| General |
| Function principle | Switches 2 outputs, measures voltage, current, power, energy, controls and switches fans, heaters, loads |
| Material | Plastic, front: smooth, housing: textured |
| Colour | Housing: RAL 7035, Front: RAL 9005 |
| Scope of delivery | CMC III Power Unit, including mounting hardware for surface mounting |
| Input connection | Cold appliance plug C14 |
| Interface bus system | 2 x RJ45 CAN-bus |
| Number of participants per IoT interface (max.) | 16 |
| Number of participants PU (max.) | 8 |
| Note | Cannot be operated with the Processing Unit Compact, for fan control, one filter 7030051 is required per fan |
| Width | 138 mm |
| Height | 40 mm |
| Depth | 132 mm |
| Output connections | 2 x cold appliance socket C13, switchable |
| Measurement range cos φ | 0 ‐ ± 90 ° |
| Energy consumption | 0 ‐ 1,000,000 kWh |
| Effective power | 46 ‐ 2,3 |
| Rated frequency | 50 ‐ 60 Hz |
| Operating temperature range | 0 °C...55 °C |
| Humidity (non-condensing) | 5...95 % |
| Fuse | Circuit breaker/fuse: 10 A |
| Voltage | 110 ‐ 230 V |
The input is switched to the outputs via two relays. In this way, the outputs may be linked to measurement values and therefore switched automatically. Examples of potential applications include fan regulation. Manual switching via the CMC III operating interface is likewise supported. Each output is monitored individually, and various values are measured.
Benefits: Fast connection and automatic detection via plug & play
Function principle: For controlling and switching fans, heaters, equipment
Measurement of voltage, current, power, work
Switches 2 outputs
Power is supplied via the CAN-BUS interface.
Status display via integral LED
Material: Plastic
Front: Smooth
Enclosure: Textured
Colour: Enclosure: RAL 7035
Front: RAL 9005
Protection category IP to IEC 60 529: IP 30
Supply includes: CMC III Power Unit
Operating manual
Mounting accessories for mounting on surfaces
Mounting clips for support rails
Packs of: 1 pc(s).
EAN: 4028177659377
Customs tariff number: 85311095
eCl@ss 5.1: 27189253
eCl@ss 7.0: 27189253
ETIM 6.0: EC002627
Dimensions: Width: 138 mm
Height: 40 mm
Depth: 132 mm
Rated operating voltage: 100 V - 230 V, 1~, 50 Hz/60 Hz
Maximum no. of users: CMC III Processing Unit: 16
Installation dimensions: Installation depth: 120 mm
Build depth: 12 mm
Operating temperature: Operation (environment): +0°C...+55°C
Ambient humidity (non-condensing): Operation (environment): 5 % - 95 %
Pre-fuse: 10 A
Connections: Input: IEC 320 connector C14
Output: 2 x IEC 320 socket C13, switched
Number of connections: 2
Measurement range: Voltage: 100 V - 230 V
Frequency: 0 Hz - 60 Hz
Amperage: 200 mA - 10 A
cos f: 0 ° - 90 °
Active power: 46 W - 2.3 kW
Energy consumption: 0 kWh - 1000000 kWh
Interfaces/connections: Bus system: 2 x RJ45 CAN bus
Weight/pack: 0.56 kg