| General |
| Model | Wall mounting, water-carrying parts copper/brass (Cu/CuZn) |
| Colour | RAL 7035 |
| Scope of delivery | Ready-wired, drilling template, sealing and mounting materials |
| Total cooling capacity | L 35 W 10 at 400 l/h: 2 kW |
| Rated operating voltage | 230 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 110 W, At 60 Hz: 140 W |
| Rated current max. | At 50 Hz: 0.49 A, At 60 Hz: 0.61 A |
| Permissible operating pressure (p max.) | 1: 10 bar |
| Working time | 100 % |
| Cooling medium | Water (specification see internet) |
| Water supply temperature | 1 °C...30 °C |
| Water connections | ½" hose nozzle, G ⅜" AG |
| Conduit volume | 0,52 l |
| Temperature control | Base controller (factory setting +35 °C) |
| Operating temperature range | 1 °C...70 °C |
| Note | Integrated check valve when equipped with e-Comfort controller |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 145 mm |
| Fuse | Circuit breaker/fuse: 4 A |
| Adjustment range | 20 °C...55 °C |
| Degree of protection IP according to EN 60 529 | IP 55 |
| NEMA degree of protection | UL Type 1, UL Type 3R, UL Type 12 |
Design: Water-carrying parts, copper/brass (Cu/CuZn)
Colour: RAL 7035
Protection category IP to IEC 60 529: IP 55
Supply includes: Fully wired ready for connection (plug-in terminal strip)
Drilling template
Sealing and assembly parts
Note: Integral non-return valve for version with e-Comfort controller
Packs of: 1 pc(s).
EAN: 4028177495678
Customs tariff number: 84158300
eCl@ss 5.1: 27180712
eCl@ss 7.0: 27180712
ETIM 6.0: EC002515
Total cooling output: L 35 W 10 at 400 l/h: 2 kW
Air throughput (unimpeded air flow): Internal circuit at 50 Hz: 880 m³/h
Internal circuit at 60 Hz: 950 m³/h
Rated operating voltage: 230 V, 1~, 50 Hz/60 Hz
Dimensions: Width: 400 mm
Height: 950 mm
Depth: 145 mm
Temperature control: Basic controller (factory setting +35°C)
Temperature range: Operation (environment): +1°C...+70°C
Setting range: +20°C...+55°C
Water inlet: +1°C...+30°C
Refrigerant/cooling medium: Cooling medium: Water (see Internet for specifications)
Duty cycle: 100 %
Power consumption Pel: At 50 Hz: 110 W
At 60 Hz: 140 W
Rated current (max.): At 50 Hz: 0.49 A
At 60 Hz: 0.61 A
Pre-fuse: Miniature circuit-breaker/fuse: 4 A
Permissible operating pressure (p. max.): 1 bar - 10 bar
Water connections: ½" connector sleeve
G ?" external thread
Weight/pack: 20 kg