| General |
| Model | PDU, switched |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | Surge protection Type 3 with replaceable discharge devices during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional surge protection, CMC III CAN-Bus sensors for environmental monitoring connectable, max. 16 sensors, other housing colours available, CMC III CAN-Bus sensors for environmental monitoring connectable, max. 16 sensors, other housing colours available |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.095 mm |
| Number of sockets and type | 18 x C13 / 2 x C19 |
| Socket outlets | 18, 2 |
| Rated operating voltage | 230 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 3,7 kW |
| Power supplies | Phases per input: 1~ |
| Electrical connection type | IEC C20 |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 1,200 mm, housing type: VX IT 19"-profile rails: ≥ 1,800 mm |
The Rittal PDU switched is a compact, switchable power distribution unit for IT network and server racks. It serves for central power supply and control of devices in data centers and IT infrastructures. The device is made of aluminum profile with a black anodized surface and has a total length of 1,095 mm, a width of 44 mm, and a depth of 70 mm. Power distribution is carried out via 18 C13 outlets and 2 C19 outlets, connected to an IEC C20 input. The rated operating voltage is 230 V (AC), the maximum rated current is 16 A, corresponding to a rated power of 3.7 kW. The PDU is designed for single-phase (1~) inputs.
Applications
The PDU is specifically designed for use in Rittal VX IT cabinet frames with a minimum length of 1,200 mm, as well as in VX IT 48,3 cm ( 19 inch ) profile rails with a minimum length of 1,800 mm. Vertical mounting is tool-free in the Zero-U-Space, allowing seamless integration into existing rack systems. The color-coded phase marking (L1=pink, L2=black, L3=white) facilitates assignment and maintenance.
Functions and Equipment in Detail
The PDU features integrated energy measurement at the input and per phase. Measurement accuracy is ±1 % (kWh) according to EN 62053-21. Individual output sockets are switchable, enabling targeted control of connected devices. The device offers programmable power-on behavior after voltage recovery (on/off/last status) and programmable switching behavior based on time or programmable logic. An integrated operating hour counter records total and cyclic operating time, with resettable counting.
Technology Explained Simply
The PDU is self-powered and requires no external power supply. It includes an integrated real-time clock with battery backup, which can last up to 10 years and is replaceable. In case of alarms, an integrated electromagnetic buzzer provides acoustic signaling. Voltage, current, and power thresholds are adjustable, enabling warnings or alarm signals when thresholds are exceeded. The PDU supports connection to CMC III CAN-Bus sensors for environmental monitoring, with up to 16 sensors connectable.
Compatibility and Accessories
Optionally, a Type 3 surge protection device with replaceable discharge elements during operation can be integrated, equipped with status monitoring. Differential current measurement (Type B) is available per input, phase, and fuse. The PDU can be monitored with an optional surge protection device. Connection to external systems is via a fully redundant Ethernet interface (10/100/1000 Mbit/s), suitable for communication with DCIM software and other systems.
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of the Rittal VX IT cabinet frame. The delivery includes mounting hardware. The PDU is designed for use in IT infrastructures requiring stable and monitorable power supply.
Operational Advantages
The PDU offers high measurement accuracy, flexible control of outputs, and comprehensive monitoring capabilities. The integrated real-time clock and operating hour counter enable precise usage documentation. Support for protocols such as SNMP, Modbus/TCP, OPC-UA, and MIB facilitates integration into existing monitoring and management systems. User management with rights management, as well as integration with LDAP(S), Radius, or Active Directory, enables secure and centralized administration. The email alarm function (SMTP) and connection to Syslog servers (up to 2 servers) support proactive fault detection.
The PDU complies with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21 are met. Operating temperature ranges from 5 °C to 50 °C, relative humidity (non-condensing) from 10 % to 95 %. Storage temperature is from -20 °C to 70 °C. The PDU is designed for indoor use, with environmental conditions within specified limits.
Interfaces and Protocols
The PDU features a USB 2.0 interface (USB-A) for mass configuration, firmware updates, and data logging. The CAN-Bus interface (RJ45) enables connection of up to 16 environmental sensors. A serial interface RS232 (RJ12) is available for connecting an LTE unit, scripting, and CLI. Communication is via TCP/IP v4 and v6, DHCP, DNS, NTP, SSH, Telnet, HTTP, HTTPS, SSL, SNMP v1, v2c, and v3, Modbus/TCP, OPC-UA, and FTP/SFTP. Integration into 3rd-party DCIM software is possible via MIB.
Options
Additional options include integrated Type 3 surge protection, differential current measurement (Type B) per input/phase/fuse, monitoring of optional surge protection, and connection of CMC III CAN-Bus sensors.
Operation and Maintenance
The PDU is designed for use in IT infrastructures requiring continuous and reliable power supply. The integrated real-time clock with battery backup enables accurate time measurement even during power failure. The battery is replaceable, extending the clock’s lifespan. Maintenance is performed via integrated interfaces and firmware update capability.
Note: Batteries are not included in the delivery scope.