| General |
| Model | 16 A / three-phase |
| Material | Aluminium extruded profile, anodized |
| Basic colour | RAL 9005 |
| Colour | RAL 9005 |
| Options | CMC III CAN-Bus sensors for environmental monitoring connectable, max. 16 sensors |
| Nominal power | 11 kW |
| Electrical connection type | CEE plug/coupler |
| Phases per feed | 3~ |
| Rated current (max.) | 16 A |
| Policies | Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU |
| Standards | EN 62368-1, EN 61000-4, EN 61000-6, EN 55 022 |
| Width | 450 mm |
| Height | 144 mm |
| Depth | 44 mm |
| Interfaces | Fully redundant Ethernet interface 10/100/1000 Mbit/s (2x RJ45, 1x with PoE), USB 2.0 port (USB-A) for mass configuration, firmware update & datalogging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers) |
| Input cable connection (type/length) | H05VV-F5G2.5, 2 m |
| Connection output cable (type/length) | H05VV-F5G2.5, 1,2 m |
The Rittal DK 7979713 is an
Inline Meter, an autonomous energy monitoring unit in the 1 HE/48,3 cm ( 19 inch ) form factor, which is inserted into the supply line of a consumer, a PDU basic, or a modular PDU without metering functionality. The unit measures all key electrical parameters analogous to a metered PDU and provides integrated differential current measurement (Type B) for leakage current monitoring of the connected device. Consumption data can be retrieved via a network interface or locally via a TFT display. The unit is designed for use in existing installations where modern metering functions are to be retrofitted, enabling quick installation with only a short operational interruption.
Applications
This metering module is suitable for energy monitoring in industrial and IT infrastructures, particularly in environments where a PDU without metering functionality is already installed. It is used for monitoring power consumption, voltage, frequency, and leakage currents. The integrated differential current measurement enables detection of leakage currents, which is important for the safety of electrical installations. The unit is especially advantageous in data centers, server rooms, or production facilities where precise energy monitoring and optimization are required.
Functions and Equipment in Detail
The unit features a
fully redundant Ethernet interface with 10/100/1000 Mbit/s (2x RJ45, one of which is PoE-enabled), ensuring a stable network connection. A USB 2.0 port (USB-A) enables mass configuration, firmware updates, and data logging. The
CAN-Bus interface (RJ45) allows connection of up to 16 CMC III CAN-Bus sensors for environmental monitoring. A serial interface RS232 (RJ12) supports connections to LTE units, scripting, CLI, as well as the use of custom certificates and TLS 1.2. Additionally, the unit can send emails on alarms via SMTP, perform user management with rights management, and connect to LDAP(S), Radius, or Active Directory. Connection to up to two Syslog servers is also possible.
Technology Explained Simply
The metering functions include measurement of current, voltage, frequency, power, power factor, and energy consumption. Measurement accuracy is typically ±1 %. The integrated differential current measurement (Type B) monitors leakage currents, which may indicate insulation faults or other electrical disturbances. The unit features an integrated GbE interface with a web server, enabling autonomous operation without additional components. Acoustic alarm notification for threshold exceedances, such as leakage currents, is adjustable. The housing is made of
aluminum extruded profile, anodized, in the color
RAL 9005, ensuring high mechanical stability and corrosion resistance. The design is energy-efficient with low self-consumption.
Compatibility and Accessories
The metering module is designed for use with PDU basic or modular PDUs without metering functions. It is equipped with pre-fabricated connection cables: the input cable is type H05VV-F5G2.5 with a length of 2 m, and the output cable is also H05VV-F5G2.5 with a length of 1.2 m. The electrical connection is made via CEE plug/coupler. The unit is designed for three-phase supply (3~) with a rated current of 16 A and a rated power of 11 kW. The unit complies with the Low Voltage Directive 2014/35/EU and EMC Directive 2014/30/EU, as well as standards EN 62368-1, EN 61000-4, EN 61000-6, and EN 55 022.
Mounting and Installation
Mounting is performed in a 48,3 cm ( 19 inch ) rack in the 1 HE format. The unit is inserted into the supply line of a consumer or a PDU. The pre-fabricated connection cables simplify installation. The unit is immediately ready for use, as the connections are pre-prepared. Installation requires only a short operational interruption.
Operational Advantages
The unit offers high measurement accuracy, comprehensive interface equipment, and integrated leakage current monitoring. The autonomous functionality with an integrated web server reduces dependency on external systems. The ability to connect external sensors via CAN-Bus extends monitoring capabilities. Energy efficiency and low self-consumption contribute to cost-effectiveness. Acoustic alarm notification for threshold exceedances supports quick response to disturbances. The unit is suitable for use in industrial and IT environments where reliable and precise energy monitoring is required.