| General |
| Model | Wall mounting, Outdoor |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Aluminium AlMg3 |
| Surface protection | Powder-coated, UV-resistant pure polyester |
| Colour | RAL 7035 |
| Scope of delivery | Refrigerant with hydrophobic RiNano coating, integrated electric condensate evaporation, pre-wired (pluggable terminal block), mounting frame for universal attachment to outdoor enclosures for surface mounting, panel mounting and flush mounting, incl. mounting material |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.5 kW, Cooling capacity L35 L35/60 Hz: 1.5 kW, Cooling capacity L35 L50/50 Hz: 0.95 kW, Cooling capacity L35 L50/60 Hz: 0.95 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the partner and Rittal for the free use of the software according to these license terms. For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,7 kW |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.65 kW, Rated power L35 L35/60 Hz: 0.65 kW, Rated power L35 L50/50 Hz: 0.55 kW, Rated power L35 L50/60 Hz: 0.55 kW |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Width | 415 mm |
| Height | 990 mm |
| Depth | 280 mm |
| Device dimensions including gasket frame and design hood | Width: 467 mm, height: 1,042 mm, depth: 280 mm |
| Mounting type | Universal installation (surface mounting, partial installation, full installation) |
| Degree of protection IP according to IEC 60 529 | With mounting frame: internal circuit IP 56, without mounting frame: internal circuit IP 54 |
| NEMA degree of protection | with mounting frame: UL Type 12/3R/4, without mounting frame: UL Type 12/3R |
| Air performance (free blowing) | External circuit: 895 m³/h, Internal circuit: 700 m³/h |
| Refrigerant/cooling medium | Refrigerant: R-1234yf, Quantity: 0.77 kg, Quantity compression system: 0.48 kg, Quantity heat pipe system: 0.29 kg, Global Warming Potential (GWP): 0.5, CO₂ equivalent (CO₂e): 0 t |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.31, Cooling performance factor L35 L35 (EER) 60 Hz: 2.31 |
| Suitable for | Cabinet type: Toptec, width: ≥ 600 mm, height: ≥ 1.200 mm |
| Suitable for part no. | 9782.818, 9782.866, 9782.868, 9782.888 |
| Adjustment range | 20 °C...50 °C |
| Operating temperature range | -30 °C...60 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -30 °C...45 °C |
| Storage temperature range | -40 °C...70 °C |
| Permissible operating pressure (p max.) | 2.4 MPa |
| Sound pressure level | 67 dB(A) |
| PCF/VE (Cradle-to-Gate) | 270.15 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
Rittal SK 3485.330 is a wall-mounted cooling unit from the Blue e+ series, specifically designed for outdoor applications. It is intended for climate control of enclosures and provides a cooling capacity of 1.5 kW at an operating voltage of 110 V to 240 V (1~, 50/60 Hz) or 380 V to 480 V (3~, 50/60 Hz). The unit is designed for universal installation on outdoor enclosures, supporting mounting options including surface mounting, partial installation, and full installation. The construction is made of aluminium AlMg3 with a powder-coated, UV-resistant surface in RAL 7035. Dimensions are 415 mm (width) × 990 mm (height) × 280 mm (depth), with overall dimensions including sealing frame and design hood measuring 467 mm × 1,042 mm × 280 mm.
Applications
This cooling unit is designed for demanding environments, particularly for use with Toptec enclosures with a minimum width of 600 mm and a minimum height of 1,200 mm. It is suitable for operating temperatures from -30 °C to 60 °C, with the refrigerant circuit operating between 3 °C and 60 °C and the heat pipe system operating between -30 °C and 45 °C. Protection rating IP 56 (with mounting frame) or IP 54 (without mounting frame) according to IEC 60 529, as well as NEMA protection rating UL Type 12/3R/4 (with mounting frame) or UL Type 12/3R (without mounting frame), ensures high protection against dust and water, even in outdoor environments. Storage temperature can range from -40 °C to 70 °C.
Functions and Equipment in Detail
The unit features an integrated e+ controller, factory-set to an internal temperature of +35 °C. The adjustable range is between 20 °C and 50 °C. The integrated electrical condensate evaporation system ensures efficient removal of condensate. The condenser is coated with hydrophobic RiNano, improving condensate drainage. The cooling unit is pre-wired, equipped with a plug-in terminal strip, and supplied with a mounting frame and fastening materials. Airflow rate is 895 m³/h in the external circuit and 700 m³/h in the internal circuit.
Technology Explained Simply
Cooling capacity is measured according to DIN EN 14511 and is 1.5 kW at L35 L35 (50 Hz and 60 Hz) and 0.95 kW at L35 L50 (50 Hz and 60 Hz). Rated power is 0.7 kW, with nominal power Pel at 0.65 kW (L35 L35) or 0.55 kW (L35 L50). Energy efficiency (EER) is 2.31 at 50 Hz and 60 Hz for L35 L35 operation. Refrigerant R-1234yf is used, with a Global Warming Potential (GWP) of 0.5, resulting in a CO₂ equivalent (CO₂e) of 0 t. Maximum operating pressure is 2.4 MPa. Sound pressure level is 67 dB(A).
Compatibility and Accessories
The cooling unit is compatible with Toptec enclosures and fits article numbers 9782.818, 9782.866, 9782.868, and 9782.888. Accessories include, among others, covers for the connection box (article numbers 3355.200 and 3355.210), IoT Interface (article number 3124.300) for remote monitoring, a door position switch, a temperature sensor for Blue e+ cooling units, as well as a hygrostat and a thermostat for enclosure internal temperature control.
Mounting and Installation
Installation is carried out using the included mounting frame, enabling universal fastening to outdoor enclosures. The installation is designed for surface mounting, partial installation, and full installation. The pre-wired connection with plug-in terminal strip simplifies electrical connection. For device protection, appropriate surge protection must be provided: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
Thanks to speed-controlled components and heat pipe technology, an average energy saving of 75 % is achieved. The gentle component cooling extends the service life of components in the enclosure and in the cooling unit. Intuitive operation is provided by the e+ controller. Remote monitoring via the IoT Interface enables monitoring of device data, statuses, and system messages, increasing machine availability and process reliability. The use of refrigerant R-1234yf with a GWP of 0.5 contributes to environmental compatibility.