| General |
| Model | Wall mounting, Outdoor |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Aluminium AlMg3 |
| Surface protection | Powder-coated, UV-resistant pure polyester |
| Colour | RAL 7035 |
| Scope of delivery | Refrigerant with hydrophobic RiNano coating, integrated electric condensate evaporation, pre-wired (pluggable terminal block), mounting frame for universal attachment to outdoor enclosures for surface mounting, panel mounting and flush mounting, incl. mounting material |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2 kW, Cooling capacity L35 L35/60 Hz: 2 kW, Cooling capacity L35 L50/50 Hz: 1.29 kW, Cooling capacity L35 L50/60 Hz: 1.29 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the partner and Rittal for the free use of the software according to these license terms. For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,85 kW |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.7 kW, Rated power L35 L35/60 Hz: 0.7 kW, Rated power L35 L50/50 Hz: 0.68 kW, Rated power L35 L50/60 Hz: 0.68 kW |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Width | 450 mm |
| Height | 1.640 mm |
| Depth | 260 mm |
| Device dimensions including gasket frame and design hood | Width: 517 mm, Height: 1,692 mm, Depth: 260 mm |
| Mounting type | Universal installation (surface mounting, partial installation, full installation) |
| Degree of protection IP according to IEC 60 529 | With mounting frame: internal circuit IP 56, without mounting frame: internal circuit IP 54 |
| NEMA degree of protection | with mounting frame: UL Type 12/3R/4, without mounting frame: UL Type 12/3R |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, quantity: 1.1 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance coefficient L35 L35 (EER) 50 Hz: 2.86, cooling performance coefficient L35 L35 (EER) 60 Hz: 2.86 |
| Suitable for | Housing type: Toptec, width: ≥ 800 mm, height: ≥ 1,800 mm |
| Suitable for part no. | 9782.828, 9783.888 |
| Adjustment range | 20 °C...50 °C |
| Operating temperature range | -30 °C...60 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -30 °C...45 °C |
| Storage temperature range | -40 °C...70 °C |
| Permissible operating pressure (p max.) | 2.4 MPa |
| Sound pressure level | 70 dB(A) |
| PCF/VE (Cradle-to-Gate) | 412.64 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
SK Kühlgerät Blue e+, Wandanbau Outdoor, 2,0 kW, R-1234yf, 110-240 V, 1~, 380-480 V, 3~, 50-60 Hz, Aluminium, BHT: 465 x 1640 x 260 mm