| General |
| Model | Wall mounting, water-carrying parts copper/brass (Cu/CuZn) |
| Colour | RAL 7035 |
| Scope of delivery | Ready-wired, drilling template, sealing and mounting materials |
| Total cooling capacity | L 35 W 10 at 400 l/h: 3 kW |
| Rated operating voltage | 400 V, 2~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 169 W, At 60 Hz: 232 W |
| Rated current max. | At 50 Hz: 0.44 A, At 60 Hz: 0.58 A |
| Permissible operating pressure (p max.) | 1: 10 bar |
| Working time | 100 % |
| Cooling medium | Water (specification see internet) |
| Water supply temperature | 1 °C...30 °C |
| Water connections | ½" hose nozzle, G ⅜" AG |
| Conduit volume | 1,4 l |
| Temperature control | Base controller (factory setting +35 °C) |
| Operating temperature range | 1 °C...70 °C |
| Note | Integrated check valve when equipped with e-Comfort controller |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 145 mm |
| Adjustment range | 20 °C...55 °C |
| Fuse | Transformer protection switch: 3.5...5 A |
| Degree of protection IP according to EN 60 529 | IP 55 |
| NEMA degree of protection | UL Type 1, UL Type 3R, UL Type 12 |