| General |
| Model | Wall mounting, Outdoor |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Aluminium AlMg3 |
| Surface protection | Powder-coated, UV-resistant pure polyester |
| Colour | RAL 7035 |
| Scope of delivery | Refrigerant with hydrophobic RiNano coating, integrated electric condensate evaporation, pre-wired (pluggable terminal block), mounting frame for universal attachment to outdoor enclosures for surface mounting, panel mounting and flush mounting, incl. mounting material |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2.5 kW, cooling capacity L35 L35/60 Hz: 2.5 kW, cooling capacity L35 L50/50 Hz: 1.6 kW, cooling capacity L35 L50/60 Hz: 1.6 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the partner and Rittal for the free use of the software according to these license terms. For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 1,05 kW |
| Rated power Pel | Rated power L35 L35/50 Hz: 1.08 kW, rated power L35 L35/60 Hz: 1.08 kW, rated power L35 L50/50 Hz: 1.03 kW, rated power L35 L50/60 Hz: 1.03 kW |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Width | 465 mm |
| Height | 1.640 mm |
| Depth | 260 mm |
| Device dimensions including gasket frame and design hood | Width: 517 mm, Height: 1,692 mm, Depth: 260 mm |
| Mounting type | Universal installation (surface mounting, partial installation, full installation) |
| Degree of protection IP according to IEC 60 529 | With mounting frame: internal circuit IP 56, without mounting frame: internal circuit IP 54 |
| NEMA degree of protection | with mounting frame: UL Type 12/3R/4, without mounting frame: UL Type 12/3R |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.1 kg, Quantity compression system: 0.65 kg, Quantity heat pipe system: 0.45 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.31, Cooling performance factor L35 L35 (EER) 60 Hz: 2.31 |
| Suitable for | Housing type: Toptec, width: ≥ 800 mm, height: ≥ 1,800 mm |
| Suitable for part no. | 9782.828, 9783.888 |
| Adjustment range | 20 °C...50 °C |
| Operating temperature range | -30 °C...60 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -30 °C...45 °C |
| Storage temperature range | -40 °C...70 °C |
| Permissible operating pressure (p max.) | 2.4 MPa |
| Sound pressure level | 70 dB(A) |
| PCF/VE (Cradle-to-Gate) | 412.64 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3487.330 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for outdoor use. It is intended for climate control of enclosures and provides a total cooling capacity of 2.5 kW at an operating voltage of 110 V to 240 V (1~, 50/60 Hz) or 380 V to 480 V (3~, 50/60 Hz). The unit is designed for mounting on outdoor enclosures and can be installed in three variants: as an add-on, partial installation, or full installation. The minimum installation width is 800 mm, and the minimum installation height is 1,800 mm, specifically designed for Toptec enclosure configurations. The unit dimensions are 465 mm (width) × 1,640 mm (height) × 260 mm (depth), while the overall dimensions including the sealing frame and design hood are 517 mm (width) × 1,692 mm (height) × 260 mm (depth).
Applications
This cooling unit is designed for demanding environments requiring high protection ratings and a wide operating temperature range. It is suitable for use at ambient temperatures from -30 °C to 60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system operating from -30 °C to 45 °C. The protection rating IP 56 (with mounting frame) or IP 54 (without mounting frame) according to IEC 60 529, as well as the NEMA protection rating UL Type 12/3R/4 (with mounting frame) or UL Type 12/3R (without mounting frame), ensures high protection against dust, splashing water, and other environmental influences. Storage is possible in the range of -40 °C to 70 °C.
Functions and Equipment in Detail
The unit features a condenser with hydrophobic RiNano coating, which reduces condensation formation and simplifies maintenance. The integrated electric condensate evaporation ensures that the generated condensate evaporates directly within the unit, eliminating the need for an external drain. The connection terminal block is plug-in, and the unit is pre-wired for connection, accelerating installation. The e+ controller regulates the internal temperature factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C. The air flow rate is 1,250 m³/h in both the external and internal circuits.
Technology Explained Simply
The cooling unit uses refrigerant R-1234yf, which has a very low Global Warming Potential (GWP) of 0.5, making it environmentally friendly. The total refrigerant charge is 1.1 kg, with 0.65 kg in the compression system and 0.45 kg in the Heat Pipe system. The Heat Pipe technology supports cooling performance and contributes to energy efficiency. The coefficient of performance (EER) is 2.31 at 50 Hz and 60 Hz in L35-L35 operation, indicating high energy efficiency. The rated power is 1.05 kW, with nominal power varying between 1.03 kW and 1.08 kW depending on the operating mode. The sound pressure level is 70 dB(A), which is acceptable for industrial applications.
Compatibility and Accessories
The cooling unit is compatible with Toptec enclosures and fits article numbers 9782.828 and 9783.888. Available accessories include, among others, the cover for the connection box (article numbers 3355.200 and 3355.210), the IoT interface (article number 3124.300) for remote monitoring, a door position switch, a temperature sensor for Blue e+ cooling units, as well as a hygrostat and thermostat for internal temperature control.
Installation and Mounting
The unit is supplied with a mounting frame, enabling universal attachment to outdoor enclosures. Installation can be performed as an add-on, partial installation, or full installation. The delivery includes the cooling unit with condenser, integrated condensate evaporation, connected terminal block, mounting frame, and fastening materials. Installation requires compliance with prescribed overvoltage protection measures: for operating voltages below 460 V (3~), overvoltage protection with Uc 275 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required; for voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, and Up 1.5 kV applies.
Operational Advantages
Thanks to speed-controlled components and Heat Pipe technology, an average energy saving of 75 % is achieved. The component-friendly cooling extends the service life of components within the enclosure and the cooling unit itself. Intuitive operation via the e+ controller and the possibility of remote monitoring via the IoT interface increase machine availability and process safety. The use of the environmentally friendly refrigerant R-1234yf reduces CO₂ equivalents to 0 t, improving the sustainability of the system. The PCF value (Cradle-to-Gate) is 412.64 kg CO₂ eq (Category B), reflecting the environmental balance of the product.