| General |
| Model | Roof structure |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condenser with hydrophobic RiNano coating, Integrated electric condensate evaporation, Pre-wired (pluggable terminal block), Drilling template, Mounting hardware |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1 kW, cooling capacity L35 L35/60 Hz: 1.09 kW, cooling capacity L35 L50/50 Hz: 0.8 kW, cooling capacity L35 L50/60 Hz: 0.81 kW |
| Rated operating voltage | 400 V, 2~, 50 Hz/60 Hz |
| Note | The rooftop cooling unit 3273.500 can be used for office applications due to its low noise level. |
| Rated current max. | At 50 Hz: 1.7 A, At 60 Hz: 2.2 A |
| Inrush current (max.) | At 50 Hz: 4.6 A, At 60 Hz: 5.7 A |
| Air performance (free blowing) | Outer circuit: 1,600 m³/h, Inner circuit: 491 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity ratio L35 L35 (EER) 50 Hz: 2.4, Cooling capacity ratio L35 L35 (EER) 60 Hz: 1.95 |
| Width | 597 mm |
| Height | 417 mm |
| Depth | 475 mm |
| Degree of protection IP according to EN 60 529 | External circuit: IP 34, internal circuit: IP 54 |
| Refrigerant/cooling medium | Refrigerant: R-513A, Quantity: 0.65 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.41 t |
| Electrical connection type | Plug-in terminal block |
| Working time | 100 % |
| Temperature control | e-Comfortcontroller (factory setting +35 °C) |
| Operating temperature range | 10 °C...55 °C |
| Maximum operating temperature at 60 Hz | 53 °C |
| Storage temperature range | -40 °C...70 °C |
| Adjustment range | 20 °C...53 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.42 kW, Rated power L35 L35/60 Hz: 0.56 kW, Rated power L35 L50/50 Hz: 0.48 kW, Rated power L35 L50/60 Hz: 0.65 kW |
| Permissible operating pressure (p max.) | 28 bar |
| Fuse | Transformer protection switch: 6.3...10 A |
Material: Sheet steel
Colour: RAL 7035
Protection category IP to IEC 60 529: External circuit IP 34
Internal circuit IP 54
Supply includes: Nano-coated condenser
Integral electric condensate evaporation
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts
Note: Thanks to their low noise level, the roof-mounted cooling units 3273.500 and 3273.515 are also suitable for use in office applications
Packs of: 1 pc(s).
EAN: 4028177323223
Customs tariff number: 84158200
eCl@ss 5.1: 27180704
eCl@ss 7.0: 27180704
ETIM 6.0: EC000855
Total cooling output to DIN EN 14511: L 35 L 35 at 50 Hz: 1 kW
L 35 L 35 at 60 Hz: 1.09 kW
L 35 L 50 at 50 Hz: 0.71 kW
L 35 L 50 at 60 Hz: 0.81 kW
Air throughput (unimpeded air flow): External circuit: 1600 m³/h
Internal circuit: 491 m³/h
Rated operating voltage: 400 V, 2~, 50 Hz/60 Hz
Dimensions: Width: 597 mm
Height: 417 mm
Depth: 475 mm
Temperature control: e-Comfort controller (factory setting +35°C)
Temperature range: Operation (environment): +10°C...+55°C
Setting range: +20°C...+55°C
Refrigerant/cooling medium: Refrigerant: R134a
Quantity: 650 g
Type of electrical connection: Plug-in terminal strip
Duty cycle: 100 %
Power consumption Pel: L 35 L 35 at 50 Hz: 0.39 kW
L 35 L 35 at 60 Hz: 0.45 kW
L 35 L 50 at 50 Hz: 0.42 kW
L 35 L 50 at 60 Hz: 0.54 kW
Rated current (max.): At 50 Hz: 1.7 A
At 60 Hz: 2.2 A
Start-up current max.: At 50 Hz: 4.6 A
At 60 Hz: 5.7 A
Pre-fuse: Transformer circuit-breaker: 6.3 A...10 A A
Permissible operating pressure (p. max.): 28 bar
Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511: 2.58
Weight/pack: 46 kg