum power dissipation | 8 W |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Operating temperature range | -25 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 82 mm |
| Height | 251,4 mm |
| Depth | 50,8 mm |
| Fire load | 22,045 MJ/m² |
| Copper content (kg/piece) | 0,375 |
| PCF/VE (Cradle-to-Gate) | 12,86 |
The Rittal RX 9360603 is a
CB device adapter for mounting compact power circuit breakers (MCCB) on 60 mm busbar systems. It is available in the
Universal Fix version and enables direct mounting of switches onto the board. The
3-pole construction is designed for a maximum rated current of 160 A and features a tool-free snap-in mounting, allowing for quick and easy pre-assembly of market-standard switch types outside the enclosure. The adapter is specifically designed for switches with
frame terminals and includes an
upper cable exit.
Applications
This device adapter is used in industrial electrical installations where secure and flexible mounting of power switches on busbars is required. It is suitable for systems with voltages up to 690 V AC and 690 V DC. The application is particularly intended for enclosures equipped with RiLineX or RiLine60 busbar systems. The universal design with sliding nuts allows adaptation to various busbar thicknesses between 5 and 10 mm, facilitating installation on different busbar profiles (15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm).
Functions and Equipment in Detail
The adapter is made of
polyamide (PA 6), which exhibits a specific flammability rating according to UL 94. The color is available in RAL shades 9005 (black) and 35745 (gray). The
protection rating IP 2XB according to IEC 60 529 protects against finger contact and solid foreign objects, but not against water. The
rated voltage is 690 V AC (600 V AC according to UL), and the
rated insulation voltage Ui is 1,000 V. The
pollution degree 3 is intended for environments with heavy contamination, as found in industrial installations. The
rated impulse voltage Uimp is 8 kV, ensuring electrical strength under transient voltage stresses.
Technology Explained Simply
The
tool-free snap-in mounting allows for quick fastening of the switch without additional tools. The semi-automatic adjustment of busbar thickness is achieved via adjustable support rails with sliding nuts, which adapt the switch’s drilling pattern to the respective busbar thickness. The
connection type frame terminal is designed for connecting cables with a cross-section of 6 mm² to 9 mm². The maximum
power loss is 8 W, limiting thermal load during operation. The
frequency of the fundamental wave ranges from 50 to 60 Hz, enabling use in standard power networks.
Compatibility and Accessories
The adapter is compatible with the
RiLineX and
RiLine60 busbar systems. It is suitable for mounting switches from various manufacturers, with selection supported by the manufacturer’s downloadable selection aid. Suitable accessories include the
enclosure protection profile RX 9365025 (length 1200 mm) and the
mounting clip RX 9365027 (for 24 pieces), which contribute to secure mounting and protection of the switching installation.
Mounting and Installation
Mounting is performed by snapping the adapter onto the busbar, with sliding nuts enabling adjustment to the busbar thickness. The switch is mounted directly onto the adapter, creating a stable and secure connection. Installation is tool-free, reducing mounting time and minimizing error potential. The adapter dimensions are 82 mm (width), 251.4 mm (height), and 50.8 mm (depth), with a device width of 81 mm.
Operational Advantages
The adapter offers high flexibility in mounting and enables quick pre-assembly of switches outside the enclosure. Tool-free mounting reduces installation time and minimizes the need for special tools. The use of polyamide ensures high mechanical stability and heat resistance. The IP 2XB protection rating provides sufficient protection for use in enclosed enclosures. The operating temperature range of -25 °C to 55 °C allows use in a wide range of industrial environments. Storage is possible between -25 °C and 75 °C, ensuring flexible storage and transportability.