| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 5.5 kW, cooling capacity L35 L35/60 Hz: 5.5 kW, cooling capacity L35 L50/50 Hz: 3.8 kW, cooling capacity L35 L50/60 Hz: 3.8 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 2,35 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance coefficient L35 L35 (EER) 50 Hz: 2.39, Cooling performance coefficient L35 L35 (EER) 60 Hz: 2.39 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.76 kg, Quantity compression system: 1.04 kg, Quantity heat pipe system: 0.72 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 2.3 kW, Rated power L35 L35/60 Hz: 2.3 kW, Rated power L35 L50/50 Hz: 2.2 kW, Rated power L35 L50/60 Hz: 2.2 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 422.34 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3489.640 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures and industrial electrical installations. It features a total cooling capacity of 5.5 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz, and is designed for use in semi-outdoor environments. The unit is made of stainless steel 1.4301 (AISI 304) and has a colour finish according to RAL 9007. Dimensions are 450 mm (width) × 1,600 mm (height) × 393 mm (depth), requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). The cooling unit is pre-wired and includes a plug-in terminal strip and mounting hardware. The condenser is coated with a hydrophobic RiNano coating, and the integrated electric condensate evaporation system ensures efficient drainage without external discharge.
Applications
This cooling unit is suitable for industrial applications in enclosures and electrical distributions, particularly in environments with increased requirements for operational safety and environmental compatibility. It is intended for use in semi-outdoor environments, with detailed specifications provided in the instruction manual. Operating temperature ranges are between -20 °C and 60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system from -20 °C to 45 °C. Storage temperature ranges extend from -40 °C to 70 °C. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Functions and Equipment in Detail
The unit employs speed-controlled components and Heat Pipe technology to achieve an average energy saving of 75 %. Airflow capacity is 2,300 m³/h for both the external and internal circuits. Energy efficiency is characterised by a coefficient of performance (EER) of 2.39 at 50 Hz and 60 Hz, and a Seasonal Energy Efficiency Ratio (SEER) of 5.6. Rated power is 2.35 kW, with nominal power varying between 2.2 kW and 2.3 kW depending on operating conditions. The cooling unit uses refrigerant R-1234yf with a total quantity of 1.76 kg, comprising 1.04 kg in the compression system and 0.72 kg in the Heat Pipe system. The Global Warming Potential (GWP) is 0.5, equivalent to 0 t of CO₂. The permissible operating pressure is 24 bar.
Technology Explained Simply
The Heat Pipe technology enables component-friendly cooling, extending the service life of components within the enclosure and the cooling unit itself. Speed-controlled components adjust their output to match current load, resulting in more efficient energy use. The integrated electric condensate evaporation system ensures that condensate formed within the unit evaporates internally, eliminating the need for external drainage. The hydrophobic RiNano coating on the condenser prevents moisture accumulation and improves heat transfer. Pre-wiring with a plug-in terminal strip simplifies installation and maintenance.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ generation cooling units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to enhance machine availability and process safety. Additional compatible components include filter mats, condensate hoses, air deflectors, and temperature sensors for Blue e+ cooling units.
Mounting and Installation
The unit is designed for wall mounting and requires a mounting cutout of 433 mm (width) × 1,579 mm (height). It is not suitable for full flush installation. Mounting is done using the included hardware. Pre-wiring with a plug-in terminal strip simplifies electrical connection. Appropriate surge protection must be provided: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The cooling unit offers high energy efficiency through the combination of speed-controlled components and Heat Pipe technology. The integrated condensate evaporation reduces maintenance effort, as no external drainage is required. The robust stainless steel construction and protection rating IP 55 for the internal circuit, as well as UL Type 12 and UL Type 3R, ensure high reliability in industrial environments. Remote monitoring via the IoT Interface enables proactive maintenance and enhances operational safety. The multi-voltage capability of 380 V to 480 V, 3~, 50 Hz/60 Hz, allows worldwide use without adapting the power supply.