| General |
| Material | Chassis: Polyamid, cover: ABS, flammability rating according to UL 94-V0 |
| Colour | RAL 7035 |
| Scope of delivery | 3 terminals including cover |
| Terminal space for laminated copper busbars at 5 mm busbar thickness (W x H) | 33 x 26 mm |
| Terminal space for laminated copper busbars at 10 mm busbar thickness (W x H) | 33 x 22 mm |
| Cable exit | Above/under |
| Rated current max. | 800 A |
| Electrical values UL (SCCR) | 65 kA - 480 V, Circuit Breaker max. 600 A, DIVQ/7, 65 kA - 600 V, Fuse Class L max. 800 A, JDDZ/7 |
| Note | At overvoltage category III, a rated operating voltage of 1000 V (AC) is achieved. When using the terminal on 2-pole busbar systems (SV 9340.040), the terminal must be rotated 180° for connection to the PE busbar. |
| Width | 50 mm |
| Height | 88 mm |
| Connection of stranded wires, fine-stranded with ferrule | 95 ‐ 185 mm² |
| Connection of stranded wires, stranded | 95 ‐ 300 mm² |
| Copper content (kg/piece) | 0,096 |
For connecting round conductors and laminated copper bars. Suitable for busbars 12 x 5 to 30 x 10 mm and PLS 800/1600.
Material: Chassis: Polyamide (PA 6.6).
Cover: ABS
Fire protection corresponding to UL 94-V0
Colour: RAL 7035
Supply includes: 3 terminals including cover.
Note: When using the terminal on 2-pole busbar systems (SV 9340.040), the terminal must be rotated through 180° for connection to the PE busbar.
Packs of: 3 pc(s).
EAN: 4028177625259
Customs tariff number: 85369010
eCl@ss 5.1: 27370302
eCl@ss 7.0: 27400613
ETIM 6.0: EC001900
Dimensions: Width: 50 mm
Height: 88 mm
Rated operating voltage: 690 V, 1~
Clamping area for laminated copper bars: Width for busbar thickness 5 mm: 33 mm
Height with busbar thickness 5 mm: 27 mm
Width for busbar thickness 10 mm: 33 mm
Height with busbar thickness 10 mm: 22 mm
Connection for round conductor cross-sections: fine wire with wire end ferrule: 95 mm² - 185 mm²
multi-wire: 95 mm² - 300 mm²
Rated current (max.): 800 A
Cable outlet: Top/bottom
Weight/pack: 1.43 kg