| General |
| Material | Socket inserts: Plastic (PA6 GF 30 V1), Profile: Aluminium, anodised |
| Scope of delivery | PSM measurement modules with CAN-Bus, CAN-Bus connection cable, 1 m |
| Distribution power per module | 3.680 W |
| Switching power per relay | 4.000 VA |
| Length | 500 mm |
| Pollution degree | 2 |
| Interface bus system | 2 x CAN-Bus interface to CMC III (max. 16 at PU/4 at PU Compact), 2 x RJ45 (connection to CMC) |
| Number | 1 |
| Relay version | Double coil, bistable |
| Rated operating voltage | 18 V (DC) - 24 V (DC), power supply via CMC III system |
| Input voltage | 230 V AC |
| Input voltage tolerance | ± 10 % |
| Nominal current | 16 A |
| Required module slots (number) | 2 |
| Number of participants PU compact (max.) | 4 |
| Number of participants PU (max.) | 16 |
| Policies | Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU |
| Degree of protection IP according to IEC 60 529 | IP 20 |
| Monitoring | Alarm management via CMC III (e.g. email or SMS), visualisation of switching status on CMC III website and RiZone, up to 16 PSM modules on one CMC III PU (per IP address), rights management via CMC III (e.g. restriction of switching functionality) |
| Standards | EN 50 600-2-2, EN 60950 |
| Description of measurement functions | Voltage V, current A, frequency Hz, active power kW, active energy kWh, reactive power kVar, reactive energy kVarh, apparent power kVA, apparent energy kVAh, power factor cosPhi, crest factor (peak factor), operating hour counter d, h, min, measurement accuracy of ± 1 %, measurement functions resettable/reset via software/interval measurement: active energy kWh, operating hour counter h, thresholds (voltage, current, power) freely configurable |
| Protocols | Network functionality (only in combination with CMC III system): IPv4, IPv6, SNMPv3, Modbus/TCP, OPC-UA |
| Width | 53 mm |
| Depth | 45 mm |
| Maximum operating altitude above sea level | 2.000 m |
| Operating temperature range | 5 °C...60 °C |
| Humidity (non-condensing) | 90 % |
| Socket outlets | 2 x C13 / 4 x C19 |
| Relative humidity (non-condensing) | 10 % |
| Storage temperature range | -20 °C...70 °C |
| PCF/VE (Cradle-to-Gate) | 3.8 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal DK 7859420 is a
PSM measuring module with integrated switching functionality, specifically designed for modular power distribution in PSM power rails. It extends existing power rails with the capability for energy measurement and individual control of output sockets. The module is suitable for use in server rooms, data centres and industrial installations where precise monitoring and control of power consumption is required. It occupies two module slots in the power rail and is compatible with the European PSM programme. Power supply is via the CMC III system, with a rated operating voltage between 18 V (DC) and 24 V (DC). The input is designed for a voltage of 230 V AC, with a tolerance of ±10 %, enabling flexible adaptation to various network conditions.
Applications
The module is designed for use in IT infrastructures, industrial control systems and energy-efficient installations. It is particularly suitable for retrofitting existing PSM installations to enable energy data acquisition or switching capability for connected loads. The maximum distribution power is 3,680 W, with a rated current of 16 A. The operating temperature ranges from 5 °C to 60 °C, allowing use in environments with moderate to high temperatures. The maximum altitude of use above sea level is 2,000 m, making it suitable for high-altitude locations. The relative humidity (non-condensing) is between 10 % and 90 %, ensuring broad usability in various climate zones.
Functions and Equipment in Detail
The module features six output sockets: four C19 sockets and two C13 sockets, standardised according to IEC 60 320. The switching functionality is achieved via relays with dual coils and bistable design, with a switching capacity of 4,000 VA per relay. The measurement functions include voltage (V), current (A), frequency (Hz), active power (kW), active energy (kWh), reactive power (kVar), reactive energy (kVarh), apparent power (kVA), apparent energy (kVAh), power factor (cosPhi), crest factor (peak factor) and operating hour counter (d, h, min). The measurement accuracy is ±1 %, ensuring high reliability of the data. The measured values can be displayed locally on a backlit LC display, which changes to red when current or power limits are exceeded. Threshold values for voltage, current and active power are freely configurable.
Technology Explained Simply
Communication is via CAN-Bus, with two CAN-Bus interfaces available for direct connection to the CMC III system. Additionally, two RJ45 connectors are provided, enabling connection to the CMC. Network functionality includes IPv4, IPv6, SNMPv3, Modbus/TCP and OPC-UA, but only in conjunction with the CMC III system. Monitoring functions include alarm management via CMC III (e.g. by email or SMS), visualisation of switching status on the CMC III website and RiZone, and rights management via CMC III (e.g. restriction of switching functionality). Up to 16 PSM modules can be connected to one CMC III PU (per IP address). The measurement functions are resettable and can be reset via software or interval measurement (e.g. active energy kWh, operating hour counter h).
Compatibility and Accessories
The module is compatible with the European PSM power rail programme and can be retrofitted into existing installations. It is designed for use with CMC III systems. Suitable accessories include the PDU Metered 16A/1P IEC-C20 6xC13 (48,3 cm ( 19 inch )), which provides supplementary power distribution with measurement functionality. The modules can be rotated in redundant systems to enable circuit switching. The protection rating IP 20 according to IEC 60 529 protects against finger contact and solid foreign objects, but not against water or dust.
Mounting and Installation
Mounting is simple and shock-protected via Plug & Play, even during operation. The module is easily mountable and demountable in the power rail, enabling flexible use at various locations. Dimensions are 500 mm (length), 53 mm (width) and 45 mm (depth). Materials consist of socket inserts made of plastic (PA6 GF 30 V1) and an anodised aluminium profile. The pollution degree class is 2, requiring use in environments with low pollution.
Operational Advantages
The module facilitates compliance with requirements from ISO 50001 and EN 50600-2-2, which relate to energy efficiency and energy management. Local display of measured values and visual warning when limits are exceeded enable quick response. The integrated switching functionality allows targeted control of connected devices, achieving efficient energy management and improved system availability. Support via the CMC III system enables central monitoring and control via various protocols, simplifying integration into existing IT infrastructures.
Scope of Delivery
The product is delivered with one PSM measuring module with CAN-Bus and one CAN-Bus connection cable (length 1 m).
Standards and Regulations
The module complies with the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU. Standards EN 50 600-2-2 and EN 60950 are met. The PCF values (Cradle-to-Gate) are 3.8 kg CO2 eq (Category B), with the value approximately calculated based on product weight and self-declared.