| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2 kW, Cooling capacity L35 L35/60 Hz: 2 kW, Cooling capacity L35 L50/50 Hz: 1.29 kW, Cooling capacity L35 L50/60 Hz: 1.29 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,73 kW |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 3.23, Cooling performance factor L35 L35 (EER) 60 Hz: 3.23 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 7,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 294 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 1.1 kg, Quantity compression system: 0.65 kg, Quantity heat pipe system: 0.45 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.62 kW, rated power L35 L35/60 Hz: 0.62 kW, rated power L35 L50/50 Hz: 0.6 kW, rated power L35 L50/60 Hz: 0.6 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 327.59 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3486.630 is a wall-mounted cooling unit of the Blue e+ series, specifically developed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of up to 2 kW at an operating temperature of +35 °C and is designed for operating voltages of 110 V to 240 V (1~, 50/60 Hz) as well as 380 V to 480 V (3~, 50/60 Hz). The unit is manufactured from stainless steel 1.4301 (AISI 304) and has a finish according to RAL 9007. Dimensions are 450 mm (width) × 1,600 mm (height) × 294 mm (depth), requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). Cooling capacity is measured according to DIN EN 14511, with values for L35 L35 at 50 Hz and 60 Hz each being 2 kW, while at L50 the cooling capacity drops to 1.29 kW. Air performance is 1,250 m³/h for both the external and internal circuits. Energy efficiency is characterised by an EER value of 3.23 (L35 L35) and a SEER value of 7.6, indicating high efficiency. Operating temperature ranges are between -20 °C and 60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system from -20 °C to 45 °C. Temperature control is performed via an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Applications
The cooling unit is intended for use in semi-outdoor environments, allowing installation in protected outdoor areas or rooms with increased environmental stress. It is suitable for enclosures in industrial plants where constant temperature control is required to avoid functional limitations of electronic components. The multi-voltage capability allows worldwide use, regardless of local power supply conditions. The integrated electrical condensate evaporation ensures that condensate evaporates within the unit itself, eliminating the need for an additional drainage system.
Functions and Equipment in Detail
The unit features a condenser with hydrophobic RiNano coating, which reduces water absorption and enhances serviceability. The variable-speed components and Heat Pipe technology ensure gentle component cooling, extending the lifespan of components installed in the enclosure. Connection is made via a plug-in terminal strip, simplifying installation. The delivery includes mounting materials to ensure secure installation.
Technology Explained Simply
The Heat Pipe technology uses a heat transfer mechanism in which liquid in a closed tube evaporates and condenses, efficiently transporting heat from the internal to the external circuit. The variable-speed components adjust their performance according to current cooling demand, resulting in an average energy saving of 75 %. The refrigerant R-1234yf has a very low Global Warming Potential (GWP) of 0.5, minimising environmental impact. Protection class IP 55 (internal circuit) and UL Type 12 as well as UL Type 3R (NEMA) ensure high protection against dust and splashing water, which is important for industrial environments.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Suitable accessories include air ducts, metal filters, steel sheet doors, support rollers, transport eyes, temperature sensors, air deflectors, condensate hoses, and filter mats. These components can be used additionally depending on application and environmental conditions.
Mounting and Installation
Mounting is done on a wall, requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). The unit is pre-wired for connection, simplifying electrical installation. The included mounting materials facilitate installation. For protection against overvoltage, an appropriate surge protection device must be provided depending on operating voltage: for voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV, and for voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The combination of variable-speed components and Heat Pipe technology leads to significant energy savings and extends the lifespan of components installed in the enclosure. The integrated condensate evaporation reduces maintenance effort, as no external drain is required. The multi-voltage capability enables worldwide use, and the robust stainless steel construction ensures high mechanical stability and corrosion resistance. Remote monitoring via the IoT Interface provides additional transparency and control over the operating status of the cooling unit.