| General |
| Model | Wall mounting, chemical industry |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Applications | Applications where sulfuric acid may be present as an aerosol in the air (e.g. paper industry, food industry, chemical industry, electroplating, offshore area) |
| Material | steel sheet |
| Surface protection | Sheet metal parts and electronics coated with clear lacquer, refrigeration circuit coated with 2K PUR lacquer |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 4 kW, cooling capacity L35 L35/60 Hz: 4 kW, cooling capacity L35 L50/50 Hz: 2.8 kW, cooling capacity L35 L50/60 Hz: 2.8 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 1,45 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity factor L35 L35 (EER) 50 Hz: 3.08, Cooling capacity factor L35 L35 (EER) 60 Hz: 3.08 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 6,4 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.76 kg, Quantity compression system: 1.04 kg, Quantity heat pipe system: 0.72 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 1.3 kW, rated power L35 L35/60 Hz: 1.3 kW, rated power L35 L50/50 Hz: 1.25 kW, rated power L35 L50/60 Hz: 1.25 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 352.88 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3488.945 is a wall-mounted cooling unit of the Blue e+ Chemistry series, specifically designed for industrial applications where sulfuric acid may occur as an aerosol in the air. It is intended for climate control of enclosures in areas such as the paper industry, food industry, chemical industry, galvanizing, or offshore environments. The unit is designed for use in semi-outdoor environments and features a robust construction made of sheet steel with a special surface coating that protects components against aggressive environmental conditions. The sheet metal parts and electronics are coated with clear lacquer, while the refrigeration circuit is coated with a 2-component PUR lacquer to ensure high corrosion resistance. The unit's color corresponds to RAL 7035.
Applications
This cooling unit is designed for applications where the air contains sulfuric acid aerosols. It is therefore particularly suitable for process environments in the chemical industry, galvanizing processes, paper and food processing, as well as offshore applications. The special chemistry version ensures a longer service life of components in the enclosure and the cooling unit itself, as cooling is performed in a component-friendly manner. The operating temperature range is between -20 °C and 60 °C, with the refrigerant circuit actively operating between 3 °C and 60 °C. The heat pipe operates in the range of -20 °C to 45 °C. The temperature control adjustment range is 20 °C to 50 °C.
Functions and Equipment in Detail
The unit features a condenser with hydrophobic RiNano coating, which reduces condensation formation and simplifies maintenance. The integrated electric condensate evaporation ensures that any condensate formed evaporates directly within the unit and does not need to be drained. The unit is pre-wired for connection, includes a plug-in terminal strip, and comes with the required mounting hardware. Temperature control is managed via an e+ controller, factory-set to +35 °C. The cooling capacity is 4.0 kW at L35 operation and 50/60 Hz, with a rated power of 1.3 kW. The air performance is 2,300 m³/h for both the external and internal circuits.
Technology Explained Simply
The cooling unit uses refrigerant R-1234yf, which has a very low Global Warming Potential (GWP) of 0.5, making it environmentally friendly. The total refrigerant charge is 1.76 kg, with 1.04 kg in the compression system and 0.72 kg in the heat pipe system. Energy efficiency is enhanced by variable-speed components and heat pipe technology, resulting in an average energy saving of 75 %. The EER (Energy Efficiency Ratio) is 3.08 at 50 Hz and 60 Hz, while the SEER (Seasonal Energy Efficiency Ratio) is 6.4. The rated operating voltage is 380 V to 480 V, 3~, 50 Hz/60 Hz, with a tolerance of -10 % (342 V) at 380 V and +6 % (509 V) at 480 V. The unit is not suitable for full enclosure installation.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ generation cooling units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Additional compatible accessories include filter mats, condensate hoses, air deflectors, and metal filters for the mentioned model series.
Mounting and Installation
The unit is designed for wall mounting. Dimensions are 450 mm (width) × 1,600 mm (height) × 393 mm (depth). The required mounting cutout is 433 mm (width) × 1,579 mm (height). The protection rating of the internal circuit corresponds to IP 55 according to EN 60 529, meaning it is dust-tight and protected against water spray. For protection of the cooling unit, appropriate surge protection must be provided: for operating voltages below 460 V (3~), Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The variable-speed components and heat pipe technology ensure high energy efficiency and reduce energy consumption. The special surface coating increases component lifespan in aggressive environments. The integrated condensate evaporation reduces maintenance effort, as no condensate needs to be drained. The pre-wired connection and included mounting hardware speed up installation. The remote monitoring capability via the IoT Interface enables proactive maintenance and increases operational safety.