| General |
| Model | Vision windows: single-pane safety glass, tinted, spring dampers for flap opening, magnets for securing flaps, flaps open in de-energised state, vision door: 2x single-pane safety glass, tinted, single-piece, with ventilation flaps, frame: aluminium extruded profile |
| Technical data | Ventilation flap construction outward: 200 mm (in open position), Mechanism construction inward: 52.5 mm, Door hinge: right (for single doors, hinge position changeable from right to left), Cable connection from door hinge: 2.5 m |
| Function principle | Controlled via CMC III Door Control Module (DCM), Integrated vertical ventilation flaps open automatically in emergency – in case of cooling system failure or activation of fire suppression system – air in the room is used for emergency cooling depending on room volume and temperature, or fire suppressant gas can directly enter IT cabinets, Front and rear doors of the ADO system must always be used |
| Material | Frame: aluminium extruded profile, vision panels: single-pane safety glass, tinted |
| Scope of delivery | Vision door with comfort handle for profile half-cylinder with security locking 3524 E |
| At DC | 0,78 A |
| Width | 800 mm |
| Height | 2.000 mm |
| Degree of protection IP according to IEC 60 529 | IP 20 with closed ventilation flaps |
The Rittal VX 7030263 is an aluminium viewing door for the VX IT system, specifically designed for the Automatic Door Opening (ADO) system. It replaces the standard door and enables automatic opening of the integrated ventilation flaps in an emergency, such as during a power failure or activation of a fire suppression system. The door has dimensions of 800 mm width and 2,000 mm height and is equipped with two tinted single-pane safety glass viewing panels, ensuring high security. The frame is made of aluminium extruded profile, providing high stability and mechanical strength.
Applications
The viewing door is intended for use in IT enclosures, particularly in environments where emergency cooling or direct supply of fire suppressant gas into the enclosure is required. The automatic opening of ventilation flaps during power failure or alarm allows efficient use of room air for cooling or supply of fire suppressant gas, depending on the application. The door is designed for use in racks of the VX IT system and must always be combined with front and rear doors in the ADO system.
Functions and Equipment in Detail
The integrated vertical ventilation flaps open automatically in an emergency when the power supply fails. The flaps are held closed by six electric magnets and open via spring dampers when power is lost. The opening is mechanical and independent of manual door operation. In the open position, the flaps extend 200 mm into the escape route, while the mechanism extends 52.5 mm deep into the enclosure from the inside. The door is equipped with a comfort handle for half cylinder and a security lock 3524 E.
Technology Explained Simply
The door is controlled via the CMC III Door Control Module (DCM). Power supply is provided by the DCM, which delivers a rated voltage of 24 V DC and a rated current of 780 mA (0.78 A). The ventilation flaps are designed to be supported by additional mechanical springs under negative pressure in the enclosure, enhancing the opening force. The protection rating IP 20 according to IEC 60 529 applies when the ventilation flaps are closed, providing protection against contact with moving parts and against solid foreign objects, but not against water. The door is designed for use in a temperature range of -5 °C to +45 °C and relative humidity of 5 % to 95 % (non-condensing).
Compatibility and Accessories
The door is intended for use in the ADO system and must be connected to the CMC III Door Control Module (part number 7030.501). The connection cable has a length of 2.5 m from the door hinge. Compatible accessories include various comfort handles for half cylinder, such as models in RAL 9005, stainless steel, or with code lock function, as well as the CMC III Online comfort handle VX with master key function. The door is designed for single-piece doors, with the hinge standard on the right, but can be changed from right to left for single-piece doors.
Installation and Mounting
Installation is carried out on VX IT racks. The door replaces the standard door and requires no modification to the locking system. The integrated ventilation flaps operate independently of manual door opening and open automatically in case of power failure. Connection to the CMC III Door Control Module is required to enable the automatic opening functions. The door is supplied with a connection cable of 2.5 m length, running from the door hinge.
Operational Advantages
The automatic opening of ventilation flaps during power failure or alarm enables rapid response to emergencies. The use of room air for emergency cooling or direct supply of fire suppressant gas into the enclosure increases safety and efficiency. The construction with aluminium extruded profile and single-pane safety glass ensures stability and security. The integrated mechanism with spring dampers and magnets ensures reliable and maintenance-friendly operation. The door is designed for use in IT infrastructures where high availability and security are required.
Scope of Delivery
The viewing door is delivered with a comfort handle for half cylinder and a security lock 3524 E. The connection cable has a length of 2.5 m. The door includes the integrated ventilation flaps and the necessary mechanism for the automatic opening function. Batteries are not included.