| General |
| Material | Polyamide (PA 6), flammability rating according to UL 94, E-Cu |
| Colour | RAL 35745, RAL 9005 |
| Scope of delivery | Including integrated busbars |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Standards | IEC 61 439-1/-2, UL 508 |
| Rated current max. | 800 A |
| Rated current (UL) | 800 A |
| Electrical values UL (SCCR) | 65 kA - 600 V, RMS, unprotected, 100 kA - 600 V, Fuse Class L max. 1600 A, JDDZ/7, 100 kA - 600 V, Circuit Breaker max. 600 A, DIVQ/7, 100 kA - 480 V, Circuit Breaker max. 800 A, DIVQ/7, 65 kA - 600 V, Circuit Breaker max. 800 A, DIVQ/7 |
| Center-to-center spacing of busbars | 60 mm |
| Rated impulse voltage Uimp | 12 kV |
| Rated voltage | 1.000 V AC, 1.500 V DC, 600 V AC (UL), 600 V DC (UL) |
| Rated insulation voltage Ui | 1.000 V AC, 1.500 V DC |
| Rated surge withstand current Ipk | 143 kA, 143 kA (UL) |
| Rated short-time withstand current / t | 65 kA/500 ms |
| Over voltage category | 4 |
| Pollution degree | 3 |
| Busbar dimensions | 30 mm x 10 mm |
| Number of poles | 3-pole |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Operating temperature range | -5 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 905 mm |
| Height | 246 mm |
| Depth | 49,2 mm |
| Fire load | 94,939 MJ/m² |
| Copper content (kg/piece) | 7,224 |
| PCF/VE (Cradle-to-Gate) | 76,05 |
The Rittal RiLineX complete board RX 9360008 is a 3-pole power distribution module with a rated current of 800 A, specifically designed for use in industrial enclosures. It features integrated busbars with dimensions 30 mm x 10 mm and a center-to-center spacing of 60 mm, ensuring safe and efficient power distribution. The board is designed for enclosures with a width of 1000 mm and has a length of 905 mm. It is made of polyamide (PA 6), which according to UL 94 has flame class E-Cu, and is available in the colors RAL 35745 and RAL 9005.
Applications
The RiLineX board is suitable for applications in the alternating current up to 1000 V AC and direct current up to 1500 V DC. It is used in industrial electrical installations where reliable power distribution and high short-circuit resistance are required. The certification according to IEC 61439-1/-2 and UL 508 makes it suitable for use in various regions and industries, including automation technology, manufacturing industry, and energy supply.
Functions and equipment in detail
The board is pre-assembled and already includes the integrated busbars, reducing installation time. Cable routing in the rear area of the board enables flexible system design, especially for control wiring. The shock protection class IP 2XB ensures sufficient protection against contact with hazardous parts. The short-circuit withstand capability is 65 kA/500 ms, providing high safety in case of faults. The rated impulse voltage is 12 kV, and the overvoltage category is 4, indicating use in environments with high transient voltages.
Technology explained simply
The busbars are made of copper and offer high electrical conductivity. The dimensions of 30 mm x 10 mm and the center-to-center spacing of 60 mm are standardized and allow the use of matching connection adapters and device adapters. The rated voltage of 1000 V AC and 1500 V DC, as well as the rated insulation voltage of 100ed voltage of 1000 V AC and 1500 V DC, ensure safe operating voltage. The frequency of the fundamental wave is 50 to 60 Hz, corresponding to standard grid frequencies. The operating temperature ranges from -5 °C to 55 °C, and the storage temperature from -25 °C to 75 °C.
Compatibility and accessories
The RiLineX board can be mounted horizontally, vertically, and overhead, enabling flexible installation. The baying of multiple boards is done using RiLineX baying connectors, without reducing the short-circuit withstand capability. Compatible accessories include connection adapters, device adapters, fuse switch disconnectors, and fuse elements, specifically developed for integration into the RiLineX system. Using these components enables modular expansion of the system.
Mounting and installation
Mounting is done by securing the board to the enclosure wall, with the pre-mounted busbars already in position. Cable routing in the rear area facilitates integration of control wiring. Baying of multiple boards is achieved using special baying connectors, ensuring a secure electrical connection. Installation is simple and requires no additional tools.
Advantages in operation
The RiLineX board offers significant time savings in planning and documentation through fully digital product data. The pre-assembled design reduces installation time compared to separate components. The high short-circuit withstand capability and certification according to IEC and UL guarantee safe and reliable operational safety. The modular expandability allows flexible adaptation to changing requirements.