| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2.6 kW, cooling capacity L35 L35/60 Hz: 2.6 kW, cooling capacity L35 L50/50 Hz: 1.7 kW, cooling capacity L35 L50/60 Hz: 1.7 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 1,05 kW |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.63, Cooling performance factor L35 L35 (EER) 60 Hz: 2.63 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 6,2 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 294 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.1 kg, Quantity compression system: 0.65 kg, Quantity heat pipe system: 0.45 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.99 kW, Rated power L35 L35/60 Hz: 0.99 kW, Rated power L35 L50/50 Hz: 0.94 kW, Rated power L35 L50/60 Hz: 0.94 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 327.59 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3487.630 is a wall-mounted cooling unit of the Blue e+ series, designed for climate control of enclosures in semi-outdoor environments. The unit features a total cooling capacity of 2.6 kW at an operating temperature of +35 °C and an operating voltage of 110–240 V, 1~, 50/60 Hz or 380–480 V, 3~, 50/60 Hz. It is made of stainless steel 1.4301 (AISI 304) and finished in RAL 9007, ensuring high corrosion resistance and a robust surface for industrial operating conditions. Dimensions are 450 mm (width) × 1,600 mm (height) × 294 mm (depth), requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). The cooling unit is designed for operating temperatures from -20 °C to +60 °C and can be stored within a temperature range of -40 °C to +70 °C.
Applications
This cooling unit is designed for use in enclosures, particularly in environments classified as semi-outdoor. It is suitable for industrial installations where continuous cooling is required to ensure the operational safety of electronic components. The multi-voltage capability enables worldwide use, regardless of local power supply standards.
Functions and Equipment in Detail
The unit features a condenser with hydrophobic RiNano coating, which minimizes condensate formation and simplifies maintenance. The integrated electric condensate evaporation ensures that generated condensate evaporates directly within the unit, eliminating the need for external drainage. The unit is pre-wired with a plug-in terminal block and includes mounting hardware for wall installation. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Technology Explained Simply
The cooling performance is achieved using refrigerant R-1234yf with a Global Warming Potential (GWP) of 0.5, representing an environmentally compatible solution. The total cooling capacity is 2.6 kW at L35 operation and a frequency of 50/60 Hz. Air performance is 1,250 m³/h in both the external and internal circuits. Energy efficiency is enhanced by variable-speed components and Heat Pipe technology, resulting in an average energy saving of 75 %. The coefficient of performance (EER) is 2.63 at 50 Hz and 60 Hz, while the seasonal energy efficiency ratio (SEER) is 6.2. The permissible operating pressure is 24 bar.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Available accessories include the cover 3355.210 for the connection box, a condensate hose (12 x 2 mm, 10 m length), an air duct for the Blue e+ wall-mounted cooling unit, as well as filter mats and air deflectors.
Installation and Mounting
The cooling unit is mounted on the wall and requires a mounting cutout of 433 mm (width) × 1,579 mm (height). Installation is carried out using the included mounting hardware. The terminal block is plug-in, enabling easy and secure wiring. For device protection, appropriate surge protection must be provided: for operating voltages below 460 V (3~), surge protection with Uc 275 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required; for voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, and Up 1.5 kV applies.
Operational Advantages
The component-friendly cooling via Heat Pipe technology extends the service life of components within the enclosure and the cooling unit itself. Intuitive operation via the e+ controller and the option for remote monitoring enhance operational safety. The multi-voltage capability enables flexible global use. Refrigerant R-1234yf with a GWP of 0.5 is environmentally compatible and contributes to reducing CO₂ equivalents. The integrated condensate evaporation reduces maintenance effort, as no external drainage is required.
Protection Rating and Operating Conditions
The internal circuit of the cooling unit is designed according to EN 60 529 with protection rating IP 55, providing dust and splash water protection. The NEMA protection rating corresponds to UL Type 12 and UL Type 3R, allowing use in indoor environments and protected outdoor areas. The cooling unit is designed for operating temperatures from -20 °C to +60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system from -20 °C to 45 °C.
Energy Efficiency and Environment
Energy efficiency is optimized through variable-speed components and Heat Pipe technology. The coefficient of performance (EER) is 2.63, and the seasonal energy efficiency ratio (SEER) is 6.2. Refrigerant R-1234yf has a GWP of 0.5, representing an environmentally friendly alternative to conventional refrigerants. The PCF values (Cradle-to-Gate) are 327.59 kg CO₂ eq (Category B), indicating the environmental assessment of the product.