| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2.6 kW, cooling capacity L35 L35/60 Hz: 2.6 kW, cooling capacity L35 L50/50 Hz: 1.7 kW, cooling capacity L35 L50/60 Hz: 1.7 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 1,05 kW |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.63, Cooling performance factor L35 L35 (EER) 60 Hz: 2.63 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 6,2 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 294 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.1 kg, Quantity compression system: 0.65 kg, Quantity heat pipe system: 0.45 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.99 kW, Rated power L35 L35/60 Hz: 0.99 kW, Rated power L35 L50/50 Hz: 0.94 kW, Rated power L35 L50/60 Hz: 0.94 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 274.42 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3487.930 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures and electronic devices. It features a total cooling capacity of 2.6 kW at an operating temperature of +35 °C (L35) and an operating voltage of 110 V to 240 V (1~) or 380 V to 480 V (3~), with a frequency of 50 Hz or 60 Hz. The unit is made of sheet steel and finished in RAL 7035. Dimensions are 450 mm (width) × 1600 mm (height) × 294 mm (depth), requiring a mounting cutout of 433 mm (width) × 1579 mm (height). The cooling capacity is 1.7 kW at an ambient temperature of +50 °C (L50). Energy efficiency is characterised by an Energy Efficiency Ratio (EER) of 2.63 and a Seasonal Energy Efficiency Ratio (SEER) of 6.2. Air flow rate is 1250 m³/h in both the external and internal circuits. The unit is intended for use in semi-outdoor environments and features an internal circuit with protection rating IP 55 according to EN 60 529, as well as NEMA protection ratings UL Type 12 and UL Type 3R. Temperature control is managed via an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C. The cooling unit uses refrigerant R-1234yf with a total quantity of 1.1 kg, comprising 0.65 kg in the compression system and 0.45 kg in the Heat Pipe system. The Global Warming Potential (GWP) is 0.5, equivalent to 0 t CO₂. The refrigerant circuit operating temperature range is 3 °C to 60 °C, and the Heat Pipe system operates between -20 °C and 45 °C. Rated power is 1.05 kW, while nominal power varies between 0.94 kW and 0.99 kW depending on operating conditions. The maximum allowable operating pressure is 24 bar. The unit is equipped with a condenser featuring a hydrophobic RiNano coating and includes an integrated electric condensate evaporation system. It is pre-wired with a plug-in terminal block and includes mounting hardware. For remote monitoring and networking of Blue e+ devices, the IoT Interface with article number 3124.300 is available. The operating voltage requires appropriate surge protection: for voltages below 460 V (3~), surge protection with Uc 275 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required; for voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, and Up 1.5 kV applies. Voltage tolerances are 110 V -10 % (99 V) and 240 V +10 % (264 V), as well as 380 V -10 % (342 V) and 480 V +6 % (509 V). Storage is possible in a temperature range from -40 °C to 70 °C. The product is designed for industrial environments where reliable and energy-efficient cooling of electronic components is required. The variable-speed components and Heat Pipe technology ensure gentle cooling, extending the service life of devices installed in the enclosure. The integrated electric condensate evaporation prevents condensation water accumulation inside the enclosure. The unit is suitable for use in various voltage ranges worldwide, facilitating application in international projects. The PCF values (Cradle-to-Gate) are 274.42 kg CO₂ eq (Category B), calculated approximately based on product weight and self-declared. Compatible accessories include, among others, door position switches, condensate hoses, filter mats, transport eyes, air ducts, sheet steel doors, air deflectors, support rollers, temperature sensors, and metal filters. These accessories are optional and serve to adapt the installation to specific requirements. Installation is on a wall, with the specified dimensions and mounting cutout to be observed. The pre-wired connection with a plug-in terminal block simplifies installation. The operating temperature ranges and protection ratings ensure safe and reliable performance in industrial applications. Remote monitoring via the IoT Interface enables monitoring of device data, statuses, and system messages, enhancing machine availability and process safety. The use of R-1234yf refrigerant with a very low GWP contributes to environmental compatibility. The integrated condensate evaporation ensures no condensation water accumulates in the enclosure, improving functionality and safety of installed devices. The variable-speed components and Heat Pipe technology provide efficient cooling, reducing energy consumption costs. Multi-voltage capability allows use in various countries and regions, increasing the unit’s flexibility. The IP 55 protection rating for the internal circuit protects against dust and splashing water, which is important for industrial environments. The NEMA protection ratings UL Type 12 and UL Type 3R offer additional protection against dust, splashing water, and light splashing water, expanding application possibilities. Temperature control via the e+ controller allows precise adjustment of cooling temperature between 20 °C and 50 °C, enabling optimal regulation of the enclosure’s operating temperature. The operating temperature ranges of the refrigerant circuit and Heat Pipe system ensure reliable performance under various environmental conditions. Nominal and rated power vary depending on operating conditions, with values between 0.94 kW and 0.99 kW. The maximum allowable operating pressure of 24 bar ensures system safety. Voltage tolerances are clearly defined and ensure stable operation of the unit. Storage within the temperature range of -40 °C to 70 °C allows flexible storage and transportation. The PCF values provide an overview of the product’s environmental impact, with the value calculated approximately. The compatibility of accessories allows individual adaptation to specific installation requirements. Installation is on a wall, with the specified dimensions and mounting cutout to be observed. The pre-wired connection with a plug-in terminal block simplifies installation. The operating temperature ranges and protection ratings ensure safe and reliable performance in industrial applications. Remote monitoring via the IoT Interface enables monitoring of device data, statuses, and system messages, enhancing machine availability and process safety. The use of R-1234yf refrigerant with a very low GWP contributes to environmental compatibility. The integrated condensate evaporation ensures no condensation water accumulates in the enclosure, improving functionality and safety of installed devices. The variable-speed components and Heat Pipe technology provide efficient cooling, reducing energy consumption costs. Multi-voltage capability allows use in various countries and regions, increasing the unit’s flexibility. The IP 55 protection rating for the internal circuit protects against dust and splashing water, which is important for industrial environments. The NEMA protection ratings UL Type 12 and UL Type 3R offer additional protection against dust, splashing water, and light splashing water, expanding application possibilities. Temperature control via the e+ controller allows precise adjustment of cooling temperature between 20 °C and 50 °C, enabling optimal regulation of the enclosure’s operating temperature. The operating temperature ranges of the refrigerant circuit and Heat Pipe system ensure reliable performance under various environmental conditions. Nominal and rated power vary depending on operating conditions, with values between 0.94 kW and 0.99 kW. The maximum allowable operating pressure of 24 bar ensures system safety. Voltage tolerances are clearly defined and ensure stable operation of the unit. Storage within the temperature range of -40 °C to 70 °C allows flexible storage and transportation. The PCF values provide an overview of the product’s environmental impact, with the value calculated approximately. The compatibility of accessories allows individual adaptation to specific installation requirements.