| General |
| Model | PDU, switched |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.295 mm |
| Number of sockets and type | 24 x C13 / 4 x C19 |
| Socket outlets | 24 x C 13, 4 x C 19 |
| Rated operating voltage | 230 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 3,7 kW |
| Power supplies | Phases per input: 1~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 1,800 mm, housing type: VX IT 19"-profile rails: ≥ 1,800 mm |
The Rittal DK 7979315 is a
switched PDU (Power Distribution Unit) for use in IT network and server racks. It serves as an intelligent power distribution unit with integrated energy measurement per phase and enables individual control of output sockets. The device is housed in a compact aluminium profile with a black anodized surface and is suitable for vertical mounting in the Zero-U-Space of Rittal VX IT or TS IT racks, with tool-free installation. The sockets are made of plastic and are standardized according to IEC 60 320: 24 x C13 and 4 x C19. The rated operating voltage is 230 V (AC), the maximum rated current is 16 A, corresponding to a rated power of 3.7 kW. Power input is via a CEE cable with a length of 3 m.
Applications
The PDU is designed for use in professional IT infrastructures, particularly in server and network racks, where precise power distribution, monitoring, and control are required. It is suitable for racks with a minimum length of 1,800 mm, both with VX IT rack frames and 48,3 cm ( 19 inch ) profile rails. Vertical mounting in the Zero-U-Space enables efficient use of the rack without losing mounting units. The integrated energy measurement per phase allows detailed analysis of energy consumption and supports energy efficiency in data centres.
Functions and Equipment in Detail
The PDU features an
integrated real-time clock with battery backup (max. 10 years, replaceable), which retains time information even during power failure. The switching function allows individual turning on and off of output sockets, with relays designed to be bistable to ensure low power consumption and high switching capacity even at high inrush currents (up to max. 300 A). Control is performed via programmable logic, time schedules, or sequential switching after power restoration to avoid overloading peaks. Relay states are stored even during power failure. An integrated electromagnetic buzzer provides acoustic alarm for warnings or alarm situations.
Technology Explained Simply
The measurement function captures voltage, current, frequency, active power, active energy, apparent power, apparent energy, power factor (cosPhi), phase angle, and neutral conductor current. Measurement accuracy is ±1 % (kWh) according to standard EN 62053-21. The PDU features a bright TFT display (128x128 pixels, RGB) with backlight and energy-saving mode, showing performance data and basic configuration. The display unit is rotatable by 180° and replaceable. Multicolour LEDs (green/yellow/red) indicate switching states and warning or alarm thresholds per phase. Power supply is redundant across all phases, with the integrated power supply fully redundant. The PDU is self-powered and does not require external power supply.
Compatibility and Accessories
The PDU is equipped with a
CAN-Bus interface (RJ45), allowing up to 16 environmental sensors of the CMC III system to be connected. This enables monitoring of temperature, humidity, and other environmental parameters. Additionally, a serial interface RS232 (RJ12) is available, which can be used for connecting an LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, and Syslog server connection (max. 2 servers). The fully redundant Ethernet interface (10/100/1000 Mbit/s) supports protocols such as HTTP, HTTPS, SSL, SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, and MIB for integration into DCIM software. A USB 2.0 port (USB-A) is provided for mass configuration, firmware updates, and data logging.
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of Rittal VX IT or TS IT racks. The PDU is supplied with a tool-free mounting kit, simplifying installation. Colour coding of phases (L1=pink, L2=black, L3=white) and fuse circuits facilitates assignment and maintenance. Mounting materials are included in the delivery scope.
Operational Advantages
The PDU offers high operational reliability through redundant power supply and fault-tolerant design. Energy measurement per phase enables precise consumption analysis and optimization of energy efficiency. Individual control of outputs and programmable switching functions support load distribution and prevent overloads. The integrated real-time clock and storage of relay states ensure continuous operational monitoring even during power failures. Support for numerous protocols and interfaces facilitates integration into existing IT infrastructures and DCIM systems. The operating temperature range is between 5 °C and 50 °C, with humidity (non-condensing) between 10 % and 95 %. The storage temperature range is from -20 °C to 70 °C. The PDU complies with the EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU, as well as standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21.
Delivery Scope
Incl. mounting materials.