| General |
| Model | 19" version |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | CMC III CAN-Bus sensors for environmental monitoring connectable, max. 16 sensors |
| Description of measurement functions | Measurement per phase or input, additional measurement per output socket, powerful CPU (ARM Cortex A8), digital input (potential-free contact), additional alarm output/relay output (changeover contact) |
| Height | 44 mm |
| Depth | 144 mm |
| Length | 450 mm |
| Number of sockets and type | 4 x C13 / 2 x C19 |
| Socket outlets | 4 x C 13, 2 x C 19 |
| Rated operating voltage | 230 V (AC) |
| Rated current (max.) | 32 A |
| Nominal power | 7,4 kW |
| Power supplies | Number: 1, Phases per input: 1~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Number of RJ45 ports for sensor units max | 2 |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 800 mm, Housing type: VX IT 19"-profile rails: ≥ 800 mm |
The Rittal DK 7979.504 is a
PDU metered plus, an intelligent power distribution unit for IT network and server racks in 48,3 cm ( 19 inch ) format. It serves for central power supply and energy measurement of IT systems and enables precise monitoring of energy consumption per individual outlet socket. The unit is designed for use in racks of type VX IT or TS IT and can be installed tool-free in Zero-U-Space during vertical mounting. The housing consists of an
aluminum profile, black anodized, with plastic sockets, ensuring a robust and durable construction.
Applications
The PDU is designed for use in IT infrastructures, particularly in server and network racks, where precise energy consumption measurement and control are required. It is suitable for racks with a minimum depth of 800 mm, both with VX IT rack frames and 48,3 cm ( 19 inch ) profile rails. The integrated energy measurement per outlet socket enables detailed load analysis and optimization of energy efficiency. The unit is designed for indoor operation, with an operating temperature range of 5 °C to 50 °C and humidity of 10 % to 95 % (non-condensing).
Functions and Equipment in Detail
The PDU features six sockets: four C13 sockets and two C19 sockets, suitable for powering servers, network devices, and other IT components. The rated operating voltage is 230 V (AC), with a maximum rated current of 32 A, corresponding to a rated power of 7.4 kW. Power supply is via a CEE connection cable with a length of 3 m. The unit is self-powered, meaning it does not require external power for its control and measurement functions.
Technology Explained Simply
The PDU integrates a powerful CPU based on the ARM Cortex A8, which handles measurement and control functions. Energy measurement is performed per phase and per outlet socket, with measurement accuracy of ±1 % (kWh) according to EN 62053-21. Measured values include voltage, current, frequency, active power, active energy, apparent power, apparent energy, power factor (cosPhi), phase angle, and neutral conductor current measurement for unbalanced load detection. An integrated real-time clock with battery backup (up to 10 years, replaceable) ensures accurate time-stamping of measurement data. An integrated electromagnetic buzzer enables acoustic alarm signaling when preset thresholds are exceeded.
Compatibility and Accessories
The PDU supports connection of up to 16 CMC III CAN-Bus sensors for environmental monitoring, with two RJ45 ports available for sensor units. Communication is via a fully redundant Ethernet interface (10/100/1000 Mbit/s), which can also be used for connection to external systems such as DCIM software. The unit supports protocols such as HTTP, HTTPS, SSH, Telnet, SNMP v1, v2c, v3, Modbus/TCP, OPC-UA, FTP/SFTP, and MIBs for integration into third-party systems. A serial interface RS232 (RJ12) enables connection to LTE modules, scripting, and CLI access. User management includes rights management, LDAP(S), Radius, and Active Directory integration. Email alarms can be sent via SMTP, and Syslog servers can be connected (up to 2 servers).
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of Rittal VX IT or TS IT racks. The delivery includes mounting hardware required for installation. The unit is designed for vertical mounting, with the display/controller unit being rotatable and replaceable within the housing by 180°. Color-coded phase marking (L1=pink, L2=black, L3=white) facilitates assignment and securing of power circuits.
Operational Advantages
The PDU offers high operational reliability through fault-tolerant power supply, which is redundantly supplied across all phases. Integrated fuse monitoring enables monitoring of fuses within the PDU. Adjustable thresholds for voltage, current, power, and per outlet socket allow individual configuration to prevent overloads. The energy-saving design ensures low self-consumption. Display is via a bright TFT display with 128x128 pixels (RGB) and backlight, which can also operate in energy-saving mode. Multicolor LEDs (green/yellow/red) indicate the switching status and thresholds per outlet socket.
Standards and Regulations
The PDU complies with the EMC Directive 2014/30/EU and the Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21 are met. Measurement accuracy conforms to EN 62053-21, ensuring high reliability of energy measurement. The unit is suitable for use in IT infrastructures with high requirements for safety and reliability.