| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.6 kW, cooling capacity L35 L35/60 Hz: 1.6 kW, cooling capacity L35 L50/50 Hz: 1.1 kW, cooling capacity L35 L50/60 Hz: 1.1 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,7 kW |
| Air performance (free blowing) | External circuit: 895 m³/h, Internal circuit: 700 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.96, Cooling performance factor L35 L35 (EER) 60 Hz: 2.96 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,4 |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 310 mm |
| Required mounting cutout | Cutout width: 383 mm, cutout height: 929 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 0.77 kg, Quantity compression system: 0.48 kg, Quantity heat pipe system: 0.29 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.54 kW, rated power L35 L35/60 Hz: 0.54 kW, rated power L35 L50/50 Hz: 0.61 kW, rated power L35 L50/60 Hz: 0.61 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 207.6 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3485.830 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures and electronic devices. It features a total cooling capacity of 1.6 kW at an operating temperature of +35 °C (L35) and a frequency of 50 Hz or 60 Hz. The unit is designed for use in semi-outdoor environments and is suitable for industrial applications where continuous cooling of electronic components is required. The cooling capacity is 1.1 kW at an ambient temperature of +50 °C (L50), ensuring reliable operation in warm environments. The cooling unit is made of sheet steel and painted in RAL 7035, allowing it to blend visually into industrial environments. Dimensions are 400 mm (width) × 950 mm (height) × 310 mm (depth), with a mounting cutout of 383 mm (width) × 929 mm (height) required.
Applications
This cooling unit is designed for use in enclosures and electronic systems where controlled temperature management is required. It is particularly suitable for industrial applications such as automation technology, manufacturing industry, or energy supply. The multi-voltage capability allows use in various countries and regions, as the unit can be operated at 110 V to 240 V (1~, 50/60 Hz) or 380 V to 480 V (3~, 50/60 Hz). Tolerances are -10 % for 110 V (99 V) and +10 % for 240 V (264 V), as well as -10 % for 380 V (342 V) and +6 % for 480 V (509 V). Operating temperature ranges are between -20 °C and +60 °C, with the refrigerant circuit actively operating between +3 °C and +60 °C. The Heat Pipe operates in the range of -20 °C to +45 °C.
Functions and Equipment in Detail
The unit features a condenser with hydrophobic RiNano coating, ensuring efficient condensate formation and drainage. The integrated electric condensate evaporation ensures that condensate evaporates directly within the unit, eliminating the need for external drainage. The unit is pre-wired and includes a plug-in terminal block, simplifying installation and commissioning. Mounting materials are included in the delivery scope for wall mounting. Temperature control is managed by an e+ controller, factory-set to +35 °C and adjustable between +20 °C and +50 °C.
Technology Explained Simply
The cooling unit uses refrigerant R-1234yf, which has a low Global Warming Potential (GWP) of 0.5, making it environmentally friendly. The total refrigerant charge is 0.77 kg, with 0.48 kg in the compression system and 0.29 kg in the Heat Pipe system. Heat Pipe technology provides component-friendly cooling, extending the lifespan of electronic components in the enclosure. Variable-speed components enable an average energy saving of 75 % compared to conventional cooling units. Airflow is 895 m³/h in the external circuit and 700 m³/h in the internal circuit, ensuring efficient air circulation within the enclosure. Energy efficiency is characterized by an Energy Efficiency Ratio (EER) of 2.96 (at 50 Hz and 60 Hz) and a Seasonal Energy Efficiency Ratio (SEER) of 5.4.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ generation cooling units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Available accessories include temperature sensors for Blue e+ cooling units and condensate hoses (12 x 2 mm, length 10 m). For installation, metal filters, filter mats, and air deflectors (for SK 3185.xxx) can also be used.
Installation and Mounting
Mounting is done on a wall, requiring a mounting cutout of 383 mm (width) × 929 mm (height). The unit is pre-wired and includes a plug-in terminal block, simplifying installation. Mounting materials are included in the delivery scope. The internal circuit protection rating is IP 55 according to EN 60 529, which is dust-tight and splash-proof. The NEMA protection rating corresponds to UL Type 12 and UL Type 3R, suitable for industrial environments. Appropriate surge protection is required: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The cooling unit offers high energy efficiency due to variable-speed components and Heat Pipe technology. The integrated condensate evaporation reduces maintenance effort, as no external drainage is required. Multi-voltage capability enables worldwide use. Component-friendly cooling extends the lifespan of electronic components in the enclosure. Remote monitoring via the IoT Interface increases process safety and machine availability. Temperature control via the e+ controller allows precise adjustment of operating temperature between +20 °C and +50 °C. Operating temperature ranges of -20 °C to +60 °C and storage temperature ranges of -40 °C to +70 °C ensure flexible use in various environments. The permissible operating pressure is 24 bar. Rated power is 0.7 kW, nominal power is 0.54 kW (L35 L35) and 0.61 kW (L50). The PCF value (Cradle-to-Gate) is 207.6 kg CO2 eq (Category B).