| General |
| Model | Vision panel: single-pane safety glass, 3 mm, spring damper for flap opening, magnets for fixing flaps, flaps open in de-energized state, vision door: 2x single-pane safety glass, tinted, single-piece, with ventilation flaps, frame: aluminium extruded profile |
| Technical data | Ventilation flap construction outward: 200 mm (in open position), Mechanism construction inward: 52.5 mm, Door hinge: right (for single doors, hinge position changeable from right to left), Cable connection from door hinge: 2.5 m |
| Function principle | Controlled via CMC III Door Control Module (DCM), Integrated vertical ventilation flaps open automatically in emergency – in case of cooling system failure or activation of fire suppression system – air in the room is used for emergency cooling depending on room volume and temperature, or fire suppressant gas can directly enter IT cabinets, Front and rear doors of the ADO system must always be used |
| Material | Frame: aluminium extruded profile, vision panels: single-pane safety glass, tinted |
| Scope of delivery | Vision door with comfort handle for profile half-cylinder with security locking 3524 E |
| At DC | 0,78 A |
| Width | 800 mm |
| Height | 2.200 mm |
| Degree of protection IP according to IEC 60 529 | IP 20 with closed ventilation flaps |
The Rittal VX 7030265 is an aluminium viewing door for VX IT enclosures, specifically designed for the Automatic Door Opening (ADO) system. It replaces the standard door and enables automatic opening of integrated ventilation flaps in an emergency, for example, in case of cooling system failure or activation of a fire extinguishing system. The door has dimensions of 800 mm width and 2,200 mm height and features two tinted single-glazed safety glasses with a thickness of 3 mm, mounted in a frame made of aluminium extruded profile. The ventilation flaps open automatically in the de-energised state, held closed by six electric magnets in the normal state. The opening is actuated by six spring dampers, which also provide the primary opening force to overcome underpressure.
Applications
The viewing door is designed for use in IT infrastructures where emergency cooling or direct supply of extinguishing gas into the enclosure is required. The automatic opening of the ventilation flaps ensures that in the event of cooling failure, ambient air can be used to cool the enclosure contents. When a fire extinguishing system is activated, the extinguishing gas can flow directly into the enclosure, increasing the system's effectiveness. The door is intended for use in racks equipped with the CMC III Door Control Module (DCM), which controls the operation.
Functions and Equipment in Detail
The ventilation flaps extend 200 mm into the escape route when open, while the mechanism extends 52.5 mm into the enclosure from the inside. The door is fitted with a comfort handle for half cylinder and a security lock 3524 E. Manual opening of the door does not affect the state of the ventilation flaps. Control is via the CMC III Door Control Module, with power supplied through this module. The rated voltage is 24 V DC, and the rated current is 780 mA. The door is designed for use at temperatures from -5 °C to +45 °C and relative humidity from 5 % to 95 % (non-condensing).
Technology Explained Simply
The integrated ventilation flaps open automatically when the power supply is interrupted, which occurs during a power failure or activation of an emergency system. The flaps are open in the de-energised state, meaning they are immediately released in the event of a power failure. The magnets holding the flaps closed lose their effect without power, allowing the spring dampers to open the flaps. The door is designed to be installed without modifying the existing locking system. Control is via the CMC III system, which triggers the opening of the flaps in case of overheating or alarm.
Compatibility and Accessories
The viewing door is intended for use with the CMC III Door Control Module (DCM). Both the front and rear doors of the ADO system must always be used to ensure proper function. Compatible accessories include, among others, the CMC III power supply, various comfort handles for half cylinder in different versions, including RAL 9005 and stainless steel, as well as an online comfort handle VX with master key function and a comfort handle VX with numeric code for VX/VX IT.
Mounting and Installation
The door is designed for mounting on VX IT racks. The hinge is standard on the right, but can be changed from right to left for single-piece doors. The connection cable has a length of 2.5 m from the hinge. Installation requires connection to the CMC III control system, with power supplied via the DCM. The door is designed for IT infrastructures requiring emergency cooling or direct extinguishing gas supply.
Operational Advantages
The automatic opening of ventilation flaps in an emergency increases the safety and efficiency of the IT infrastructure. Using ambient air for emergency cooling can prevent damage to IT equipment. Direct supply of extinguishing gas into the enclosure improves the effectiveness of the fire protection system. The door is robustly constructed with an aluminium extruded profile frame and tinted single-glazed safety glass, ensuring high security. The ventilation flaps extend only 200 mm into the escape route, minimising space requirements. Compatibility with the CMC III system enables central control and monitoring.
The protection rating IP 20 according to IEC 60 529 applies with closed ventilation flaps. The door is therefore suitable for indoor use where no direct contact with water or dust is expected. Delivery includes the viewing door with comfort handle for half cylinder and security lock 3524 E.