| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.6 kW, cooling capacity L35 L35/60 Hz: 1.6 kW, cooling capacity L35 L50/50 Hz: 1.1 kW, cooling capacity L35 L50/60 Hz: 1.1 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,7 kW |
| Air performance (free blowing) | External circuit: 895 m³/h, Internal circuit: 700 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.96, Cooling performance factor L35 L35 (EER) 60 Hz: 2.96 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,4 |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 310 mm |
| Required mounting cutout | Cutout width: 383 mm, cutout height: 929 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 0.77 kg, Quantity compression system: 0.48 kg, Quantity heat pipe system: 0.29 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.54 kW, rated power L35 L35/60 Hz: 0.54 kW, rated power L35 L50/50 Hz: 0.61 kW, rated power L35 L50/60 Hz: 0.61 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 246.62 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
The Rittal SK 3485.530 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures and electronic devices in industrial applications. The unit features a total cooling capacity of 1.6 kW at an operating temperature of +35 °C and is designed for use in semi-outdoor environments. It is manufactured from stainless steel 1.4301 (AISI 304), ensuring high corrosion resistance and long service life. The unit is finished in RAL 9007, a neutral grey tone that integrates well in industrial environments. Dimensions are 400 mm (width) × 950 mm (height) × 310 mm (depth), requiring a mounting cutout of 383 mm (width) × 929 mm (height). The cooling unit is pre-wired and connected, including mounting hardware, and features a plug-in terminal strip for quick and secure installation.
Applications
This cooling unit is designed for use in industrial enclosures, control systems, and other electronic units requiring constant cooling to ensure operational reliability and component longevity. It is suitable for semi-outdoor environments, meaning it can be operated in protected outdoor areas, such as under a canopy or in a covered hall. Operating temperature ranges are between -20 °C and +60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system from -20 °C to 45 °C. Storage temperature ranges extend from -40 °C to +70 °C, enabling flexible storage conditions.
Functions and Equipment in Detail
The unit operates with refrigerant R-1234yf, which has a very low Global Warming Potential (GWP) of 0.5, making it environmentally friendly. The total refrigerant charge is 0.77 kg, with 0.48 kg in the compression system and 0.29 kg in the Heat Pipe system. The integrated electric condensate evaporation ensures that condensate evaporates within the unit and does not need to be drained, simplifying installation. The condenser is coated with a hydrophobic RiNano coating, which reduces water absorption and increases efficiency. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range between 20 °C and 50 °C.
Technology Explained Simply
The cooling performance is achieved through a combination of speed-controlled components and Heat Pipe technology, enabling an average energy saving of 75 %. The Heat Pipe technology transfers heat more efficiently, reducing stress on components within the enclosure and the cooling unit. Airflow rates are 895 m³/h in the external circuit and 700 m³/h in the internal circuit, ensuring effective air circulation. Energy efficiency is described by an Energy Efficiency Ratio (EER) of 2.96 (at 50 Hz and 60 Hz) and a Seasonal Energy Efficiency Ratio (SEER) of 5.4. The rated operating voltage includes 110 V to 240 V (1~, 50/60 Hz) and 380 V to 480 V (3~, 50/60 Hz), enabling worldwide use. Permissible voltage tolerances are -10 % (99 V) for 110 V and +10 % (264 V) for 240 V, and -10 % (342 V) for 380 V and +6 % (509 V) for 480 V. The rated power is 0.7 kW, with actual power consumption varying between 0.54 kW and 0.61 kW depending on operating conditions.
Compatibility and Accessories
The cooling unit is compatible with an IoT interface (part number 3124.300), enabling remote monitoring and networking of devices. This allows monitoring of device data, statuses, and system alerts to increase machine availability and process safety. Available accessories include covers for the connection box (part numbers 3355.200 and 3355.210), a condensate hose (12 x 2 mm, length 10 m), an air deflector, and a temperature sensor for Blue e+ series cooling units.
Mounting and Installation
Installation is carried out on the wall of the enclosure, requiring a mounting cutout of 383 mm (width) × 929 mm (height). The unit is pre-wired and connected, including mounting hardware, simplifying installation. The internal circuit protection rating is IP 55, which is dust-tight and protected against water spray, and the NEMA protection rating corresponds to UL Type 12 and UL Type 3R, suitable for industrial environments. Appropriate surge protection must be provided: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV, and for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The cooling unit offers high energy efficiency, extended component life due to gentle cooling, and intuitive operation via the e+ controller. Global usability due to multi-voltage capability and integrated condensate evaporation reduce installation and maintenance costs. Remote monitoring via the IoT interface enables proactive maintenance and increases operational safety. The use of environmentally friendly refrigerant R-1234yf contributes to reducing CO₂ equivalents, with a PCF value (Cradle-to-Gate) of 246.62 kg CO₂ eq (Category B).
Protection Rating and Operating Conditions
The IP 55 protection rating for the internal circuit ensures the unit is dust-tight and protected against water spray, making it suitable for industrial environments. The NEMA protection rating UL Type 12 and UL Type 3R meets requirements for use in protected outdoor areas. Operating temperature ranges are between -20 °C and +60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe system from -20 °C to 45 °C. Storage temperature ranges extend from -40 °C to +70 °C, enabling flexible storage. The maximum allowable operating pressure is 24 bar.