| General |
| Material | Polyamide (PA 6), flammability rating according to UL 94, E-Cu |
| Colour | RAL 35745, RAL 9005 |
| Scope of delivery | Including integrated busbars |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Standards | IEC 61 439-1/-2, UL 508 |
| Rated current max. | 550 A |
| Rated current (UL) | 540 A |
| Electrical values UL (SCCR) | 45 kA - 600 V, RMS, unprotected, 100 kA - 600 V, Fuse Class L max. 1600 A, JDDZ/7, 100 kA - 600 V, Circuit Breaker max. 600 A, DIVQ/7, 100 kA - 480 V, Circuit Breaker max. 800 A, DIVQ/7, 65 kA - 600 V, Circuit Breaker max. 800 A, DIVQ/7 |
| Center-to-center spacing of busbars | 60 mm |
| Rated impulse voltage Uimp | 12 kV |
| Rated voltage | 1.000 V AC, 1.500 V DC, 600 V AC (UL), 600 V DC (UL) |
| Rated insulation voltage Ui | 1.000 V AC, 1.500 V DC |
| Rated surge withstand current Ipk | 115,5 kA, 94,5 kA (UL) |
| Rated short-time withstand current / t | 45 kA/500 ms |
| Over voltage category | 4 |
| Pollution degree | 3 |
| Busbar dimensions | 30 mm x 5 mm |
| Number of poles | 3-pole |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Operating temperature range | -5 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 905 mm |
| Height | 246 mm |
| Depth | 49,2 mm |
| Fire load | 94,939 MJ/m² |
| Copper content (kg/piece) | 3,612 |
| PCF/VE (Cradle-to-Gate) | 50,98 |
The Rittal RiLineX complete board type RX 9360004 is a 3-pole power distribution module with a rated current of 550 A, specifically designed for use in industrial enclosures. It features integrated copper busbars with dimensions 30 mm x 5 mm and a center-to-center spacing of 60 mm, ensuring safe and efficient power distribution. The board is designed for enclosures with a width of 1000 mm and has a length of 905 mm. It is made of polyamide (PA 6), classified according to UL 94 E-Cu, providing high flame resistance. The color scheme is RAL 35745 and RAL 9005, enabling visual integration into existing installations.
Applications
The RiLineX board is suitable for applications in alternating current up to 1000 V AC and direct current up to 1500 V DC. It is used in industrial environments where reliable power distribution under high loads is required. The tested short-circuit withstand capability up to 45 kA/500 ms makes it suitable for installations with high electrical loads. The overvoltage category 4 and pollution degree 3 ensure safe operation in environments with increased pollution risk. The operating temperature ranges from -5 °C to 55 °C, making it usable even in climatically demanding environments.
Functions and Equipment in Detail
The board is pre-assembled and includes the integrated busbars, reducing installation time. Cable routing at the rear of the board enables flexible system design, especially for control wiring. The touch protection class IP 2XB protects against direct contact with live parts, with an upgrade to IP 3X possible using additional cover strips (item RX 9365020). Multiple boards can be connected using RiLineX baying connectors (item RX 9360000), without compromising short-circuit withstand capability. Horizontal, vertical, and overhead mounting are possible, increasing flexibility during installation.
Technology Explained Simply
The rated voltage is 1,000 V AC and 1,500 V DC, with UL approval for 600 V AC and 600 V DC. The rated insulation voltage Ui is also 1,000 V AC and 1,500 V DC. The rated impulse voltage Uimp is 12 kV, ensuring high insulation strength against transient voltage surges. The rated impulse current withstand Ipk is 115.5 kA (100 kA according to UL), describing the board’s ability to withstand surge currents under extreme conditions. The frequency of the fundamental wave is between 50 and 60 Hz, ensuring compatibility with European and North American power grids.
Compatibility and Accessories
The RiLineX board is compatible with the baying set RX 9360000, which enables secure and short-circuit-safe connections between multiple boards. Additionally, cover strips RX 9365020 can be used to increase touch protection to IP 3X. Approvals according to IEC 61 439-1/-2 and UL 508 ensure compliance with international safety standards. The electrical values according to UL (SCCR) include various scenarios, including 45 kA at 600 V (unprotected), 100 kA at 600 V with fuse class L (max. 1600 A, JDDZ/7), and 100 kA at 600 V with circuit breaker (max. 600 A, DIVQ/7). For 480 V and 600 V with circuit breaker (max. 800 A, DIVQ/7), values of 100 kA and 65 kA are also specified.
Mounting and Installation
Mounting is done by direct fixation in the enclosure. The pre-assembled design significantly reduces installation time. Horizontal, vertical, and overhead mounting are possible, allowing the board to be used in various configurations. Cable routing at the rear enables structured wiring, especially for control circuits. Multiple boards can be connected using special connectors, with electrical safety ensured by the tested short-circuit withstand capability.
Operational Advantages
Complete digital product data enables time savings in planning and documentation. The pre-assembled design reduces on-site installation time. Simple expandability and the ability to connect multiple boards allow for flexible system design. IEC and UL approvals ensure worldwide usability. High short-circuit withstand capability and robust construction ensure reliable operation under industrial conditions. Materials and construction are designed for long service life, with a copper content per unit of 3.612 kg.