| General |
| Model | Wall surface mounted |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condenser with hydrophobic RiNano coating, pre-wired (pluggable terminal block), drilling template, mounting material |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/60 Hz: 0.6 kW, Cooling capacity L35 L50/60 Hz: 0.35 kW |
| Rated operating voltage | 115 V, 1~, 60 Hz |
| Rated current max. | At 60 Hz: 5.7 A |
| Inrush current (max.) | At 60 Hz: 11.5 A |
| Air performance (free blowing) | External circuit: 345 m³/h, Internal circuit: 280 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity factor L35 L35 (EER) 60 Hz: 1.36 |
| Width | 280 mm |
| Height | 550 mm |
| Depth | 210 mm |
| Degree of protection IP according to EN 60 529 | External circuit: IP 34, internal circuit: IP 54 |
| NEMA degree of protection | UL Type 12 |
| Refrigerant/cooling medium | Refrigerant: R-513A, Quantity: 0.19 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.12 t |
| Temperature control | e-Comfortcontroller (factory setting +35 °C) |
| Operating temperature range | 10 °C...55 °C |
| Maximum operating temperature at 60 Hz | 54 °C |
| Storage temperature range | -40 °C...70 °C |
| Adjustment range | 20 °C...54 °C |
| Rated power Pel | Rated power L35 L35/60 Hz: 0.44 kW, Rated power L35 L50/60 Hz: 0.5 kW |
| Permissible operating pressure (p max.) | 28 bar |
| Fuse | Circuit breaker/fuse: 10 A |
Material: Sheet steel
Colour: RAL 7035
Protection category IP to IEC 60 529: External circuit IP 34
Internal circuit IP 54
Supply includes: Nano-coated condenser
Fully wired ready for connection (plug-in terminal strip)
Drilling template
Assembly parts
Packs of: 1 pc(s).
EAN: 4028177322837
Customs tariff number: 84158200
eCl@ss 5.1: 27180704
eCl@ss 7.0: 27180704
ETIM 6.0: EC000855
Total cooling output to DIN EN 14511: L 35 L 35 at 60 Hz: 0.66 kW
L 35 L 50 at 60 Hz: 0.4 kW
Air throughput (unimpeded air flow): External circuit: 345 m³/h
Internal circuit: 280 m³/h
Rated operating voltage: 115 V, 1~, 60 Hz
Dimensions: Width: 280 mm
Height: 550 mm
Depth: 210 mm
Temperature control: e-Comfort controller (factory setting +35°C)
Temperature range: Operation (environment): +10°C...+55°C
Setting range: +20°C...+55°C
Refrigerant/cooling medium: Refrigerant: R134a
Quantity: 170 g
Power consumption Pel: L 35 L 35 at 60 Hz: 0.5 kW
L 35 L 50 at 60 Hz: 0.53 kW
Rated current (max.): At 60 Hz: 5.7 A
Start-up current max.: At 60 Hz: 11.5 A
Pre-fuse: Miniature circuit-breaker/fuse: 10 A
Permissible operating pressure (p. max.): 28 bar
Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511: 1.4
Weight/pack: 17 kg