| General |
| Model | PDU, metered |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | Overvoltage protection Type 3 with replaceable diverters during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional overvoltage protection, CMC III CAN-Bus sensors for environment monitoring connectable, max. 16 sensors, other housing colours available |
| Description of measurement functions | measurement per phase or input, powerful CPU (ARM Cortex A8), digital input (potential-free contact), additional alarm output/relay output (changeover contact) |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.895 mm |
| Number of sockets and type | 36 x C13 / 6 x C19 |
| Rated operating voltage | 400 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 11 kW |
| Power supplies | Number: 1, phases per input: 3~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Cabinet type: VX IT cabinet frame: ≥ 2,000 mm, cabinet type: VX IT 19"-profile rails: ≥ 2,200 mm |
The Rittal DK 7979240 is a
PDU (Power Distribution Unit) with integrated energy measurement, specifically designed for use in IT network and server racks. As a
metered variant, it enables precise measurement of power consumption values per phase and input, allowing detailed energy management and monitoring in data centers and IT infrastructures. The device features a compact design with a width of 44 mm, a length of 1,895 mm, and a depth of 70 mm, making it suitable for installation in standard 19-inch enclosures. Power distribution is provided via 36 C13 outlets and 6 C19 outlets, standardized according to IEC 60 320. The rated operating voltage is 400 V (AC), with a maximum rated current of 16 A, corresponding to a rated power of 11 kW. Power input is via a CEE supply cable with a length of 3 m.
Applications
The PDU is designed for use in IT infrastructures, particularly in VX IT racks, where a minimum rack frame length of 2,000 mm or 19-inch profile rails of 2,200 mm is required. Vertical mounting is tool-free in Zero-U-Space, simplifying installation in existing systems. The unit is intended for indoor use, with an operating temperature range of 5 °C to 50 °C and humidity of 10 % to 95 % (non-condensing). Storage is possible in the range of -20 °C to 70 °C.
Functions and Equipment in Detail
The DK 7979240 features a powerful CPU based on the ARM Cortex A8, supporting energy management and monitoring. Measurement accuracy is ±1 % (kWh) according to EN 62053-21. Energy measurement is performed per phase or per input, enabling detailed analysis of power consumption. Additionally, total and cyclic operating hour counters are integrated and resettable. The unit includes an integrated real-time clock with battery backup (up to 10 years, replaceable battery), ensuring time continuity even during power failure. An integrated electromagnetic buzzer provides acoustic alarm notification when predefined thresholds for voltage, current, and power are exceeded.
Technology Explained Simply
The PDU is self-powered and does not require external power for its control and monitoring functions. The self-consumption is low, increasing efficiency. The socket outlets are made of plastic, and the enclosure is made of black anodized aluminum profile, ensuring a robust and durable construction. Color coding of phases (L1=pink, L2=black, L3=white) facilitates identification and maintenance. The PDU is equipped with a display showing key operational data.
Compatibility and Accessories
The PDU is equipped with a variety of interfaces, including a fully redundant Ethernet interface (10/100/1000 Mbit/s), a USB 2.0 interface (USB-A) for mass configuration, firmware updates, and data logging, and a CAN-Bus interface (RJ45) for connecting up to 16 CMC III environmental sensors. A serial RS232 interface (RJ12) enables connection to an LTE unit, scripting, CLI, and use of custom certificates/TLS 1.2. Integration into DCIM software is possible via MIB and protocols such as SNMP v1, v2c, v3, Modbus/TCP, and OPC-UA. The unit supports email alerts on alarm (SMTP), user management with rights management, and integration with LDAP(S), Radius, or Active Directory. Connection to Syslog servers (up to 2 servers) is also possible. Available accessories include various CMC III CAN-Bus cables, covers for C13 and C19 outlets, mounting adapters, a universal lock for C14/C20 plugs, a numeric code lock for CMC III, a VX IT CMC III transponder reader (RAL 9005), and a PDU surge protector (rated power 11 kW, rated current 50 A, part number 7979723).
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of VX IT racks. The delivery includes the required mounting hardware. Vertical mounting is possible without tools, speeding up installation and simplifying maintenance. The PDU is designed for use in 19-inch enclosures, requiring minimum lengths of rack frames (≥ 2,000 mm) and 19-inch profile rails (≥ 2,200 mm).
Operational Advantages
The DK 7979240 offers high measurement accuracy, comprehensive monitoring functions, and flexible integration into existing IT infrastructures. Support for multiple protocols and interfaces enables seamless integration into DCIM systems. The integrated real-time clock and acoustic alarm ensure reliable operational monitoring. Tool-free mounting and low self-consumption increase efficiency and reduce maintenance effort. Options such as Type 3 surge protection with replaceable discharge devices during operation, residual current measurement (Type B) per input/phase/fuse, and connection to environmental sensors extend the functionality and safety of the system.