| General |
| Model | Wall mounting, Outdoor |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Aluminium AlMg3 |
| Surface protection | Powder-coated, UV-resistant pure polyester |
| Colour | RAL 7035 |
| Scope of delivery | Refrigerant with hydrophobic RiNano coating, integrated electric condensate evaporation, pre-wired (pluggable terminal block), mounting frame for universal attachment to outdoor enclosures for surface mounting, panel mounting and flush mounting, incl. mounting material |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 4.55 kW, cooling capacity L35 L35/60 Hz: 4.55 kW, cooling capacity L35 L50/50 Hz: 2.85 kW, cooling capacity L35 L50/60 Hz: 2.85 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the partner and Rittal for the free use of the software according to these license terms. For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 2,35 kW |
| Rated power Pel | Rated power L35 L35/50 Hz: 2.35 kW, Rated power L35 L35/60 Hz: 2.35 kW, Rated power L35 L50/50 Hz: 1.7 kW, Rated power L35 L50/60 Hz: 1.7 kW |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Width | 465 mm |
| Height | 1.640 mm |
| Depth | 360 mm |
| Device dimensions including gasket frame and design hood | Width: 517 mm, Height: 1,692 mm, Depth: 360 mm |
| Mounting type | Universal installation (surface mounting, partial installation, full installation) |
| Degree of protection IP according to IEC 60 529 | With mounting frame: internal circuit IP 56, without mounting frame: internal circuit IP 54 |
| NEMA degree of protection | with mounting frame: UL Type 12/3R/4, without mounting frame: UL Type 12/3R |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.76 kg, Quantity compression system: 1.04 kg, Quantity heat pipe system: 0.72 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 1.94, Cooling performance factor L35 L35 (EER) 60 Hz: 1.94 |
| Suitable for | Housing type: Toptec, width: ≥ 800 mm, height: ≥ 1,800 mm |
| Suitable for part no. | 9782.828, 9783.888 |
| Adjustment range | 20 °C...50 °C |
| Operating temperature range | -30 °C...60 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -30 °C...45 °C |
| Storage temperature range | -40 °C...70 °C |
| Permissible operating pressure (p max.) | 2.4 MPa |
| Sound pressure level | 71 dB(A) |
| PCF/VE (Cradle-to-Gate) | 522.24 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
Rittal SK 3489.340 is a wall-mounted cooling unit from the Blue e+ series, designed for outdoor use. It is intended for climate control of enclosures and provides a total cooling capacity of 4.55 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz. The unit is designed for universal installation and can be mounted as a wall-mounted, partial-insertion, or full-insertion variant on outdoor enclosures, particularly on Toptec enclosures with a minimum width of 800 mm and a minimum height of 1,800 mm. The dimensions of the unit are 465 mm (width) × 1,640 mm (height) × 360 mm (depth), while the overall dimensions including the sealing frame and design hood are 517 mm (width) × 1,692 mm (height) × 360 mm (depth).
Applications
This cooling unit is designed for demanding environments requiring high protection ratings and a wide operating temperature range. It is suitable for outdoor use, supporting an operating temperature range of -30 °C to 60 °C. The protection rating IP 56 (with mounting frame) or IP 54 (without mounting frame) according to IEC 60 529, as well as the NEMA protection rating UL Type 12/3R/4 (with mounting frame) or UL Type 12/3R (without mounting frame), ensures high protection against dust and water. The operating temperature of the refrigerant circuit is between 3 °C and 60 °C, while the Heat Pipe operation reaches up to 45 °C. The storage temperature can range from -40 °C to 70 °C.
Functions and Equipment in Detail
The unit features an integrated e+ controller, factory-set to a temperature control of +35 °C. The adjustable range for internal temperature is 20 °C to 50 °C. The cooling capacity is achieved through speed-controlled components and Heat Pipe technology, resulting in an average energy saving of 75 %. The integrated electrical condensate evaporation ensures efficient dehumidification. The condenser is coated with a hydrophobic RiNano coating, improving heat transfer. The unit is pre-wired for connection and includes a plug-in terminal strip. The delivery includes a mounting frame for universal fastening and mounting hardware.
Technology Explained Simply
The cooling unit uses refrigerant R-1234yf, which has a very low Global Warming Potential (GWP) of 0.5. The total refrigerant charge is 1.76 kg, with 1.04 kg in the compression system and 0.72 kg in the Heat Pipe system. Energy efficiency is described by the coefficient of performance (EER) of 1.94 at 50 Hz and 60 Hz (L35 L35). The air performance is 2,300 m³/h in both the outdoor and indoor circuits. The permissible operating pressure is 2.4 MPa. The sound pressure level is 71 dB(A). The rated power is 2.35 kW, with the nominal power also being 2.35 kW at L35 L35/50 Hz and L35 L35/60 Hz.
Compatibility and Accessories
The cooling unit is specifically designed for Toptec enclosures and fits article numbers 9782.828 and 9783.888. Available accessories include, among others, a thermostat, hygrostat, SK temperature sensor for Blue e+ cooling units, SK condensate hose 12 x 2 mm (length 10 m), IoT Interface (article number 3124.300), door position switch, TS support roller for TS, SE, PC, and VX support roller 8618420. The IoT Interface enables remote monitoring and networking of cooling units and chillers from the Blue e+ generation, increasing machine availability and process reliability.
Installation and Mounting
Mounting is done using the included mounting frame, which allows universal fastening to outdoor enclosures. Installation can be performed as wall-mounted, partial-insertion, or full-insertion. The pre-wired connection with a plug-in terminal strip simplifies electrical connection. For protection of Blue e+ cooling units, appropriate surge protection must be provided: for operating voltage < 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltage > 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The speed-controlled components and Heat Pipe technology ensure gentle cooling, extending the service life of components in the enclosure and the cooling unit. The intuitive operation via the e+ controller and the possibility of remote monitoring via the IoT Interface increase operational safety and process availability. The high protection rating IP 56 and UL Type 12/3R/4 enable use in demanding environments. The use of refrigerant R-1234yf with a GWP of 0.5 reduces environmental impact. The integrated condensate evaporation ensures efficient dehumidification without additional drainage lines.