| General |
| Material | steel sheet |
| Colour | Housing: RAL 7035, Front: RAL 9005 |
| Interfaces | 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 sockets), 1 x/1 x input for door contact switch (terminal/RJ12 socket), 2 x CAN connection for master-slave networking, 3 x connection (external alarm/hand call point/tank and level), 1 x voltage output for DET-AC Slave III (24 V DC max. 500 mA), 1 x USB, 2 x CAN-Bus interface to CMC III (max. 16 at PU/4 at PU Compact) |
| Uninterrupted mains power operation | ca. 4 h |
| Note | The system is designed exclusively for use in enclosed, non-accessible cabinet systems. For proper installation and commissioning of the fire detection and extinguishing system, the system must be installed by a trained installer. Rittal is happy to support you and offers the corresponding service. |
| Display | Display with plain text and 6 LEDs |
| Sensing technology | Optical smoke detector (sensitivity: approx. 3.5 %/m light obscuration), Optical smoke detector HS (sensitivity: approx. 0.25 %/m light obscuration) |
| Width | 482,6 mm |
| Height | 44 mm |
| Depth | 490 mm |
| Operating temperature range | 10 °C...40 °C |
| Storage temperature range | -20 °C...65 °C |
| Storage temperature range for batteries | -15 °C...40 °C |
| Relative humidity (non-condensing) | 96 % |
| Rated operating voltage | 100 V - 240 V, 1~, 50 Hz/60 Hz |
| Airflow monitoring | approx. ±10 % of total airflow |
| PCF/VE (Cradle-to-Gate) | 57.2 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal fire early detection system DK 7338221, type EFD III, is a compact 48,3 cm ( 19 inch ) mounting solution with a space requirement of 1 U, specifically designed for use in enclosed, non-accessible enclosure systems. The device integrates an active smoke extraction system, where an integrated fan continuously draws air through a pipe system from the area to be protected. The drawn air passes by two optical smoke detectors, with the highly sensitive detector (sensitivity approx. 0.25 %/m light obscuration) triggering a pre-alarm and the second detector (sensitivity approx. 3.5 %/m light obscuration) activating the main alarm. The detectors are permanently monitored by the evaluation and control electronics for functionality, ensuring high reliability of detection.
Applications
The system is intended for use in enclosed server and enclosure cabinets, where early fire detection is critical. It is particularly suitable for IT infrastructures, industrial control systems, and other installations where fire risk exists due to electronic components. The construction from sheet steel in the colours RAL 7035 (enclosure) and RAL 9005 (front) ensures a robust and long-lasting installation in the cabinet.
Functions and equipment in detail
The system features a display with text readout and six LEDs for visual status indication. Alarm and fault signals are transmitted via potential-free relay outputs (pre-alarm and main alarm, as well as collective fault), with connections available both via terminals and RJ12 sockets. Additionally, there is an input for a door contact switch, enabling monitoring of the cabinet status. The integrated CAN-Bus interface allows networking with the CMC III monitoring system, with up to 16 systems connectable to one PU or up to 4 to a PU Compact. A USB port is also provided.
Technology explained clearly
The system operates with a rated supply voltage of 100 V to 240 V, 1~, 50 Hz/60 Hz. In the event of a power failure, an internal power supply ensures uninterrupted operation for approximately 4 hours. Airflow monitoring is performed with an accuracy of approx. ±10 % of the total airflow, ensuring that suction efficiency is maintained. The operating temperature range is between 10 °C and 40 °C, with storage temperature ranging from -20 °C to 65 °C. Relative humidity may reach up to 96 % (non-condensing). The system is designed for use in enclosed, non-accessible enclosure systems and requires professional installation and commissioning by a qualified installer.
Compatibility and accessories
The system is compatible with the CMC III monitoring system, with networking achieved via the CAN-Bus interface. Suitable accessories include the CMC III CAN-Bus cable RJ45 with a length of 1.0 m, enabling the connection between the fire early detection system and the monitoring system. The system features a voltage output for DET-AC Slave III with 24 V DC and a maximum current of 500 mA, which can be used for additional sensors or modules.
Mounting and installation
Mounting is performed in a 48,3 cm ( 19 inch ) frame of an enclosure system, with the system dimensions being 482.6 mm (width), 44 mm (height), and 490 mm (depth). Installation must be carried out by a qualified installer to ensure proper commissioning and system safety. Rittal offers corresponding services for this purpose.
Advantages in operation
Early fire detection via the active smoke extraction system enables rapid response to fire beginnings, minimizing damage to electronic components and systems. The integrated monitoring of detectors and networking capability with the CMC III system increase reliability and transparency of monitoring. The compact design with only 1 U optimizes space usage in the cabinet, while the potential-free relay outputs allow flexible integration into existing alarm and control systems. The system has been tested by VdS Schadenverhütung GmbH, confirming the quality and safety of the system.