| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 4 kW, cooling capacity L35 L35/60 Hz: 4 kW, cooling capacity L35 L50/50 Hz: 2.8 kW, cooling capacity L35 L50/60 Hz: 2.8 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 1,45 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity factor L35 L35 (EER) 50 Hz: 3.08, Cooling capacity factor L35 L35 (EER) 60 Hz: 3.08 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 6,4 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.76 kg, Quantity compression system: 1.04 kg, Quantity heat pipe system: 0.72 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 1.3 kW, rated power L35 L35/60 Hz: 1.3 kW, rated power L35 L50/50 Hz: 1.25 kW, rated power L35 L50/60 Hz: 1.25 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 352.59 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
Rittal SK 3488.940 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of 4.0 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz. The unit is made of sheet steel and painted in RAL 7035. Dimensions are 450 mm (width) × 1600 mm (height) × 393 mm (depth), requiring a mounting cutout of 433 mm (width) × 1579 mm (height). Cooling capacity is measured according to DIN EN 14511 and amounts to 4.0 kW at L35 L35/50 Hz and 60 Hz, and 2.8 kW at L35 L50/50 Hz and 60 Hz. Rated power is 1.45 kW, nominal power is 1.3 kW (L35 L35) and 1.25 kW (L35 L50). Air flow rate is 2300 m³/h in both outdoor and indoor circuits. Energy efficiency is characterised by an EER value of 3.08 (50/60 Hz, L35 L35) and a SEER value of 6.4. The unit uses refrigerant R-1234yf with a Global Warming Potential (GWP) of 0.5 and a CO₂ equivalent of 0 t. The total refrigerant charge is 1.76 kg, with 1.04 kg in the compression system and 0.72 kg in the Heat Pipe system. Operating temperature ranges are between -20 °C and 60 °C (general), 3 °C and 60 °C (refrigerant circuit active), and -20 °C and 45 °C (Heat Pipe). The temperature control range is 20 °C to 50 °C, with the e+ controller factory-set to +35 °C. The indoor circuit protection rating corresponds to IP 55 according to EN 60 529, and NEMA protection ratings UL Type 12 and UL Type 3R. The unit is intended for use in semi-outdoor environments, with appropriate surge protection required: for operating voltage < 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV, and for > 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. The permissible operating pressure limit is 24 bar. The cooling unit is equipped with a condenser featuring a hydrophobic RiNano coating and includes an integrated electric condensate evaporation system. It is pre-wired with a plug-in terminal block and includes mounting hardware. The operating voltage tolerates a deviation of -10 % (342 V) at 380 V and +6 % (509 V) at 480 V. Full installation is not possible. The PCF value (Cradle-to-Gate) is 352.59 kg CO₂ eq (Category B), declared approximately based on the product's own weight. Energy savings are achieved through variable-speed components and Heat Pipe technology, enabling an average saving of 75 %. Component-friendly cooling extends the service life of components in the enclosure and in the cooling unit. Operation is via a touch display and intelligent interfaces. For remote monitoring and networking of Blue e+ units, the IoT Interface with article number 3124.300 can be used to monitor device data, statuses, and system messages. The unit is designed for industrial environments where reliable and energy-efficient climate control is required. Delivery includes the cooling unit with integrated condensate evaporation, mounting hardware, and connected plug-in terminal block. Compatible accessories include, among others, lifting eyes, air deflectors, metal filters, condensate hoses, support rollers, temperature sensors, sheet steel doors, filter mats, and door position switches. Storage and operating temperature ranges are between -40 °C and 70 °C (storage) and -20 °C and 60 °C (operation).