| General |
| Model | For 60 mm busbar systems |
| Material | Polyamide, flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| Colour | Chassis: RAL 7035, Cover: RAL 7035/7001 |
| Terminal space for laminated copper busbars | Clamping space width: 13 mm, clamping space height: 13 mm |
| For rail systems with centre spacing | 60 mm |
| Note | The specified technical data may vary for UR applications. UR applications only in combination with "Special Purpose Fuses". |
| Cable exit | Above/under |
| Electrical connection type | Frame clamp |
| Rated operating current max. | 160 A |
| Rated operating voltage | 690 V, 3~ |
| For NH size | 00 |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 106 mm |
| Height | 194 mm |
| Connection of ring conductors | 4 ‐ 95 mm² |
| Suitable for busbars | Height: 5, 10 mm |
| Number of poles | 3-pole |
| Cross-section round conductor | 4 ‐ 95 mm² |
| Copper content (kg/piece) | 0,2 |
Material: Polyamide (PA 6)
Fire protection corresponding to UL 94-V0
Contact tracks: Electrolytic copper, silver-plated
Colour: Chassis: RAL 7035
Cover: RAL 7035/7001
Basis of test: IEC/DIN EN 60 947-3
DIN EN 60 269-2 (fuse inserts)
Note: The technical data may vary for UR applications. Applications to UR only in conjunction with Special Purpose Fuses.
Packs of: 1 pc(s).
EAN: 4028177540255
Customs tariff number: 85369085
eCl@ss 5.1: 27370302
eCl@ss 7.0: 27371401
ETIM 6.0: EC001040
Design: Size: 00
To fit busbars: with cross-section height: 5 mm
with cross-section height: 10 mm
Number of poles: 3-pole
For bar systems with centre-to-centre spacing: 60 mm
Dimensions: Width: 106 mm
Height: 194 mm
Type of electrical connection: Box terminal
Rated operating voltage: 690 V, 3~
Clamping area for laminated copper bars: Width: 13 mm
Height: 13 mm
Connection for round conductor cross-sections: 4 mm² - 95 mm²
Rated operating current max.: 160 A
Cable outlet: Top/bottom
Weight/pack: 0.94 kg