| General |
| Material | Polyamide (PA 6), flammability rating according to UL 94, E-Cu |
| Colour | RAL 35745, RAL 9005 |
| Scope of delivery | Including integrated busbars |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Standards | IEC 61 439-1/-2, UL 508 |
| Rated current max. | 550 A |
| Rated current (UL) | 540 A |
| Electrical values UL (SCCR) | 45 kA - 600 V, RMS, unprotected, 100 kA - 600 V, Fuse Class L max. 1600 A, JDDZ/7, 100 kA - 600 V, Circuit Breaker max. 600 A, DIVQ/7, 100 kA - 480 V, Circuit Breaker max. 800 A, DIVQ/7, 65 kA - 600 V, Circuit Breaker max. 800 A, DIVQ/7 |
| Center-to-center spacing of busbars | 60 mm |
| Rated impulse voltage Uimp | 12 kV |
| Rated voltage | 1.000 V AC, 1.500 V DC, 600 V AC (UL), 600 V DC (UL) |
| Rated insulation voltage Ui | 1.000 V AC, 1.500 V DC |
| Rated surge withstand current Ipk | 115,5 kA, 94,5 kA (UL) |
| Rated short-time withstand current / t | 45 kA/500 ms |
| Over voltage category | 4 |
| Pollution degree | 3 |
| Busbar dimensions | 30 mm x 5 mm |
| Number of poles | 3-pole |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Operating temperature range | -5 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 705 mm |
| Height | 246 mm |
| Depth | 49,2 mm |
| Fire load | 74,304 MJ/m² |
| Copper content (kg/piece) | 2,805 |
| PCF/VE (Cradle-to-Gate) | 39,79 |
The Rittal RiLineX complete board type RX 9360084 is a 3-pole power distribution module with a rated current of 550 A, specifically designed for use in industrial enclosures. It features integrated busbars with dimensions 30 mm x 5 mm and a center-to-center spacing of 60 mm. The size of 705 mm width, 246 mm height, and 49.2 mm depth is designed for enclosures with a width of 800 mm. The board is made of polyamide (PA 6), classified according to UL 94 E-Cu, thus providing high fire protection. The color options RAL 35745 and RAL 9005 allow for visual harmonization within the enclosure. The delivery includes a pre-assembled board with integrated busbars.
Applications
The RiLineX board is suitable for applications in alternating current up to 1,000 V AC and direct current up to 1,500 V DC. It is used in industrial electrical installations where reliable power distribution with high short-circuit withstand capability is required. Certification according to IEC 61 439-1/-2 and UL 508 ensures compliance with international safety standards. The tested short-circuit withstand capability is up to 45 kA/500 ms, enabling use in demanding environments. The overvoltage category 4 and pollution degree 3 indicate application in environments with high electrical stress and potential contamination.
Functions and Equipment in Detail
The board provides complete touch protection class up to IP 2XB according to IEC 60 529. Cable routing can be done in the rear area of the board, offering additional flexibility during system installation. Multiple boards can be connected via RiLineX baying connectors, without reducing short-circuit withstand capability. Mounting can be done horizontally, vertically, or overhead, facilitating integration into various enclosure configurations. Fully digital product data enables time savings during planning and documentation.
Technology Explained Simply
The rated voltage is 1,000 V AC and 1,500 V DC, with the rated insulation voltage Ui also being 1,000 V AC and 1,500 V DC. The rated impulse voltage Uimp is 12 kV, indicating the board’s ability to divert transient voltage surges. The rated impulse current withstand Ipk is 115.5 kA, highlighting its capability to handle short-term current surges. The operating temperature range is between -5 °C and 55 °C, while the storage temperature range extends from -25 °C to 75 °C. The relative humidity (non-condensing) is 10 to 90 %.
Compatibility and Accessories
To extend the system, compatible accessories are available, including the cover strip RX 9365020, which upgrades the touch protection class to IP 3X, and the baying set RX 9360000, which enables connection of multiple boards. Compatibility with RiLineX systems ensures modular expandability.
Mounting and Installation
Mounting is done in enclosures with a width of 800 mm. The board can be installed in various orientations (horizontal, vertical, overhead). The pre-assembled configuration reduces installation time. Cable routing in the rear area allows for flexible arrangement of control wiring.
Advantages in Operation
The pre-assembled configuration and integrated busbars reduce installation time. Digital product data availability supports planning and documentation. High short-circuit withstand capability and certification according to IEC and UL ensure safe and reliable operation. Modular expandability enables flexible adaptation to growing requirements.