| General |
| Technical data | Extinguishing agent discharge via propellant cartridge, integrated electrical actuation unit, integrated extinguishing agent monitoring (indication of >15 % loss), maximum permissible protection volume: 2.8 m³ |
| Material | steel sheet |
| Colour | Housing: RAL 7035, Front: RAL 9005 |
| Extinguishing agent | Type: FK 5-1-12, fill volume: 1.8 l |
| Tank | Material: Aluminium, Volume: 2 l |
| Interfaces | 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 receptacles), 1 x/1 x input for door contact switch (terminal/RJ12 receptacle), 2 x CAN connection networking master-slave, 2 x connection (external alarm/hand call point), 1 x voltage output for DET-AC Slave III (24 V DC max. 500 mA), 1 x USB, 2 x CAN bus interface to CMC III (max. 16 at PU/4 at PU Compact) |
| Uninterrupted mains power operation | ca. 4 h |
| Note | The system is designed exclusively for use in enclosed, non-accessible cabinet systems with a maximum volume of 2.8 m³. For proper installation and commissioning of the fire alarm and extinguishing system, the system must be installed by a trained installer. Rittal is happy to support you and offers the corresponding service. |
| Width | 482,6 mm |
| Height | 44 mm |
| Depth | 660 mm |
| Operating temperature range | 10 °C...40 °C |
| Storage temperature range | -20 °C...65 °C |
| Storage temperature range for batteries | -15 °C...40 °C |
| Relative humidity (non-condensing) | 96 % |
| Rated operating voltage | 24 V (DC) |
| PCF/VE (Cradle-to-Gate) | 72.8 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The DK 7338321 is an add-on unit of the Rittal DET-AC III Slave system, specifically designed as an additional fire suppression unit for closed, non-accessible server rack systems. It is used in combination with a DET-AC III Master unit to enable fire suppression in adjacent racks. The Slave unit is responsible for storing the extinguishing agent for the respective rack, while detection and activation of the suppression are managed by the central Master unit. Upon triggering of the main alarm, the Master unit simultaneously activates all connected Slave units, allowing up to five adjacent racks within a rack row to be suppressed.
Applications
This unit is exclusively intended for use in closed, non-accessible rack systems with a maximum protection volume of 2.8 m³. It is particularly suitable for IT infrastructures, server rooms, and other technical rooms where rapid and reliable fire suppression is required without damaging electronic components due to the extinguishing agent. The system is designed for use in 48,3 cm ( 19 inch ) racks and occupies only 1 U, enabling a compact installation.
Functions and Equipment in Detail
The DK 7338321 features an integrated electrical activation unit and extinguishing agent discharge via a propellant cartridge. The extinguishing agent used is FK 5-1-12, an environmentally friendly, non-conductive gas that is safe for IT components. The fill volume is 1.8 liters, and the aluminum tank has a volume of 2 liters. The integrated extinguishing agent monitoring indicates when the agent loss exceeds 15%, providing early warning for necessary refilling.
Technology Explained Simply
The unit is powered by a nominal operating voltage of 24 V (DC). In the event of a power interruption, it can continue to operate for approximately 4 hours. Communication is via CAN-Bus interfaces, enabling networking between Master and Slave units. Additionally, two CAN-Bus interfaces are available for integration with the CMC III monitoring system, allowing the system to be incorporated into existing monitoring systems. The interfaces also include potential-free relay outputs for pre-alarm and main alarm as well as general fault, an input for door contact switches, connections for external alarm signaling and manual call points, and a USB interface.
Compatibility and Accessories
The DK 7338321 is designed for use with the DET-AC III Master unit and can be combined with the EFD III fire early detection system. Compatible accessories include the pipe kit for DET-AC III/EFD III, the DS sealing kit for TS IT and LCP, the CMC III access sensor VX, and slide rails for TS IT/VX IT with a length of 600–825 mm and a load capacity of 80 kg. These components support the installation and operation of the system.
Installation and Mounting
Professional installation and commissioning of the fire detection and suppression system must be carried out by a trained installer. The unit is designed for installation in the 48,3 cm ( 19 inch ) rack space of server rack systems. Dimensions are 482.6 mm (width), 44 mm (height), and 660 mm (depth). The operating temperature range is between 10 °C and 40 °C, and the storage temperature range is between -20 °C and 65 °C. Relative humidity must not exceed 96 % (non-condensing).
Operational Advantages
The unit provides reliable and rapid fire suppression in multiple adjacent racks. The use of FK 5-1-12 ensures a safe and environmentally compatible solution that does not damage IT components. The integrated monitoring and networking capability with the CMC III system enable centralized monitoring and control. Certification by VdS Schadenverhütung GmbH confirms the reliability and safety of the system.
The DK 7338321 is therefore a powerful add-on unit for existing DET-AC III Master systems, enabling fire suppression in multiple racks without impairing the functionality of the IT infrastructure. The unit is designed for use in closed, non-accessible rack systems and requires professional installation by a trained installer.