| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 5.5 kW, cooling capacity L35 L35/60 Hz: 5.5 kW, cooling capacity L35 L50/50 Hz: 3.8 kW, cooling capacity L35 L50/60 Hz: 3.8 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 2,35 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance coefficient L35 L35 (EER) 50 Hz: 2.39, Cooling performance coefficient L35 L35 (EER) 60 Hz: 2.39 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.76 kg, Quantity compression system: 1.04 kg, Quantity heat pipe system: 0.72 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 2.3 kW, Rated power L35 L35/60 Hz: 2.3 kW, Rated power L35 L50/50 Hz: 2.2 kW, Rated power L35 L50/60 Hz: 2.2 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 352.59 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3489.940 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of 5.5 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz, and is designed for use in industrial environments. The unit is made of
steel sheet and has a color according to
RAL 7035. Dimensions are 450 mm width, 1,600 mm height, and 393 mm depth, with a mounting cutout requirement of 433 mm width and 1,579 mm height.
Wall mounting is intended; full enclosure installation is not possible.
Applications
This cooling unit is suitable for use in enclosures in semi-outdoor environments, with detailed application information available in the instruction manual. It is designed for operating temperatures from -20 °C to 60 °C, with the refrigerant circuit operating between 3 °C and 60 °C in active mode and the Heat Pipe system between -20 °C and 45 °C. Storage temperature ranges from -40 °C to 70 °C. Temperature control is managed by an
e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Functions and Equipment in Detail
The unit features a
condenser with hydrophobic RiNano coating, which reduces condensation formation and simplifies maintenance. The integrated
electrical condensate evaporation ensures that condensate is evaporated directly within the unit, eliminating the need for an external drain. The unit is
pre-wired for connection with a plug-in terminal strip and includes the
mounting hardware for installation. Air performance is 2,300 m³/h for both the external and internal circuits, ensuring efficient air circulation within the enclosure.
Technology Explained Simply
The cooling capacity is achieved through a speed-controlled compression system and
Heat Pipe technology, enabling component-friendly cooling and extending the service life of components within both the enclosure and the cooling unit. Energy efficiency is characterized by an
Energy efficiency ratio (EER) of 2.39 at 50 Hz and 60 Hz, and a
Seasonal energy efficiency ratio (SEER) of 5.6. The rated power is 2.35 kW. The refrigerant
R-1234yf is used, which has a Global Warming Potential (GWP) of 0.5, resulting in very low environmental impact. The total refrigerant charge is 1.76 kg, with 1.04 kg in the compression system and 0.72 kg in the Heat Pipe system. The CO₂ equivalent (CO₂e) is 0 t.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ cooling units, the
IoT Interface with article number 3124.300 can be used to monitor device data, statuses, and system messages. Available accessories include, among others, a
condensate hose 12 x 2 mm, length 10 m, a
run-on roller, a
steel sheet door for VX, an
air deflector,
metal filters,
filter mats, a
door position switch,
transport eyes, a
temperature sensor, and the
cover for connection box (article number 3355.210).
Installation and Mounting
Mounting is done on the wall, requiring a mounting cutout of 433 mm width and 1,579 mm height. The unit is pre-wired for connection and includes the necessary mounting hardware. Installation requires appropriate surge protection: for operating voltages below 460 V (3~), surge protection with Uc 275 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required. For operating voltages above 460 V (3~), surge protection with Uc 385 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required. The operating voltage tolerance is 380 V -10 % (342 V) and 480 V +6 % (509 V).
Operational Advantages
Thanks to speed-controlled components and Heat Pipe technology, an average energy saving of 75 % is achieved. The integrated condensate evaporation reduces maintenance effort, as no external drain is required. The
protection rating IP 55 for the internal circuit and
protection rating NEMA UL Type 12 and UL Type 3R ensure high protection against dust and splashing water, increasing reliability in industrial use.
Multi-voltage capability enables worldwide use of the unit. The
intuitive operation via the e+ controller and the option for remote monitoring increase machine availability and process safety.
Permissible Operating Pressure
The permissible operating pressure is 24 bar. The unit is designed for use in enclosures in semi-outdoor environments, with detailed application information available in the instruction manual. The PCF values (Cradle-to-Gate) are 352.59 kg CO₂ eq (Category B), calculated approximately based on product weight and self-declared.