| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2 kW, Cooling capacity L35 L35/60 Hz: 2 kW, Cooling capacity L35 L50/50 Hz: 1.29 kW, Cooling capacity L35 L50/60 Hz: 1.29 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,73 kW |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 3.23, Cooling performance factor L35 L35 (EER) 60 Hz: 3.23 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 7,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 294 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.1 kg, Quantity compression system: 0.65 kg, Quantity heat pipe system: 0.45 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.62 kW, rated power L35 L35/60 Hz: 0.62 kW, rated power L35 L50/50 Hz: 0.6 kW, rated power L35 L50/60 Hz: 0.6 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 274.42 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3486.930 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures. It features a total cooling capacity of 2 kW at an operating temperature of +35 °C (L35) and a frequency of 50 Hz or 60 Hz. The unit is intended for use in semi-outdoor environments and is suitable for industrial applications where reliable temperature control within the enclosure is required. The cooling performance is achieved through a variable-speed compressor system and Heat Pipe technology, resulting in an average energy saving of 75 % compared to conventional systems. The operating voltage includes both single-phase (110 V – 240 V, 1~, 50/60 Hz) and three-phase networks (380 V – 480 V, 3~, 50/60 Hz), enabling worldwide usability. The voltage tolerance is 99 V for 110 V and 264 V for 240 V, and for three-phase, 342 V to 509 V.
Applications
This cooling unit is designed for use in industrial environments, particularly in enclosures installed in semi-outdoor areas. It is suitable for systems requiring continuous cooling performance to maintain the operating temperature of electronic components within the enclosure within acceptable limits. The operating temperature range of the unit is from -20 °C to +60 °C, with the refrigerant circuit active between +3 °C and +60 °C. The Heat Pipe operates within the range of -20 °C to +45 °C. Storage of the unit is possible at temperatures from -40 °C to +70 °C.
Functions and Equipment in Detail
The unit is equipped with an e+ controller, factory-set to a temperature of +35 °C. The adjustable range is between +20 °C and +50 °C. The integrated electric condensate evaporation ensures that the condensate generated within the unit evaporates and does not need to be drained. The condenser is coated with a hydrophobic RiNano coating, which improves heat transfer and reduces condensate formation. The unit is pre-wired for connection and includes a plug-in terminal strip. Mounting hardware is included in the delivery scope.
Technology Explained Simply
The cooling performance is generated by a refrigerant (R-1234yf) that has very low environmental impact. The Global Warming Potential (GWP) is 0.5, meaning the refrigerant has practically no greenhouse gas effect. The total refrigerant quantity is 1.1 kg, with 0.65 kg in the compression system and 0.45 kg in the Heat Pipe system. The air performance is 1,250 m³/h in both the external and internal circuits. Energy efficiency is described by the Energy Efficiency Ratio (EER) of 3.23 (at 50 Hz and 60 Hz) and the Seasonal Energy Efficiency Ratio (SEER) of 7.6. The rated power is 0.73 kW, the nominal power is 0.62 kW (L35 L35) and 0.6 kW (L50). The maximum operating pressure is 24 bar.
Compatibility and Accessories
The unit is compatible with the IoT Interface (part number 3124.300), enabling remote monitoring and networking of cooling units. This allows monitoring of device data, statuses, and system messages, increasing machine availability and process safety. Available accessories include, among others, covers for the connection box (part numbers 3355.200 and 3355.210), a condensate hose (12 x 2 mm, length 10 m), filter mats, metal filters, an air deflector for SK 3184, 3186, 3187.xxx, an SK IT air duct for Blue e+ wall-mounted cooling units, and a temperature sensor for Blue e+ cooling units.
Mounting and Installation
The unit is mounted on the wall and requires a mounting cutout with a width of 433 mm and a height of 1,579 mm. The dimensions of the unit are 450 mm (width) × 1,600 mm (height) × 294 mm (depth). The protection rating of the internal circuit is IP 55 according to EN 60 529, meaning it is dust-tight and protected against water spray. The NEMA protection rating corresponds to UL Type 12 and UL Type 3R, representing a protection class for indoor and outdoor use. For device protection, an appropriate surge protection device must be provided: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The variable-speed technology and Heat Pipe technology ensure gentle component cooling, extending the service life of components within the enclosure and within the cooling unit. The integrated condensate evaporation reduces maintenance effort, as no condensate needs to be drained. The multi-voltage capability enables use in various countries and power networks. The remote monitoring capability via the IoT Interface provides additional transparency and process safety. The unit is made of sheet steel and is available in the color RAL 7035.