| General |
| Model | PDU, metered plus |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | Overvoltage protection Type 3 with replaceable diverters during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional overvoltage protection, CMC III CAN-Bus sensors for environment monitoring connectable, max. 16 sensors, other housing colours available |
| Description of measurement functions | Measurement per phase or input, additional measurement per output socket, powerful CPU (ARM Cortex A8), digital input (potential-free contact), additional alarm output/relay output (changeover contact) |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.495 mm |
| Number of sockets and type | 16 x Schuko (Type F, CEE 7/3) |
| Socket outlets | 18 x Schuko |
| Rated operating voltage | 400 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 11 kW |
| Power supplies | Number: 1, phases per input: 3~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 1,800 mm, housing type: VX IT 19"-profile rails: ≥ 1,800 mm |
The Rittal DK 7979533 is a
PDU (Power Distribution Unit) of the
metered plus type, specifically designed for use in IT network and server racks. It serves as an intelligent power distribution unit with integrated energy measurement for each individual outlet socket, enabling monitoring of the power demand of individual consumers. The device is housed in a compact aluminium profile enclosure with a black anodized surface and has a length of 1,495 mm, a width of 44 mm, and a depth of 70 mm. Power supply is via a CEE connection cable with a length of 3 m, supporting a rated operating voltage of 400 V (AC) and a nominal current of 16 A. The maximum nominal power is 11 kW, with power input via a three-phase (3~) connection type.
Applications
The PDU is designed for use in racks of type VX IT, particularly in cabinet frames with a minimum length of 1,800 mm or on 48,3 cm ( 19 inch ) profile rails of corresponding length. When mounted vertically, it can be installed tool-free in Zero-U-Space, minimizing rack space requirements. The colour-coded phase marking (L1=pink, L2=black, L3=white) facilitates identification and maintenance. The unit is suitable for use in IT infrastructures where precise energy monitoring and control are required, for example in data centres, server rooms, or network areas.
Functions and Equipment in Detail
The DK 7979533 features 18 Schuko outlets (CEE 7/3), made of plastic. Energy measurement is performed per phase or input as well as per individual outlet socket, with a measurement accuracy of ±1 % (kWh) according to standard EN 62053-21. Measured values include voltage, current, frequency, active power, active energy, apparent power, apparent energy, power factor (cosPhi), phase angle, and neutral conductor current measurement for unbalanced load detection. An integrated real-time clock with battery backup (up to 10 years, replaceable) ensures correct time display even during power failure. An integrated electromagnetic buzzer enables acoustic alarm signaling in case of exceedances.
Technology Explained Simply
Control is managed by a powerful CPU (ARM Cortex A8), responsible for processing measurement data and communication via various interfaces. The PDU is self-powered, meaning it does not require external power supply, as it features an integrated, fully redundant power supply unit that can be powered from all phases. This ensures fault-tolerant power supply. The display is rotatable and replaceable within the enclosure by 180°, allowing adaptation to different mounting positions. It is a bright TFT display with 128x128 pixels (RGB) and backlighting, showing performance data and basic configuration. Multicoloured LEDs (green/yellow/red) indicate the switching status and limit values for each outlet socket.
Compatibility and Accessories
The PDU supports connection to CMC III CAN-Bus sensors for environmental monitoring, with up to 16 sensors connectable. Optionally, a Type 3 surge protection device with replaceable discharge elements during operation and status monitoring can be integrated. Differential current measurement (Type B) is available per input, phase, or fuse. Accessories include, for example, CAN-Bus cables in various lengths (0.5 m, 1.0 m, 1.5 m), covers for C13 and C19 sockets, mounting adapters, and a numeric code lock for CMC III. The PDU can be combined with an optional surge protection device (article number 7979723).
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of VX IT racks. The delivery includes fastening materials required for installation in the rack. The PDU is designed for vertical mounting, with positioning correctly displayed via position sensors in the display. Installation requires no additional tools, as the fastening mechanism operates tool-free.
Operational Advantages
The PDU offers high operational reliability through redundant power supply and integrated alarm functions. Adjustable limit values for voltage, current, and power per outlet socket enable precise monitoring. Communication is via a fully redundant Ethernet interface (10/100/1000 Mbit/s), compatible with protocols such as HTTP, HTTPS, SSH, Telnet, SNMP, Modbus/TCP, OPC-UA, and FTP/SFTP. Integration into DCIM software is possible via MIBs. User management with rights management, LDAP(S)/Radius/Active Directory integration, and Syslog server connection (up to 2 servers) enables centralized administration. E-mail alarms (SMTP) and an additional relay output (changeover contact) support alarm signaling in critical conditions. The energy-saving design ensures low self-consumption.
Standards and Regulations
The PDU complies with the EMC Directive 2014/30/EU and the Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21 are met. The operating temperature range is 5 °C to 50 °C, with non-condensing humidity between 10 % and 95 %. Storage temperature is -20 °C to 70 °C.